[R.O. 2007 § 504.010; Ord. No. 4626 §§ 1—2, 9-14-2006; Ord.
No. 5543 §§ 1—2 (Exh. A(504.010)), 2-10-2011; Ord. No. 6958, 5-10-2018]
The 2015 International Residential Code® for One- and Two-Family Dwellings, as published by the International Code Council®, Inc., as amended, is hereby adopted as the Residential Code for One- and Two-Family Dwellings of the City; and all of the regulations, provisions, penalties, conditions, and terms of the 2015 International Residential Code® for One- and Two-Family Dwellings, as published by the International Code Council®, Inc., are hereby referred to, adopted and made part thereof, as if fully set out in this Chapter, with additions, insertions, deletions, and changes prescribed in this Chapter. Included Appendices (A, B, C, D, E, G, K, M, N, P) as amended under Section 504.040.
[R.O. 2007 § 504.020; Ord. No. 4626 §§ 1—2, 9-14-2006; Ord.
No. 5543 §§ 1—2 (Exh. A(504.020)), 2-10-2011]
Throughout the Residential Code for One- and Two-Family Dwellings adopted in Section 504.010, wherever the term "Name of Jurisdiction" or "Local Jurisdiction" appears, it shall be deemed to mean the City of St. Peters, Missouri.
[R.O. 2007 § 504.030; Ord. No. 4626 §§ 1—2, 9-14-2006; Ord.
No. 5543 §§ 1—2 (Exh. A(504.030)), 2-10-2011]
Throughout the Residential Code for One- and Two-Family Dwellings adopted in Section 504.010, wherever the term "Code Official" or "Building Official" is used, it is deemed to mean the Building Commissioner.
[Ord. No.
5543 §§ 1—2 (Exh. A(504.031)), 2-10-2011; Ord.
No. 5603 § 1, 6-23-2011]
Throughout the Residential Code For One- and Two-Family Dwellings adopted in Section 504.010, wherever the term "International Building Code" is used, it is deemed to mean St. Peters Building Code Chapter 505, wherever the term "ICC Electrical Code" is used, it is deemed to mean St. Peters Electrical Code Chapter 510, wherever the term "International Fuel Gas Code" is used, it is deemed to mean St. Peters Fuel Gas Code Chapter 516, wherever the term "International Mechanical Code" is used, it is deemed to mean St. Peters Mechanical Code Chapter 515, wherever the term "International Plumbing Code" is used, it is deemed to mean St. Peters Plumbing Code Chapter 520, wherever the term "International Property Maintenance Code" is used, it is deemed to mean St. Peters Property Maintenance Code Chapter 525, wherever the term "International Fire Prevention Code" is used, it is deemed to mean St. Peters Fire Prevention Code Chapter 507.
[R.O. 2007 § 504.040; Ord. No. 4626 §§ 1—2, 9-14-2006; Ord.
No. 5305 §§ 1—2, 12-17-2009; Ord. No. 5543 §§ 1—2 (Exh. A(504.040)), 2-10-2011; Ord. No. 5603 § 1, 6-23-2011; Ord. No. 6958, 5-10-2018]
A.
The Code adopted in Section 504.010 is amended as follows:
1.
101.1 Title. These provisions shall
be known as the Residential Code for One- and Two-Family Dwelling
of the City of St. Peters, and shall be cited as such and will be
referred to herein as "this code."
2.
101.2.1 Application Of Prior Codes.
At the discretion of the City Administrator of the City of St. Peters,
contractors may be allowed to complete residential construction under
prior building codes, if the City should adopt new code(s) during
active construction of the subdivision.
4.
Appendix A. Sizing and Capacities of Gas Piping (Refer to Chapter 516 of the Municipal Code of the City of St. Peters).
5.
Appendix B. Sizing of Venting Systems Serving Appliances Equipped with Draft Hoods, Category I Appliances, and Appliances Listed for Use with Type B Vents (Refer to Chapter 516 of the Municipal Code of the City of St. Peters).
6.
Appendix C. Exit Terminals of Mechanical Draft and Direct-Vent Venting Systems (Refer to Chapter 516 of the Municipal Code of the City of St. Peters).
7.
Appendix D. Recommended Procedure for Safety Inspection of an Existing Appliance Installation (Refer to Chapter 516 of the Municipal Code of the City of St. Peters).
8.
Appendix E. Manufactured Housing
Used as Dwellings.
AE101.1 General. Factory-built structures, modular units or closed prefabricated assemblies shall not be acceptable unless they are built within the jurisdiction of the City of St. Peters and are subject to inspection by the Code Official, with the exception of a manufactured home, modular unit, or closed prefabricated assemblies used as a single dwelling unit, and installed per Section 405.170, "R-M" Mobile/Modular Home Residential District. These provisions shall be applicable only to the above described manufactured home, modular unit, or closed prefabricated assemblies used as a single dwelling unit in the "R-M" Mobile/Modular Home Residential District:
| |
1.
|
Construction, alteration and repair
of any foundation system, which is necessary to provide for the installation
of a manufactured home unit.
|
2.
|
Construction, installation, addition,
alteration, repair or maintenance of the building service equipment
which is necessary for connecting manufactured homes to water, fuel,
or power supplies and sewage systems.
|
3.
|
Alterations, additions or repairs
to existing manufactured home. The construction, alteration, moving,
demolition, repair and use of accessory buildings and structures and
their building service equipment shall comply with the requirement
of the codes adopted by this jurisdiction.
|
These provisions shall not be applicable
to the design and construction of manufactured homes and shall not
be deemed to authorize either modification or additions to manufactured
homes where otherwise prohibited.
| |
Exception: New and replacement manufactured homes to be located in flood hazard areas are subject to Chapter 410, Floodplain Management of the Municipal Code of the City of St. Peters.
| |
AE304.1 Permit Fees. (Refer to Attachment
1, Title V, Appendix A of the Municipal Code of the City of St. Peters.)
| |
AE304.2 — Delete.
| |
AE304.3 — Delete.
| |
AE304.3.1 — Delete.
| |
AE304.3.2 — Delete.
| |
AE304.3.2.1 — Delete.
| |
AE304.3.2.2 — Delete.
| |
AE304.3.3 — Delete.
| |
AE304.3.3.1 — Delete.
| |
AE304.3.3.2 — Delete.
| |
AE304.3.3.3 — Delete.
|
9.
Appendix F. — Delete.
10.
Appendix G. — (No Changes).
11.
Appendix H. — Delete.
12.
Appendix I. — Delete.
13.
Appendix J. — Delete.
14.
Appendix K. — (No Changes).
15.
Appendix L. — Delete.
16.
Appendix M. — (No Changes).
17.
Appendix N. — (No Changes).
18.
Appendix O. — Delete.
19.
Appendix P. — (No Changes).
20.
Appendix Q. — Delete.
21.
Appendix R. — Delete.
22.
Appendix S. — Delete.
23.
Appendix T. — Delete.
24.
Appendix U. — Delete.
25.
R105.2 Work Exempt From Permit. Permits
shall not be required for the following. Exemption from permit requirements
of this code shall not be deemed to grant authorization for any work
to be done in any manner in violation of the provisions of this code
or any other laws or ordinances of this jurisdiction.
Building:
| |
1.
|
One-story detached accessory structures
used as tool and storage sheds, playhouses and similar uses, provided
the floor area does not exceed one hundred twenty (120) square feet
(11.15 m2).
|
2.
|
Fences not over six (6) feet (1,829
mm) high.
|
3.
|
Retaining walls that are not over
four (4) feet (1,219 mm) in height measured from the lowest adjacent
grade to top of the wall, unless supporting a surcharge or impounding
Class I, II or IIIA liquids.
|
4.
|
Water tanks supported directly upon
grade if the capacity does not exceed five thousand (5,000) gallons
(18,927 L) and the ratio of height to diameter or width does not exceed
two to one (2:1).
|
5.
| |
6.
|
Painting, papering, tiling, carpeting,
cabinets, counter tops and similar finish work.
|
7.
|
Prefabricated swimming pools that
are less than twenty-four (24) inches (610 mm) deep.
|
8.
|
Swings and other playground equipment.
|
9.
|
Window awnings support by an exterior
wall which do not project more than fifty-four (54) inches (372 mm)
from the exterior wall and do not require additional support.
|
Electrical:
| |
1.
|
Listed cord-and-plug connected temporary
decorative lighting.
|
2.
|
Reinstallation of attachment plug
receptacles but not the outlets thereof.
|
3.
|
Replacement of branch circuit overcurrent
devices of the required capacity in the same location.
|
4.
|
Electrical wiring, devices, appliances,
apparatus or equipment operating at less than twenty-five (25) volts
and not capable of supplying more than fifty (50) watts of energy.
|
5.
|
Minor repair work, including the
replacement of lamps or the connection of approved portable electrical
equipment to approved permanently installed receptacles.
|
Gas:
| |
1.
|
Portable heating, cooking or clothes
drying appliances.
|
2.
|
Replacement of any minor part that
does not alter approval of equipment or make such equipment unsafe.
|
3.
|
Portable-fuel-cell appliances that
are not connected to a fixed piping system and are not interconnected
to a power grid.
|
Mechanical:
| |
1.
|
Portable heating appliances.
|
2.
|
Portable ventilation appliances.
|
3.
|
Portable cooling units.
|
4.
|
Steam, hot- or chilled-water piping
within any heating or cooling equipment regulated by this code.
|
5.
|
Replacement of any minor part that
does not alter approval of equipment or make such equipment unsafe.
|
6.
|
Portable evaporative coolers.
|
7.
|
Self-contained refrigeration systems
containing ten (10) pounds (4.54 kg) or less of refrigerant or that
are actuated by motors of one (1) horsepower (746 W) or less.
|
8.
|
Portable-fuel-cell appliances that
are not connected to a fixed piping system and are not interconnected
to a power grid.
|
Plumbing:
| |
1.
|
The stopping of leaks in drains,
water, soil, waste or vent pipe; provided, however, that if any concealed
trap, drainpipe, water, soil, waste or vent pipe becomes defective
and it becomes necessary to remove and replace the same with new material,
such work shall be considered as new work and a permit shall be obtained
and inspection made as provided in this code.
|
2.
|
The clearing of stoppages or the
repairing of leaks in pipes, valves or fixtures, and the removal and
reinstallation of water closets, provided such repairs do not involve
or require the replacement or rearrangement of valves, pipes or fixtures.
|
26.
R105.10 Integrated Permits. The Code
Official may issue integrated building, plumbing, mechanical, electrical,
etc., permits on a single permit application.
27.
R106.1.1.1 Sprinkler Verification.
All applications for permit for one- and two-family dwellings shall
include a written verification by the builder affirming that a fire
sprinkler system was offered to the purchaser prior to entering into
the purchase contract in conformance with Section R325.1 of this code.
If there is no purchaser at the time of the permit application submittal,
then said verification shall be made as soon as there is a purchaser
and prior to the issuance of a certificate of occupancy for the new
residence.
28.
R106.3.1 Approval Of Construction
Documents. Where the Code Official issues a permit, the construction
documents shall be approved, in writing, or by a stamp that states
"REVIEWED FOR CODE COMPLIANCE." One (1) set of construction documents
so reviewed shall be retained by the Code Official. The other set
may be kept at the site of work or made available at the time of inspection
and shall be open to inspection by the Code Official or a duly authorized
representative.
29.
R108.2 Fee Schedule. (See Appendix
A of this Title).
30.
R108.2.1 Amount Due Or Refunds. The
Code Official shall authorize the refunding of money. The collection
of fees due to the City and the refunding of money shall be as follows:
1.
Refund the full amount of any fee
paid hereunder which was erroneously paid or collected.
2.
Refund ninety percent (90%) or collect
ten percent (10%) of the permit fee when no work has been done on
the site and application required a plan review to process a permit.
3.
Refund eighty percent (80%) or collect
twenty percent (20%) of the permit fee when no work has been done
on the site and application required a plan review to process a permit.
4.
No refund if permit has been voided;
if work has been stopped; or if any work has been done at the site.
The Code Official shall not authorize
the refunding of any fee paid, except upon written application filed
by the original permittee not later than one hundred eighty (180)
days after the date of fee payment.
|
31.
R108.6 Work Commencing Before Permit
Issuance. Any person who commences work requiring a permit on a building,
structure, electrical, gas, mechanical or plumbing system before obtaining
the necessary permits shall be subject to a fee as set out in Appendix
A of this Title. A fee may be assessed for each additional inspection
that shall be in addition to the required permit fees.
Exception: Stakeouts and other necessary
planning procedures.
32.
R109.5 Supplemental Inspection. In
addition to the required inspection heretofore specified, the Code
Official may make other inspections, which in his/her judgment is
reasonably necessary due to unusual construction or circumstances.
The Code Official shall have the authority to inspect any construction
work in order to ascertain whether compliance with the Building Code
is being met and in order that he/she may properly enforce the rules
promulgated by this code. These inspections may include but are not
limited to examinations to determine whether zoning requirements are
being met, and may include all other phases of building construction.
A fee as set out in Appendix A of this Title may be assessed for each
additional inspection.
33.
R109.6 Extra Inspection. If by judgment
of the Code Official an inspection requested is not ready or accessible
for inspection, or in the judgment of the Code Official the applicant
has caused the City extra inspections other than typically required,
a fee as set out in Appendix A of this Title may be assessed for each
additional inspection or re-inspection.
34.
R110.1 Use And Occupancy. A building or structure shall not
be used or occupied, and a change in the existing use or occupancy
classification of a building or structure or portion thereof shall
not be made until the building official has issued a certificate of
occupancy therefor as provided herein. Issuance of a certificate of
occupancy shall not be construed as an approval of a violation of
the provisions of this code or of other ordinances of the jurisdiction.
Certificates presuming to give authority to violate or cancel the
provisions of this code or other ordinances of the jurisdiction shall
not be valid.
[Ord. No. 7490, 8-26-2021[1]]
Exceptions:
|
1. Work exempt from permits under Section R105.2.
|
2. Accessory building or structures.
|
35.
R110.1.1 Use And Occupancy — Non- Owner-Occupied Dwelling
Units. A dwelling unit shall not be occupied upon a change in occupancy
thereof, nor shall any owner or agent thereof permit, allow, or cause
any dwelling unit to be occupied upon a change in occupancy thereof,
until the building official has issued a reoccupancy permit therefor
as provided herein. A reoccupancy permit shall be required on each
change of occupancy of a dwelling unit.
[Ord. No. 7490, 8-26-2021]
36.
R110.1.2 Applications And Issuance Of Reoccupancy Permit.
[Ord. No. 7490, 8-26-2021]
R110.1.2.1 Applications.
| |
Prior to the occupancy of a dwelling unit upon a change in occupancy
thereof, the owner of such dwelling unit shall make written application
to the building official for a reoccupancy permit on a form to be
furnished by the City for that purpose. Such application shall include
such information as necessary to administer and enforce the provisions
of, and to ensure compliance with, the provisions of Section 110.1.2.2.1
of this code.
| |
R110.1.2.2 Action on Application.
| |
The building official shall examine or cause to be examined
applications for reoccupancy permits and amendments thereto, and shall
inspect or cause to be inspected each dwelling unit to be covered
by the reoccupancy permit and all common areas thereto, if any, within
a reasonable time after filing, before a reoccupancy permit is issued.
| |
R110.1.2.2.1 Reoccupancy Inspections.
| |
The building official is authorized to and may make reoccupancy inspections of the dwelling unit to be covered by the reoccupancy permit and all common areas thereto, if any, upon a change in occupancy thereof. Such reoccupancy inspections shall be for the purpose of determining whether such dwelling unit and all common areas thereto, if any, comply with the provisions of the City of St. Peters, Missouri, Zoning and Subdivision Codes, as amended, the St. Peters Property Maintenance Code, as amended, and Chapter 215 of the St. Peters City Code, as amended. For purpose of making the reoccupancy inspection, the building official is authorized to enter, examine and survey the dwelling unit and all common areas thereto, if any, by appointment with the knowledge of the owner thereof, and, if occupied, the tenant. Should any owner, tenant, occupant or other person in charge of a dwelling unit, the common areas thereto, or building or structure fail or refuse to permit free access and entry to the dwelling unit and all common areas, if any, under control for any reoccupancy inspection pursuant to this Code, then the building official may seek a search warrant or other appropriate court order authorizing such reoccupancy inspections. Under this Section, common areas shall not be subject to independent inspection but shall only be inspected in conjunction with the reoccupancy inspection of a dwelling unit.
| |
R110.1.2.3 Reoccupancy Permit And Inspection Fees.
| |
At the time of filing an application for a reoccupancy permit,
a reoccupancy permit and inspection fee as set out in Appendix A of
this Title shall be charged and collected. No reoccupancy permit shall
be valid until such reoccupancy permit and inspection fee as set out
in Appendix A of this Title has been paid.
| |
R110.1.2.4 Issuance of Reoccupancy Permit.
| |
If, upon completion of the reoccupancy inspection of the dwelling unit and the common areas thereto, if applicable, the building official finds that the dwelling unit is in compliance with the City of St. Peters, Missouri, Zoning and Subdivision Codes, as amended, the St. Peters Property Maintenance Code, as amended, and Chapter 215 of the St. Peters City Code, as amended, the building official shall, as soon as practicable, issue a reoccupancy permit therefor which shall contain at least the following:
| |
1.
|
The reoccupancy permit number;
|
2.
|
The address of the principal building or structure to which
the subject dwelling unit is located;
|
3.
|
The name and address of the owner;
|
4.
|
A description of the dwelling unit and common areas, if applicable,
for which the reoccupancy permit is issued;
|
5.
|
A statement that the described dwelling unit and common areas,
if applicable, have been inspected for compliance with the requirements
of this Code;
|
6.
|
The date of such reoccupancy inspection;
|
7.
|
The name of the building official;
|
8.
|
The edition of the code under which the permit was issued;
|
9.
|
If an automatic sprinkler system is provided and whether the
sprinkler system is required; and
|
10.
|
Any special stipulations and conditions of the reoccupancy permit.
|
If the building official finds that the dwelling unit is not in compliance with any requirement of the City of St. Peters, Missouri, Zoning and Subdivision Codes, as amended, the St. Peters Property Maintenance Code, as amended, or Chapter 215 of the St. Peters City Code, or any combination or combinations thereof, have not been met or if a violation is found, the building official shall transmit or cause to be transmitted to the owner a written denial specifying the defect(s) or violation(s), or both. If a defect or violation is found, the owner shall be given a reasonable length of time to make repairs and bring the dwelling unit or common areas, if applicable, or both, into compliance prior to reinspection. No final reoccupancy permit shall be issued until the dwelling unit and the common areas thereto, if applicable, complies or comply with the requirements of Section R110.1.2.2.1. Issuance of a reoccupancy permit shall not be construed as an approval of a violation of the provisions of this code or of other ordinances of the City. Reoccupancy permits presuming to give authority to violate or cancel the provisions of this code or other ordinances of the City shall not be valid.
|
37.
R110.1.3 Suspension Or Revocation. The building official is
authorized to, and the building official shall, in writing, suspend
or revoke a reoccupancy permit issued under the provisions of this
code wherever the reoccupancy permit is issued in error or on the
basis of incorrect, inaccurate or incomplete information, or in violation
of any ordinance or regulation or any of the provisions of this Code,
as amended.
[Ord. No. 7490, 8-26-2021]
38.
R110.1.4 Exceptions.
[Ord. No. 7490, 8-26-2021]
The provisions of Sections R110.1.1 to R110.1.3 hereof shall
not apply to the following:
| |
1.
|
Lawful occupancies existing at the time of the effective date
of such Sections; or
|
2.
|
An owner-occupied dwelling unit used exclusively for residential
purposes, and wherein no home occupation is conducted. For purposes
of Sections R110.1.1 to R110.1.3, the term "owner-occupied dwelling
unit" shall mean a dwelling unit for which the occupant thereof is
expressly named as an owner of the dwelling unit, or is a trustee
or beneficiary of a trust that is expressly named as an owner of the
dwelling unit, all as indicated upon the deed of record on file in
the Office of the Recorder of Deeds of St. Charles County, Missouri.
|
39.
R112 Board Of Appeals. (Refer to Chapter 410 of Title IV: Land Use).
R112.1 — Delete.
R112.2 — Delete.
R112.3 — Delete.
R112.4 — Delete.
40.
R113.4 Violations, Penalties. Any
person who shall violate a provision of this code or shall fail to
comply with any requirement thereof or who shall erect, construct,
alter or repair a building or structure in violation of approved construction
documents or directive of the Code Official, or of a permit or certificate
issued under the provisions of this code, shall be guilty of an offense.
Each day that a violation continues after due notice has been served
shall constitute a separate offense.
41.
R114.2 Unlawful Continuance. Any
person who shall continue any work in or about the structure after
having been served with a stop work order, except such work that person
is directed to perform to remove a violation or unsafe condition,
shall be guilty of an offense.
42.
PERSON
ROUGH-IN
R202 Definitions. Amend.
An individual, heirs, executors, trustee, administrators
or assigns, its or their successors or assigns, or the agent of any
of the aforesaid. The term "person" shall also mean a firm, partnership,
copartnership, company, corporation, association, joint stock company,
joint venture, trust, estate, organization or combination of individuals,
of any kind, character, form or nature whatsoever, its or their successors
or assigns, or an officer, manager, member, partner, employee, executor,
trustee, administrator or agent of any of the aforesaid.
[Ord. No. 7490, 8-26-2021]
The installation of all parts of the plumbing system that
must be completed prior to covering from view. This includes DWV,
water supply and built-in fixture supports. DWV shall be the minimum
installation in an unfinished area.
43.
R302.1 Exterior Walls. Construction,
projections, openings and penetrations of exterior walls of dwellings
and accessory building shall comply with Table R302.1(1); or dwellings
equipped throughout with an automatic sprinkler system installed in
accordance with Section P2904 shall comply with Table R302.1(2).
Exceptions:
1.
|
Walls, projects, openings or penetrations
in walls perpendicular to the line used to determine the fire separation
distance.
|
2.
|
Walls of dwellings and accessory
structures located on the same lot.
|
3.
|
Detached tool shed and storage sheds,
playhouses and similar structures exempted from permits are not required
to provide wall protection based on location on the lot. Projections
beyond the exterior wall shall not extend over the lot line.
|
4.
|
Detached garages accessory to a dwelling
located within two (2) feet (610 mm) of a lot line are permitted to
have roof eave projections not exceeding four (4) inches (102 mm).
|
5.
|
Foundation vents installed in compliance
with this code are permitted.
|
6.
|
Cantilevered manufactured fireplaces.
|
7.
|
Uncovered decks.
|
44.
R302.2 Townhouses. Common walls separating
townhouses shall be assigned a fire-resistance rating in accordance
with Section R302.2, Item 1 or 2. The common wall shared by two (2)
townhouses shall be constructed without plumbing or mechanical equipment,
ducts or vents in the cavity of the common wall. The wall shall be
rated for fire exposure from both sides and shall extend to and be
tight against exterior walls and the underside of the roof sheathing.
Electrical installations shall be in accordance with Chapter 34 through
43. Penetrations of the membrane of common walls for electrical outlet
boxes shall be in accordance with Section R302.4.
1.
|
Where a fire sprinkler system in
accordance with Section P2904 is provided, the common wall shall be
not less than a one-hour fire-resistance-rated wall assembly tested
in accordance with ASTM E 119 or UL 263.
|
2.
|
Where a fire sprinkler system in
accordance with Section P2904 is not provided, the common wall shall
be not less than a two-hour fire-resistance-rated wall assembly tested
in accordance with ASTM E 119 or UL 263, or the common wall shall
be two (2) independent one-hour fire-resistance-rated wall assemblies.
|
45.
R302.5.1 Opening Protection. Openings
from a private garage directly into a room used for sleeping purposes
shall not be permitted. Other openings between the garage and residence
shall be equipped with solid wood doors not less than one and three-eighths
(1 3/8) inches (35 mm) in thickness, solid or honeycomb-core
steel doors not less than one and three-eighths (1 3/8) inches
(35 mm) thick, or twenty-minute fire-rated doors.
46.
R302.13 Fire Protection Of Floors.
Floor assemblies that are not required elsewhere in this code to be
fire-resistance rated, shall be provided with one-half (1/2) inch
(12.7 mm) gypsum wallboard membrane, five-eighths (5/8) inch (16 mm)
wood structural panel membrane, or equivalent on the underside of
the floor framing member. Penetrations or openings for ducts, vents,
electrical outlets, lighting, devices, luminaires, wires, speakers,
drainage, piping and similar openings or penetrations shall be permitted.
Fire blocking, draft stopping, fire taping, and/or additional framing
is not required.
Exceptions:
1.
|
Floor assemblies located directly
over a space protected by an automatic sprinkler system in accordance
with Section P2904, NFPA 13D, or other approved equivalent sprinkler
system.
| |
2.
|
Floor assemblies located directly
over a crawl space not intended for storage or fuel-fired appliances.
| |
3.
|
Portions of floor assemblies shall
be permitted to be unprotected where complying with the following:
| |
3.1
|
The aggregate area of the unprotected
floor assembly does not exceed one hundred (100) square feet per HVAC
zone.
| |
3.2
|
Areas of the floor assembly covered
by HVAC metal plenum, trunk lines, and steel structural beams shall
be considered protected. Gypsum wallboard membrane shall be within
two (2) inches of all previously listed items.
| |
4.
|
Wood floor assemblies using dimension
lumber or structural composite lumber equal to or greater than two
(2) inch by ten (10) inch (50.8 mm by 254 mm) nominal dimension, or
other approved floor assemblies demonstrating equivalent fire performance.
|
47.
R303.4 Mechanical Ventilation. Where
the air infiltration rate of a dwelling unit is less than five (5)
air changes per hour where tested with a blower door at a pressure
of two-tenths (0.2) inch w.c (50 Pa) in accordance with Section N1102.4.1.2,
the dwelling unit shall be provided with whole-house mechanical ventilation
in accordance with Section M1507.3.
48.
R303.5.2 Exhaust Openings. Exhaust
air shall not be directed below six (6) feet and eight (8) inches
onto public walkways.
49.
R303.8 Exterior Stairway Illumination.
Exterior stairways shall be provided with an artificial light source.
Exterior stairways providing access to a basement from the outdoor
grade level shall be provided with an artificial light sources located
at the bottom landing of the stairway.
50.
R306.5 Hose Bib. Every dwelling unit
shall provide a minimum of one (1) frost-proof hose bib, which shall
be protected from backflow per Section P2902.4.3.
51.
R306.6 Floor Drain. All basements
and laundry areas shall have a floor drain.
52.
R309.5 Fire Sprinklers. Private garages
shall be protected by fire sprinklers where the garage wall has been
designed based on Table 302.1(2), Footnote a, and the homeowner has
opted to purchase a fire sprinkler system for their resident, as per
Missouri Revised Statutes Section 67.281. Sprinklers in garages shall
be connected to an automatic sprinkler system that complies with Section
P2904. Garage sprinklers shall be residential sprinklers or quick-response
sprinklers, designed to provide a density of 0.05 gpm/ft2. Garage doors shall not be considered obstructions
with respect to sprinkler placement.
53.
Floors And Landings At Exterior Doors.
There shall be a landing or floor at each side of each exterior door.
The width of each landing shall not be less than the door served.
Every landing shall have a dimension of not less than thirty-six (36)
inches (914 mm) measured in the direction of travel. The slope at
exterior landings shall not exceed one fourth (1/4) unit vertical
in twelve (12) units horizontal two percent (2%).
Exceptions:
1.
|
Exterior balconies less than sixty
(60) square feet (5.6 m2) and only accessible
from a door are permitted to have a landing less than thirty-six (36)
inches (914 mm) measured in the direction of travel.
|
2.
|
Doors that are not required egress
doors and are served by a stairway of no more than four (4) risers.
|
3.
|
Doors protected by a guard in accordance
with this code.
|
4.
|
Doors protected in a manner approved
by the Code Official.
|
54.
R311.3.2. Floor Elevations For Other
Exterior Doors. Doors other than the required egress door shall be
provided with landings or floors not more than seven and three-fourths
(7 3/4) inches (196 mm) below the top of the threshold.
Exception: A top landing is not required
where a stairway of four (4) or fewer risers is located on the exterior
side of the door, provided the door does not swing over the stairway.
55.
R311.3.2.1 Future Deck/Balcony. Doors
installed for a future deck/balcony with raised floor surface more
than thirty (30) inches (762 mm) above grade shall be protected in
accordance with Section R312, or made inoperable to open more than
four (4) inches clear.
56.
R312.3 Opening Limitations. Required
guards shall not have openings from the walking surface to the required
guard height which allow passage of a sphere four (4) inches (102
mm) in diameter. Guards shall not have an ornamental pattern or horizontal
rails that would provide a ladder effect, as determined by the Code
Official.
Exceptions:
1.
|
The triangular openings at the open
side of a stair, formed by the riser, tread and bottom rail of a guard,
shall not allow passage of a sphere six (6) inches (153 mm) in diameter.
|
2.
|
Guards on the open sides of stairs
shall not have openings which allow passage of a sphere four and three-eighths
(4 3/8) inches (111 mm) in diameter.
|
57.
R313.1 Townhouse Automatic Fire Sprinkler
Systems. Notwithstanding the provisions of the Building Code and International
Residential Code, as amended and adopted by the City of St. Peters,
Missouri, a builder of one- or two-family dwellings shall offer to
any purchaser on or before the time of entering into the purchase
contract the option, at the purchaser's cost, to install or equip
fire sprinklers in the dwelling, residence, or unit. Notwithstanding
any other provision of law to the contrary, no purchaser of such a
one- or two-family dwelling shall be denied the right to choose or
decline to install a fire sprinkler system in such dwelling or residence
being purchased.
58.
R313.1.1 Additions And Alterations
To Townhouses With Existing Automatic Fire Sprinkler Systems. An automatic
residential fire sprinkler system shall be designed and installed
per Section R313.1.2.
Exception: An automatic residential
fire sprinkler system shall not be required when additions or alterations
are made to existing townhouses that do not have an automatic residential
fire sprinkler system installed.
59.
R313.1.2 Design And Installation.
Automatic residential fire sprinkler systems for townhouses shall
be designed and installed in accordance with Section P2904 or NFPA
13D.
60.
R313.2 One- And Two-Family Dwelling
Automatic Fire Systems. Notwithstanding the provisions of the Building
Code and International Residential Code, as amended and adopted by
the City of St. Peters, Missouri, a builder of one- or two-family
dwellings shall offer to any purchaser on or before the time of entering
into the purchase contract the option, at the purchaser's cost, to
install or equip fire sprinklers in the dwelling, residence, or unit.
Notwithstanding any other provision of law to the contrary, no purchaser
of such a one- or two-family dwelling shall be denied the right to
choose or decline to install a fire sprinkler system in such dwelling
or residence being purchased.
Exception: An automatic residential
fire sprinkler system shall not be required for additions or alterations
to existing buildings that are not already provided with an automatic
residential fire sprinkler system.
61.
R313.2.1 Additions And Alterations
To One- And Two-Family Dwellings With Existing Automatic Fire Sprinkler
Systems. An automatic residential fire sprinkler system shall be designed
and installed per Section R313.2.2.
62.
R313.2.2 Design And Installation.
Automatic residential fire sprinkler systems shall be designed and
installed in accordance with Section P2904 or NFPA 13D.
63.
R315.2 Alterations, Repairs And Additions.
When alterations, repairs or additions requiring a permit occur, or
when one (1) or more sleeping rooms are added or created in existing
dwellings, the individual dwelling unit shall be provided with carbon
monoxide alarms in accordance with Section 315.1.
Exceptions:
1.
|
Work involving the exterior surfaces
of dwellings, such as the replacement of roofing or siding, or the
addition or replacement of windows or doors, or the addition of a
porch or deck, are exempt from the requirements of this Section.
|
2.
|
Installation, alteration or repairs
of plumbing or mechanical systems are exempt from the requirements
of this Section.
|
64.
R322 Flood-Resistant Construction. Refer to Chapter 410 Floodplain Management of the Municipal Code of the City of St. Peters.
R322.1 — Delete.
|
R322.1.1 — Delete.
|
R322.1.2 — Delete.
|
R322.1.3 — Delete.
|
R322.1.4 — Delete.
|
R322.1.4.1 — Delete.
|
R322.1.4.2 — Delete.
|
R322.1.5 — Delete.
|
R322.1.6 — Delete.
|
R322.1.7 — Delete.
|
R322.1.8 — Delete.
|
R322.1.9 — Delete.
|
R322.1.10 — Delete.
|
R322.2 — Delete.
|
R322.2.1 — Delete.
|
R322.2.2 — Delete.
|
R322.2.2.1 — Delete.
|
R322.2.3 — Delete.
|
R322.2.4 — Delete.
|
R322.3 — Delete.
|
R322.3.1 — Delete.
|
R322.3.2 — Delete.
|
R322.3.3 — Delete.
|
R322.3.4 — Delete.
|
R322.3.5 — Delete.
|
R322.3.5.1 — Delete.
|
R322.3.6 — Delete.
|
R322.3.7 — Delete.
|
65.
403.1.1 Minimum Size. The minimum
width, W, and thickness, T, for concrete footings shall be in accordance
with Tables R403.1(1) through R403.1(4) and Figure R403.1(1) or R403.1.3,
as applicable. The footing width shall be based on the load-bearing
value of the soil in accordance with Table R401.4.1. Footing projects,
P, shall not be less than two (2) inches (51 mm) and shall not exceed
the thickness of the footing. Footing thickness and projection for
fireplaces shall be in accordance with Section R1001.2. The size of
footings supporting piers and columns shall be based on the tributary
load and allowable soil pressure in accordance with Table R401.4.1.
Footings for wood foundations shall be in accordance with the details
set forth in Section R403.2, and Figures R403.1(2) and R403.1(3).
66.
403.1.7 Footings On Or Adjacent To
Slopes. The placement of buildings and structures on or adjacent to
slopes steeper than one (1) unit vertical in three (3) units horizontal
(33.3% slope) shall conform to Sections R403.1.7.1 through R403.1.7.4,
or plans as signed and sealed by a registered engineer licensed in
the State of Missouri.
67.
Table R403.1(4) Minimum Width Of
Concrete, Precast Or Masonry Footings (Inches) For Light-Frame Construction
With Pre-Fabricated Roof Trusses.
Minimum Width of Concrete, Precast
or Masonry Footings (inches) for Light-Frame Construction with Pre-Fabricated
Roof Trussesa,b,c
| ||||
---|---|---|---|---|
Load-Bearing Value of Soil
(psf)
| ||||
1,500
|
2,000
|
3,000
|
>4,000
| |
Conventional light-frame construction
with pre-fabricated trusses
| ||||
1 story
|
12
|
12
|
12
|
12
|
2 story
|
15
|
12
|
12
|
12
|
3 story
|
23
|
17
|
12
|
12
|
4-inch brick veneer over light
frame or 8-inch hollow concrete masonry
| ||||
1 story
|
12
|
12
|
12
|
12
|
2 story
|
21
|
16
|
12
|
12
|
3 story
|
32
|
24
|
16
|
12
|
8-inch solid or fully grouted
masonry
| ||||
1 story
|
16
|
12
|
12
|
12
|
2 story
|
29
|
21
|
14
|
12
|
3 story
|
42
|
32
|
21
|
16
|
For SI: one (1) inch equals 25.4
mm. one (1) pound per square foot+0.0479 kPa
| |
a.
|
Spread footings shall be same thickness
as the wall (minimum of eight (8) inches).
|
b.
|
Where minimum footing width is twelve
(12) inches, use of a single wythe of solid or fully grouted twelve-inch
nominal concrete masonry units is permitted.
|
c.
|
Snow Load or Roof Live Load shall
not exceed twenty (20) psf. If load exceeds twenty (20) psf, designs
must be completed by a licensed design professional.
|
68.
R404.1.2.2 Reinforcement For Foundation
Walls. Concrete foundation walls shall be laterally supported at the
top and bottom. Horizontal reinforcement shall be provided in accordance
with Table R404.1.2(1). Vertical reinforcement shall be provided in
accordance with Table R404.1.2(2), R404.1.2(3), R404.1.2(4), R404.1.2(5),
R404.1.2(6), R404.1.2(7) or R404.1.2(8). Vertical reinforcement for
flat basement walls retaining four (4) feet (1,219 mm) or more of
unbalanced backfill is permitted to be determined in accordance with
Table R404.1.2(9). For basement walls supporting above-grade concrete
walls, vertical reinforcement shall be the greater of that required
by Tables R404.1.2(2) through R404.1.2(8) or by Section R611.6 for
the above-grade wall. In buildings assigned to Seismic Design Category
D0, D1 or D2, concrete foundation walls shall also comply with Section
R404.1.4.2.
Exceptions:
1.
|
Where unstable soil or ground water
conditions do not exist, plain concrete foundation walls may be constructed
a minimum of eight (8) inches (203 mm) thick where the wall height
from the top of the footing to the top of the wall does not exceed
eight (8) feet (2,438 mm). A minimum of two (2) No. 4 horizontal reinforcing
bars shall be provided in the top and bottom of plain concrete foundation
walls. A minimum of two(2) No. 5 reinforcing bars shall be provided
around all window and door openings in plain concrete foundation and
basement walls. Bars shall extend a minimum twenty-four (24) inches
(610 mm) beyond the corners of the openings.
|
2.
|
Where unstable soil or ground water
conditions do not exist, plain concrete foundation walls may be constructed
a minimum of ten (10) inches (254 mm) thick where the wall height
from the top of the footing to the top of the wall does not exceed
nine (9) feet (2,743 mm). A minimum of two (2) No. 5 reinforcing bars
shall be place horizontally in the top, middle, and bottom of the
foundation wall. A minimum of two (2) No. 5 reinforcing bars shall
be provided around all window and door openings in plain concrete
foundation and basement walls. Bars shall extend a minimum of twenty-four
(24) inches (610 mm) beyond the corners of the openings.
|
69.
R404.1.3.2 Reinforcement For Foundation
Walls. Concrete foundation walls shall be laterally supported at the
top and bottom. Horizontal reinforcement shall be provided in accordance
with Table R404.1.2(1). Vertical reinforcement shall be provided in
accordance with Table R404.1.2(2), R404.1.2(3), R404.1.2(5), R404.1.2(6),
R404.1.2(7) or R404.1.2(8). Vertical reinforcement for flat basement
walls retaining four (4) feet (1,219 mm) or more of unbalanced backfill
is permitted to be determined in accordance with Table 404.1.2(9).
For basement walls supporting above-grade concrete walls, vertical
reinforcement shall be the greater of that required by Tables R404.1.2(2)
through R404.1.2(8) or by Section R608.6 for the above-grade wall.
In buildings assigned to Seismic Design Category D0, D1 or D2 concrete
foundation walls shall also comply with Section 404.1.4.2.
Exception: Where unstable soil or
ground water conditions do not exist, concrete foundation walls may
be constructed in accordance with Table R404.1.2(10).
70.
Table R404.1.2(10) Concrete Foundation
Walls.
Maximum Wall Height
|
Maximum Depth of Unbalanced Backfill
|
Minimum Nominal Wall Thickness
|
---|---|---|
8'-0"
|
7'-6" or less
|
8" (Note a)
|
9'-0"
|
8'-6" or less
|
10" (Note b)
|
10'0"
|
9'-6" or less
|
12" (Note c)
|
Note a: Concrete foundation walls
may be constructed a minimum of nominal eight (8) inches thick where
the wall height from the top of the footing to the top of the wall
does not exceed eight (8) feet. A minimum of two (2) #4 reinforcing
bars shall be place horizontally in the top and bottom of the foundation
wall. A minimum of two (2) #5 reinforcing bars shall be provided around
all window and door openings in concrete foundation and basement walls;
bars shall extend a minimum of twenty-four (24) inches beyond the
corners of the openings.
|
Note b: Concrete foundation walls
may be constructed a minimum of nominal ten (10) inches thick. A minimum
of two (2) #5 reinforcing bars shall be placed horizontally in the
top, middle, and bottom of the foundation wall. A minimum of two (2)
#5 reinforcing bars shall be provided around all window and door openings
in concrete foundation and basement walls; bars shall extends a minimum
of twenty-four (24) inches beyond the corners of the openings.
|
Note c: Concrete foundation walls
may be constructed a minimum of nominal twelve (12) inches thick.
A minimum of three (3) #5 reinforcing bars shall be placed horizontally
in the top, middle, and bottom of the foundation wall. A minimum of
two (2) #5 reinforcing bars shall be provided around all window and
door openings in concrete foundation and basement walls; bars shall
extend a minimum of twenty-four (24) inches beyond the corners of
the openings.
|
Note d: The concrete minimum wall
thickness shall be eight (8) inches for foundation walls in soil classes
SC, MH, ML-CL and inorganic CL when maximum wall height is eight (8)
feet.
|
Note e: The concrete minimum wall
thickness shall be ten (10) inches for foundation walls in soil classes
SC, MH, ML-CL and inorganic CL when the maximum wall height is nine
(9) feet.
|
Note f: The concrete minimum wall
thickness shall be twelve (12) inches for foundation walls in soil
classes SC, MH, ML-CL and inorganic CL when the maximum wall height
is ten (10) feet.
|
71.
405.1 Concrete Or Masonry Foundations.
Drains shall be provided around concrete or masonry foundation that
retain earth and enclose habitable or usable spaces located below
grade. Drainage tiles, gravel or crushed stone drains, perforated
pipe or other approved systems or materials shall be installed at
or below the area to be protected and shall discharge by gravity or
mechanical means into an approved drainage system. Gravel or crushed
stone drains shall extend not less than one (1) foot (305 mm) beyond
the outside edge of the footing and six (6) inches (152 mm) above
the top of the footing and be covered with an approved filter membrane
material. The top of open joints of drain tiles shall be protected
with strips of building paper. Except where otherwise recommended
by the drain manufacturer, perforated drains shall be surrounded with
an approved filter membrane or the filter membrane shall cover the
washed gravel or crushed rock covering the drain. Drainage tiles or
perforated pipe shall be placed on a minimum of two (2) inches (51
mm) of washed gravel or crushed rock not less than one (1) sieve size
larger than the tile joint opening or perforation and covered with
not less than six (6) inches (152 mm) of the same material.
Exceptions:
1.
|
A drainage system is not required
where the foundation is installed on well-drained ground or sand-gravel
mixture soils according to the Unified Soil Classification System,
Group I soils, as detailed in Table R405.1.
|
2.
|
Drains provided as detailed in Section
405.1.2 are approved as an alternative method to meet the requirements
of this Section.
|
72.
R405.1.2 Soil Evaluations. An evaluation
of the soil for the presence or absence of groundwater is required.
The evaluation report shall be based on either a subsurface soil investigation
or satisfactory data from adjacent areas together with an inspection
of the excavation prior to pouring concrete.
73.
R405.1.2.1 Groundwater Present. Provide
drain tile, perforated pipe or other approved foundation drainage
systems (such as water channel system) around perimeter of the outside
of the foundation and inside the foundation. Drain discharge shall
be by gravity to daylight or be connected to a basement floor sump.
74.
R405.1.2.2 No Groundwater Present.
Provide drain tile, perforated pipe or other approved foundation drainage
systems (such as water channel system) around perimeter of the outside
of the foundation or inside the foundation. Drain discharge shall
be by gravity to daylight or be connected to a basement floor sump.
75.
R405.1.2.3 Filter Membranes. An approved
filter membrane shall be placed over the top of the joints/pipe perforation.
The tile/pipe shall be placed on two (2) inches minimum of gravel
or crushed stone and have six (6) inches of minimum cover.
76.
R405.1.2.4 Drainage System. A drainage
system shall discharge by gravity to daylight or be connected to an
approved sump eighteen (18) inches in diameter x twenty-four (24)
inches deep with fitted cover). A sump pump shall be provided if the
basement is finished or partially finished with pump discharge by
an approved method.
77.
R502.2.2.1 Alternate Deck Ledger
Connections. Deck ledger connections not conforming to Table R502.2.2.1
shall be designed in accordance with accepted engineering practice.
Girders supporting deck joists shall not be supported on deck ledgers.
Deck ledgers shall not be supported on stone or masonry veneer. Girders
may be support of rim board with positive connected mechanical hangers.
78.
R502.2.2.2 Deck Lateral Load Connection.
The lateral load connection required by Section R502.2.2 shall be
permitted to be in accordance with Figure R502.2.2.3. Hold-down tension
devices shall be installed in not less than two (2) locations per
deck, and each device shall have an allowable stress design capacity
of not less than one thousand five hundred (1,500) pounds (6672N).
Exception: All decks that are one
hundred (100) square feet or less.
79.
Table 507.2 — Delete footnote
e.
80.
R507.2.4 Deck Lateral Load Connection.
The lateral load connection required by Section R507.1 shall be one
(1) of the following methods:
1.
|
In accordance with Figure R507.2.3(1)
with hold-down tension devices installed in not less than two (2)
locations per deck, within twenty-four (24) inches of each end of
the deck. Each device shall have an allowable stress design capacity
of not less than one thousand five hundred (1,500) pounds (6672 N).
|
2.
|
In accordance with Figure R507.2.3(2)
with hold-down tension devices installed in not less than four (4)
locations per deck, and each device shall have an allowable stress
design capacity of not less than seven hundred fifty (750) pounds
(3336 N).
|
3.
|
Using knee braces extending from
the floor system to the posts.
|
81.
Table R602.7.5.
Table 602.7.5
| ||
---|---|---|
Ultimate Design Wind Speed and Exposure
Category
| ||
Maximum Header Span
(feet)
|
<140mph, Exposure B
or <130mph, Exposure C
|
<115mph, Exposure Bb
|
4
|
1
|
1
|
6
|
2
|
1
|
8
|
2
|
1
|
10
|
3
|
2
|
12
|
3
|
2
|
14
|
3
|
2
|
16
|
4
|
2
|
18
|
4
|
2
|
a.
|
For header spans between those given
above, use the minimum number of full-height studs associated with
the larger header span.
|
b.
|
The tabulated minimum number of full-height
studs is applicable where jack studs are provided to support the header
at each end in accordance with Table R602.7(1). Where a framing anchor
is used to support the header in lieu of a jack stud in accordance
with footnote "d" of Table R602.7(1), the minimum number of full-height
studs at each end of a header shall be in accordance with requirements
for wind speed <140mph, Exposure B.
|
82.
R602.12 Simplified Wall Bracing.
Buildings meeting all of the conditions listed below shall be permitted
to be braced in accordance with this Section as an alternate to the
requirements of Section R602.10. The entire building shall be braced
in accordance with this Section; the use of other bracing provisions
of Section R602.10, except as specified herein, shall not be permitted.
1.
|
There shall be not more than three
(3) stories above the top of a concrete or masonry foundation or basement
wall. Permanent wood foundations shall not be permitted.
|
2.
|
Floors shall not cantilever more
than twenty-four (24) inches (607 mm) beyond the foundation or bearing
wall below.
|
3.
|
Wall height shall not be greater
than a nominal twelve (12) feet when using the minimum required bracing
lengths specified in Table 602.12.4.
|
4.
|
The building shall have a roof eave-to-ridge
height of fifteen (15) feet (4,572 mm) or less.
|
5.
|
Exterior walls shall have gypsum
board with a minimum thickness of one-half (1/2) inch (12.7 mm) installed
on the interior side fastened in accordance with Table R702.3.5.
|
Exception: Gypsum board is not required
for wall bracing on exterior walls in garages.
|
6.
|
The structure shall be located in
Seismic Design Category A, B or C for detached one- and two-family
dwellings or Seismic Design Category A, B or C for townhouses.
|
7.
|
Cripple walls shall not be permitted
in three-story buildings.
|
83.
R602.12.2 Sheathing Materials. The
following sheathing materials installed on the exterior side of exterior
walls shall be used to construct a bracing unit as defined in Section
R602.12.3. Mixing materials is prohibited.
1.
|
Wood structural panels with a minimum
thickness of seven-sixteenths (7/16) inch fastened in accordance with
Table R602.3(3).
|
2.
|
Structural fiberboard sheathing with
a minimum thickness of one-half (1/2) inch (12.7 mm) fastened in accordance
with Table R602.3(1).
|
84.
R602.12.3 Bracing Unit. A bracing
unit shall be a full-height sheathed segment of the exterior wall
without openings or vertical or horizontal offsets and a minimum length
as specified herein. Interior walls shall not contribute toward the
amount of the required bracing. Mixing of Items 1 and 2 is prohibited
on the same story.
1.
|
Where all framed portions of all
exterior walls are sheathed in accordance with Section R602.12.2,
including wall areas between bracing units, above and below openings
and on gable end walls, the minimum length of a bracing unit shall
be three (3) feet (914 mm). For walls with heights greater than a
nominal ten (10) feet, the minimum length of a bracing unit shall
be four (4) feet (1,219 mm).
|
2.
|
Where the exterior walls are braced
with sheathing panels in accordance with Section R602.12.2 and areas
between bracing units are covered with other materials, the minimum
length of a bracing unit shall be four (4) feet (1,219 mm).
|
85.
R905.2.8.2 Valleys. Valley linings
shall be installed in accordance with the manufacturer's instructions
before applying shingles. Valley linings of the following types shall
be permitted:
1.
|
For open valleys (valley lining exposed)
lined with metal, the valley lining shall be not less than twenty-four
(24) inches (610 mm) wide and of any of the corrosion-resistant metals
in Table R905.2.8.2.
|
2.
|
For open valley, valley lining of
two (2) plies of mineral-surfaced roll roofing, complying with ASTM
D 3909 or ASTM D 6380 Class M, shall be permitted. The bottom layer
shall be eighteen (18) inches (457 mm) and the top layer not less
than thirty-six (36) inches (914 mm) wide.
|
3.
|
For closed valleys (valley covered
with shingles), valley lining of two (2) ply of No. 15 felt complying
with ASTM D 226 Type I, ASTM D 4869 Type I, or ASTM D 6757, or valley
lining as described in Item 1 and 2 shall be permitted. Self-adhering
polymer modified bitumen underlayment complying with ASTM D 1970 shall
be permitted in lieu of the lining material.
|
86.
R905.2.8.5 Drip Edge. A drip edge
shall be provided at eaves and rake edges of shingle roofs. Adjacent
segments of drip edge shall be overlapped not less than two (2) inches
(51 mm). Drip edges shall extend not less than one-fourth (1/4) inch
(6.4 mm) below the roof sheathing and extend up back onto the roof
deck not less than two (2) inches (51 mm). Drip edges shall be mechanically
fastened to the roof deck at not more than twelve (12) inches (305
mm) o.c. with fasteners as specified in Section R905.2.5. Underlayment
shall be installed over the drip edge along eaves and under the underlayment
along rake edges.
Exception: For new construction only,
a drip edge is not necessary if the metal fascia is bent to form a
drip edge.
87.
R1005.7 Factory-Built Chimney Offsets.
Where a factory-built chimney assembly incorporates offsets, no part
of the chimney shall be at an angle of more than thirty degrees (30°)
(0.52 rad) from vertical at any point in the assembly and the chimney
shall not include more than four (4) elbows.
Exception: When chimneys are installed
per manufacturer's installation instructions.
88.
PROJECTION FACTOR
N1101.6 (R202) Defined Terms.
The ratio of the horizontal depth of an overhang, eave, or
permanently attached shading device, divided by the distance measured
vertically from the bottom of the fenestration glazing to the underside
of the overhang, eave, or permanently attached shading device.
89.
N1101.13 (R401.2) Compliance. Projects
shall comply with one (1) of the following:
1.
|
Sections N1101.14 through N1104 as
amended.
|
2.
|
Section N1105 and the provisions
of Sections N1101.14 through N1104 labeled "Mandatory."
|
3.
|
An energy rating index (ERI) approach
in Section N1106.
|
90.
N1101.14 (R401.3) Certificate (Mandatory).
A permanent certificate shall be completed by the builder or registered
design professional and posted on a wall in the space where the furnace
is located, a utility room or an approved location inside the building,
unless otherwise presented to the homeowner or Code Official, in writing.
Where located on an electrical panel, the certificate shall not cover
or obstruct the visibility of the circuit director label, service
disconnect label or other required labels. The certificate shall list
the predominant R-values of insulation installed in or on ceiling/roof,
walls, foundation (slab, basement wall, crawl space wall and/or floor)
and ducts outside conditioned spaces; U-factors for fenestration and
the solar heat gain coefficient (SHGC) of fenestration, and the results
from any required duct system and building envelope air leakage testing
done on the building. Where there is more than one (1) value for each
component, the certificate shall list the value covering the largest
area. The certificate shall list the types and efficiencies of heating,
cooling and service water heating equipment. Where a gas-fired unvented
room heater, electric furnace, or baseboard electric heater is installed
in the residence, the certificate shall list "gas-fired unvented room
heater," "electric furnace" or "baseboard electric heater," as appropriate.
An efficiency shall not be listed for gas-fired unvented room heaters,
electric furnaces or electric baseboard heaters.
91.
Table N1102.1.2 (R402.1.2).
Table N1102.1.2 (R402.1.2)
| ||||||||||
---|---|---|---|---|---|---|---|---|---|---|
Insulation and Fenestration Requirements
by Componenta
| ||||||||||
Climate Zone
|
Fenest- ration U-Factorb
|
Skylightb U-Factor
|
Glazed Fenest- ration SHGCb,c
|
Ceiling R-Value
|
Wood Frame Wall R-Value
|
Mass Wall R-Valuei
|
Floor R-Value
|
Base- mentc Wall R-Value
|
Slabd R-Value
and Depth
|
Crawl Spacec Wall R-Value
|
1
|
NR
|
0.75
|
0.25
|
30
|
13
|
3/4
|
13
|
0
|
0
|
0
|
2
|
0.40
|
0.65
|
0.25
|
38
|
13
|
4/6
|
13
|
0
|
0
|
0
|
3
|
0.35
|
0.55
|
0.25
|
38
|
20 or 13 + 5h
|
8/13
|
19
|
5/13f
|
0
|
5/13
|
4 except Marine
|
0.40
|
0.55
|
NR
|
38
|
13
|
8/13
|
19
|
0j
|
10,2 ft
|
10/13
|
5 and Marine 4
|
0.32
|
0.55
|
NR
|
49
|
20 or 13 + 5h
|
13/17
|
30g
|
15/19
|
10, 2 ft
|
15/19
|
6
|
0.32
|
0.55
|
NR
|
49
|
20 + 5
Or 13 + 10h
|
15/20
|
30g
|
15/19
|
10, 4 ft
|
15/19
|
7 and 8
|
0.32
|
0.55
|
NR
|
59
|
20 + 5
Or 13 + 10h
|
19/21
|
38g
|
15/19
|
10, 4 ft
|
15/19
|
For SI: one (1) foot — 304.8
mm.
| |
---|---|
a.
|
R-values are minimums. U-factors
and SHGC are maximums. When insulation is installed in a cavity which
is less than the label or design thickness of the insulation, the
installed R-value of the insulation shall not be less than the R-value
specified in the table.
|
b.
|
The fenestration U-factor column
excludes skylights. The SHGC column applies to all glazed fenestration.
|
Exception: Skylights may be excluded
from glazed fenestration SHGC requirements in Climate Zones 1 through
3 where the SHGC for such skylights does not exceed 0.30.
| |
c.
|
"15/19" means R-15 continuous insulation
on the interior or exterior of the home or R-19 cavity insulation
at the interior of the basement wall. "15/19" shall be permitted to
be met with R-13 cavity insulation on the interior of the basement
wall plus R-5 continuous insulation on the interior or exterior of
the home. "10/13" means R-10 continuous insulation on the interior
or exterior of the home or R-13 cavity insulation at the interior
of the basement wall.
|
d.
|
R-5 shall be added to the required
slab edge R-values for heated slabs. Insulation depth shall be the
depth of the footing or two (2) feet, whichever is less in Zones 1
through 3 for heated slabs.
|
e.
|
There are no SHGC requirements in
the Marine Zone.
|
f.
|
Basement wall insulation is not required
in warm-humid locations as defined by Figure N1101.10 or Table N1101.10.
|
g.
|
Or insulation sufficient to fill
the framing cavity, R-19 minimum.
|
h.
|
The first value is cavity insulation,
the second value is continuous insulation, so "13 + 5" means R-13
cavity insulation plus R-5 continuous insulation.
|
i.
|
The second R-value applies when more
than half of the insulation is on the interior of the mass wall.
|
j.
|
Band boards and cripple walls shall
be insulated to R-13.
|
92.
N1102.1.3 R-Value Computation. Insulation
material used in layers, such as framing cavity insulation, or continuous
insulation shall be summed to compute the corresponding component
R-value. The manufacturer's settled R-value shall be used for flown
insulation. Computed R-values may include an R-value for other building
materials or air films. Where insulated siding is used for the purpose
of complying with the continuous insulation requirements of Table
N1102.1.2, the manufacturer's labeled R-Value for insulated siding
shall be reduced by R-0.6.
93.
N1102.1.5 (R402.1.5) Total UA Alternative.
If the total building envelope UA (sum of U-factor times assembly
area) is less than or equal to the total UA resulting from using the
U-factors in Table N1102.1.4 (multiplied by the same assembly area
as in the proposed building), the building shall be considered in
compliance with Table N1102.1.2. The UA calculation shall be done
using a method consistent with the ASHRAE Handbook of Fundamentals
and shall include the thermal bridging effects of framing materials.
The SHGC requirements shall be met in addition to UA compliance.
Exception: Glazed Fenestration SHGC.
In Climate Zone 4, permanently shaded vertical fenestration shall
be permitted to satisfy SHGC requirements. The project factor of an
overhang, eave, or permanently attached shading device shall be greater
than or equal to the value listed in Table N1102.2.2.1 for the appropriate
orientation. The minimum projection shall extend beyond each side
of the glazing a minimum of twelve (12) inches. Each orientation shall
be rounded to the nearest cardinal orientation (+/- 45° or 0.79
rad) for purposes of calculations and demonstrating compliance.
94.
N1102.2.4 (R402.2.4) Access Hatches
And Doors. Access doors from conditional spaces to unconditioned spaces
such as attics and crawl spaces shall be insulated to a level equivalent
to the insulation on the surrounding surfaces. Access shall be provided
to all equipment that prevents damaging or compressing the insulation.
A wood-framed or equivalent baffle or retainer is required to be provided
when loose-fill insulation is installed, the purpose of which is to
prevent the loose-fill insulation from spilling into the living space
when the attic access is opened, and to provide the permanent means
of maintaining the installed R-value of the loose-fill insulation.
Exception: Vertical doors that provide
access from the conditioned to unconditioned spaces shall be permitted
to meet the fenestration requirement of Table R1102.1.2 based on the
applicable climate zone specified in Chapter 3.
95.
N1102.4 (R402.4) Air Leakage. The
building thermal envelope may be designed and constructed to limit
air leakage in accordance with the requirements of Sections R1102.4.1
through R1102.4.4.
96.
Table N1102.4.1.1 (402.4.1.1).
Table N1102.4.1.1 (402.4.1.1)
Air Barrier and Insulation Installation
| ||
---|---|---|
Component
|
Air Barrier Criteria
|
Insulation Installation Criteria
|
General Requirements
|
A continuous air barrier shall be
installed in the building envelope.
The exterior thermal envelope contains
a continuous air barrier.
Breaks or joints in the air barrier
shall be sealed.
|
Air-permeable insulation shall not
be used as a sealing material.
|
Ceiling/attic
|
The air barrier in any dropped ceiling/soffit
shall be aligned with the insulation and any gaps in the air barrier
sealed.
Access openings, drop down stairs
or knee wall doors to unconditioned attic spaces shall be sealed.
|
The insulation in any dropped ceiling/soffit
shall be aligned with the air barrier.
|
Walls
|
The junction of the foundation and
sill plate shall be sealed.
The junction of the top plate and
the top of the exterior walls shall be sealed.
Knee walls shall be sealed.
|
Cavities within corners and headers
of frame walls shall be insulated by completely filling the cavity
with a material having a thermal resistance of R-3 per inch minimum.
Exterior thermal envelope insulation
for framed walls shall be installed in substantial contact and continuous
alignment with the air barrier.
|
Windows, skylights and doors
|
The space between window/door jambs
and framing, and skylights and framing shall be sealed.
| |
Rim joists
|
Rim joists shall include the air
barrier.
|
Rim joists shall be insulated.
|
Floors (including above garage and
cantilevered floors)
|
The air barrier shall be installed
at any exposed edge of insulation.
|
Floor framing cavity insulation shall
be installed to maintain permanent contact with the underside of subfloor
decking, or floor framing cavity insulation shall be permitted to
be in contact with the top side of sheathing, or continuous insulation
installed on the underside of floor framing; and extends from the
bottom to the top of all perimeter floor framing members.
|
Crawl space walls
|
Exposed earth in unvented crawl spaces
shall be covered with Class I vapor retarder with overlapping joists
taped.
|
Where provided instead of floor insulation,
insulation shall be permanently attached to the crawl space walls.
|
Narrow cavities
|
Batts in narrow cavities shall be
cut to fit, or narrow cavities shall be filled by insulation that
on installation readily conforms to the available cavity space.
| |
Garage separation
|
Air sealing shall be provided between
the garage and conditioned spaces.
| |
Plumbing and wiring
|
Batt insulation shall be cut neatly
to fit around wiring and plumbing in exterior walls, or insulation
that on installation readily conforms to available space shall extend
behind piping and wiring.
| |
Shower/tub on exterior wall
|
The air barrier installed at exterior
walls adjacent to showers and tubs shall separate them from showers
and tubs.
|
Exterior walls adjacent to showers
and tubs shall be insulated.
|
Electrical/phone box on exterior
walls
|
The air barrier shall be installed
behind electrical or communication boxes or air-sealed boxes shall
be installed.
| |
Concealed sprinklers
|
When required to be sealed, concealed
fire sprinklers shall only be sealed in a manner that is recommended
by the manufacturer. Caulking or other adhesive sealants shall not
be used to fill voids between fire sprinkler cover plates and walls
or ceilings.
|
a.
|
In addition, inspection of log walls
shall be in accordance with the provisions of ICC 400.
|
97.
N1102.4.1.2 (R402.4.1.2) Testing
Option. If testing is elected, the building or dwelling unit may be
tested and verified as having an air leakage rate of not exceeding
five (5) air changes per house in Climate Zone 4. Testing shall be
conducted in accordance with ASTM E 779 or ASTM E 1827 and reported
at a pressure of 0.2 inch w.g. (50 Pascals). Where required by the
Code Official, testing shall be conducted by an approved third party.
A written report of the results of the test shall be signed by the
party conducting the test and provided to the Code Official. Testing
shall be performed at any time after creation of all penetrations
of the building thermal envelope.
During testing:
1.
|
Exterior windows and doors, fireplace
and stove doors shall be closed, but not sealed, beyond the intended
weatherstripping or other infiltration control measures.
|
2.
|
Dampers including exhaust, intake,
makeup air, backdraft and flue dampers shall be closed, but not sealed
beyond intended infiltration control measures.
|
3.
|
Interior doors, if installed at the
time of the test, shall be open.
|
4.
|
Exterior doors for continuous ventilation
systems and heat recovery ventilators shall be closed and sealed.
|
5.
|
Heating and cooling systems, if installed
at the time of the test, shall be turned off.
|
6.
|
Supply and return registers, if installed
at the time of the test, shall be fully open.
|
98.
N1102.4.2.1 Visual Inspection Option.
The items listed in Table N1102.4.2, applicable to the method of construction,
are field verified, by the builder or a party independent from the
installer of the insulation, shall inspect the air barrier and insulation.
99.
N1102.4.4 (R402.4.4) Rooms Containing
Fuel-Burning Appliances. In Climate Zones 3 through 8, where open
combustion air ducts provide combustion air to open combustion fuel-burning
appliances, the appliances and combustion air opening shall be located
outside the building thermal envelope or enclosed in a room, isolated
from inside the thermal envelope. Such rooms shall be sealed and insulated
in accordance with the envelope requirements of Table N1102.1.2, where
the walls, floors and ceiling shall meet a minimum of the basement
wall R-value requirement. The door into the room shall be fully gasketed
and any water lines and ducts in the room insulated in accordance
with Section N1103. The combustion air duct shall be insulated where
it passes through conditioned space to a minimum of R-8.
Exceptions:
1.
|
Direct vent appliances with both
intake and exhaust pipes installed continuous to the outside.
|
2.
|
Fireplaces and stoves complying with
Sections N1102.4.2 and R1006.
|
3.
|
Mechanical equipment in an unfinished
space.
|
100.
N1103.1.1 — Delete.
101.
N1103.3.3 (R403.3.3) Duct Testing
(Optional). Ducts shall be pressure tested to determine the air leakage
by one (1) of the following methods:
1.
|
Rough-in test: Total leakage shall
be measured with a pressure differential of one-tenth (0.1) inch w.g.
(25 Pa) across the system, including the manufacturer's air handler
enclosure if installed at the time of the test. All registers shall
be taped or otherwise sealed during the test.
|
2.
|
Postconstruction test: Total leakage
shall be measured with a pressure differential of one-tenth (0.1)
inch w.g. (25 Pa) across the entire system, including the manufacturer's
air handler enclosure. Registers shall be taped or otherwise sealed
during the test.
|
Exception: A duct air leakage test
shall not be required where ducts and air handlers are located entirely
within the building thermal envelope.
|
102.
N1103.3.5 (R403.3.5) — Delete.
103.
N1103.4.1 (R403.4.1) Protection Of
Piping Insulation. Piping insulation exposed to weather shall be protected
from damage, including that caused by sunlight, moisture, equipment
maintenance and wind, and shall provide shielding from solar radiation
that can cause degradation of the material. Adhesive tape shall not
be permitted.
Exception: Line sets between the
structure and the condensing unit.
104.
1103.5.3 (R405.5.3) Hot Water Pipe
Insulation (Prescriptive). Insulation for hot water pipe with a minimum
thermal resistance (R-value) of R-3 shall be applied to the following:
1.
|
Piping larger than 3/4 inch (19 mm)
in nominal diameter.
|
2.
|
Piping serving more than one (1)
dwelling unit.
|
3.
|
Piping located outside the conditioned
space.
|
4.
|
Piping from the water heater to a
distribution manifold.
|
5.
|
Piping located under a floor slab.
|
6.
|
Buried in piping.
|
7.
|
Supply and return piping in recirculation
systems other than demand recirculation systems.
|
105.
N1103.6 (R403.6) Mechanical Ventilation.
Mandatory where required by N1102.4.1.2. If, in accordance with N1102.4.1.2,
the resulting air changes per hour (ACH) at fifty (50) Pascals is
less than five (5) air changes per hour, the building shall be provided
with ventilation that meets the requirements of Section M1507 of this
code or the International Mechanical Code, as applicable, or with
other approved means of ventilation. Outdoor air intakes and exhausts
shall have automatic or gravity dampers that close when the ventilation
system is not operating.
106.
N1103.6.1 (R403.6.1) — Delete.
107.
Table N1103.6.1 (R403.6.1) —
Delete.
108.
N1104 (R404) Electrical Power And
Lighting Systems (Optional).
109.
N1104.1 (R404.1) Lighting Equipment
(Optional). Not less than seventy-five percent (75%) of the lamps
in permanently installed lighting fixtures shall be high efficacy
lamps or not less than seventy-five percent (75%) of the permanently
installed lighting fixtures shall contain only high efficacy lamps.
Exception: Low voltage lighting.
110.
N1104.1.1 (R404.1.1) Lighting Equipment
(Optional). Fuel gas lighting systems shall not have continuously
burning pilot lights.
111.
Table N1105.5.2(1) [R405.5.2(1)].
Table N1105.5.2(1) [R405.5.2(1)]
Specifications for the Standard Reference
and Proposed Designs
| ||
---|---|---|
Building Component
|
Standard Reference Design
|
Proposed Design
|
Above-grade walls
|
Type: mass wall if proposed wall
is mass; otherwise wood frame
|
As proposed
|
Gross area: same as proposed
|
As proposed
| |
U-factor: as specified in Table N1102.1.4
|
As proposed
| |
Solar absorptance = 0.75
|
As proposed
| |
Remittance = 0.90
|
As proposed
| |
Basement and crawl space walls
|
Type: same as proposed
|
As proposed
|
Gross area: same as proposed
|
As proposed
| |
U-factor: from table N1102.1.4, with
insulation layer on interior side of walls
|
As proposed
| |
Above-grade floors
|
Type: wood frame
|
As proposed
|
Gross area: same as proposed
|
As proposed
| |
U-factor: as specified in Table N1102.1.4
|
As proposed
| |
Ceilings
|
Type: wood frame
|
As proposed
|
Gross area: same as proposed
|
As proposed
| |
U-factor: as specified in Table N1102.1.4
|
As proposed
| |
Roofs
|
Type: composition shingle on wood
sheathing
|
As proposed
|
Gross area: same as proposed
|
As proposed
| |
Solar absorptance = 0.75
|
As proposed
| |
Emittance = 0.90
|
As proposed
| |
Attics
|
Type: vented with aperture = 1 ft2 per 300 ft2 ceiling area
|
As proposed
|
Type: same as proposed
|
As proposed
| |
Foundations
|
Foundation wall area above and below
grade and soil characteristics: same as proposed
|
As proposed
|
Opaque doors
|
Area: 40 ft2
|
As proposed
|
Orientation: North
|
As proposed
| |
U-factor: same as fenestration from
Table N1102.1.4
|
As proposed
| |
Vertical fenestration other than
opaque doors
|
Total areab = 15% of the conditioned floor area
|
As proposed
|
Orientation: equally distributed
to four (4) cardinal compass orientations (N, E., S & W)
|
As proposed
| |
U-factor: as specified in Table N1102.1.4
|
As proposed
| |
SHGC: as specified in Table N1102.1.2
except that for climates with no requirement (NR) SHGX = 0.40 shall
be used
|
As proposed
| |
Interior shade fraction: 0.92 —
(0.21 x SHGC for the standard reference design)
|
0.92 — (0.21 x SHGC as proposed)
| |
External shading: none
|
As proposed
| |
Skylights
|
None
|
As proposed
|
Thermally isolated sunrooms
|
None
|
As proposed
|
Air exchange rate
|
Air leakage rate of five (5) air
changes per hour in Climate Zone 4. The mechanical ventilation rate
shall be in addition to the air leakage rate and the same as in the
proposed design, but no greater than 0.01 x CFA + 7.5 x (Nbr + 1)
where:
CFA = conditional floor area
Nbr = number
of bedrooms
Energy recovery shall not be assumed
for mechanical ventilation
|
For residences that are not tested,
the same air leakage rate as the standard reference design.
For tested residences, the measured
air exchange ratea.
The mechanical ventilation rate rateb shall be in addition to the air leakage rate and
shall be proposed.
|
Mechanical ventilation
|
None, except where mechanical ventilation
is specified by the proposed design, in which case:
Annual vent fan energy use:
KWh/yr = 0.03942 x CFA + 29.565 x
(Nbr + 1)
where:
CFA = conditional floor area
Nbr = number
of bedrooms
|
As proposed
|
Internal gains
|
IGain = 17,900 + 23.8 x CFA + 4104
x Nbr (Btu/day per dwelling unit)
|
Same as standard reference design
|
Internal mass
|
An internal mass for furniture and
contents of 8 pounds per square foot of floor area
|
Same as standard reference design,
plus any additional mass specifically designed as a thermal storage
elementc but not integral to the building
envelope or structure
|
Structural mass
|
For masonry floor slabs, 80% of floor
area covered by R-2 carpet and pad, and 20% of floor directly exposed
to room air
|
As proposed
|
For masonry basement walls, as proposed,
but with insulation required by Table R402.1.4 located on the interior
side of the walls
|
As proposed
| |
For other walls, for ceilings, floors,
and interior walls, wood frame construction
|
As proposed
| |
Heating systemsd, e
|
Fuel type: same as the proposed design
Efficiencies:
Electric: air-source heat pump with
prevailing Federal minimum standards
Non-electric Furnaces: natural gas
furnace with prevailing Federal minimum standards
Non-electric boilers: natural gas
boiler with prevailing Federal minimum standards
Capacity: sized in accordance with
Section N1103.7
|
As proposed
|
Cooling systemsd, f
|
Fuel type: electric
Efficiency: in accordance with prevailing
Federal minimum standards
Capacity: sized in accordance with
Section N1103.7
|
As proposed
|
Service water heatingd, e, f
|
Fuel type: same as proposed design
Efficiency: in accordance with prevailing
Federal minimum standards
Use: gal/day = 30 + 10 x Nbr
Tank temperature: 120° F.
|
As proposed
Same as standard reference
|
Thermal distribution systems
|
Duct insulation: from Section N1103.2.1
A thermal distribution system efficiency
(DSE) of 0.88 shall be applied to both the heating and cooling system
efficiencies for all systems other than tested duct systems. For tested
duct systems, the leakage rate shall be 4 cfm (113.3 L/min) per 100
ft2 (9.29 m2) of conditioned floor area at a pressure of differential of one
tenths (0.1) inches w.g. (25 Pa)
|
As tested or specified in Table R405.5.2(2)
if not tested. Duct insulation shall be as proposed
|
Thermostat
|
Type: Manual, cooling temperature
setpoint = 75° F.
Heating temperature setpoint = 72°
F.
|
Same as standard reference
|
For SI: 1 square foot = 0.93 m2,
1 British thermal unit = 1055 J, 1 pound per square foot = 4.88 kg/m2,
1 gallon (US) = 3.785 L, °C = (°F-32)/1.8, 1 degree = 0.79
rad.
| |
a.
|
Where required by the Code Official,
testing shall be conducted by an approved party. Hourly calculations
as specified in the ASHRAE Handbook of Fundamentals, or the equivalent
shall be used to determine the energy loads resulting from infiltration.
|
b.
|
The combined air exchange rate for
infiltration and mechanical ventilation shall be determined in accordance
with Equation 43 of 2001 ASHRAE Handbook of Fundamentals, page 26.19
for intermittent mechanical ventilation.
|
c.
|
Thermal storage element shall mean
a component not part of the floors, walls or ceilings that is part
of a passive solar system, and that provides thermal storage such
as enclosed water columns, rock beds, or phase-change containers.
A thermal storage element must be in the same room as fenestration
that faces within 15° (0.26 rad) of true south, or must be connected
to such a room with pipes or ducts that allow the element to be actively
charged.
|
d.
|
For a proposed design with multiple
heating, cooling or water heating systems using different fuel types,
the applicable standard reference design system capacities and fuel
types shall be weighted in accordance with their respective loads
as calculated by accepted engineering practice for each equipment
and fuel type present.
|
e.
|
For a proposed design without a proposed
heating system, a heating system with the prevailing Federal minimum
efficiency shall be assumed for both the standard reference design
and proposed design.
|
f.
|
For a proposed design home without
a proposed cooling system, an electric air conditioner with the prevailing
Federal minimum efficiency shall be assumed for both the standard
reference design and the proposed design.
|
g.
|
For a proposed design with a non-storage-type
water heat, a forty-gallon storage-type water heater with the prevailing
Federal minimum energy factor for the same fuel as the predominant
heating fuel type shall be assumed. For the case of a proposed design
without a proposed water heater, a forty-gallon storage-type water
heater with the prevailing Federal minimum efficiency for the same
fuel as the predominant heating fuel type shall be assumed for both
the proposed design and standard reference design.
|
112.
M1201.3 Licensing of Mechanical Contractors. For licensing requirement refer to Section 515.040 of the Municipal Code of the City of St. Peters.
113.
M1301.2 Identification. — Delete.
114.
M1301.3 Installation Of Materials.
— Delete.
115.
M1301.4 Plastic Pipe, Fittings And
Components. — Delete.
116.
M1301.5 Third Party Testing And Certification.
— Delete.
117.
M1305.1.4.1 Ground Clearance. Equipment
and appliances supported from the ground shall be level and firmly
supported on a concrete slab or other approved material extending
not less than two (2) inches (50.8 mm) above the adjoining ground.
Such support shall be in accordance with the manufacturer's installation
instructions. Appliances suspended from the floor shall have a clearance
of not less than six (6) inches (152 mm) from the ground.
118.
M1305.1.4.3 Electrical Requirements.
A luminaire controlled by a switch located at the required passageway
opening and a receptacle outlet shall be installed at or near the
appliance location in accordance with Chapter 39. Exposed lamps shall
be protected from damage by location or lamp guards.
Exception: Basements.
119.
M1307.2 Anchorage Of Appliances.
Appliances designed to be fixed in position shall be fastened or anchored
in an approved manner. In Seismic Design Categories D0, D1 and D2, water
heaters and thermal storage units shall be anchored or strapped to
resist horizontal displacement caused by earthquake motion in accordance
with one (1) of the following:
1.
|
Anchorage and strapping shall be
designed to resist a horizontal force equal to one-third (1/3) of
the operating weight of the water heater storage tank, acting in any
horizontal direction. Strapping shall be at points within the upper
one-third (1/3) and lower one-third (1/3) of the appliance's vertical
dimensions. At the lower point, the strapping shall maintain a minimum
distance of four (4) inches (102 mm) above the controls.
|
2.
|
The anchorage strapping shall be
in accordance with the appliance manufacturer's recommendations.
|
120.
M1411.3.1 Auxiliary And Secondary
Drain Systems. In addition to the requirements of Section M1411.3,
a secondary drain or auxiliary drain pan shall be required for each
cooling or evaporator coil where damage to any building components
will occur as a result of overflow from the equipment drain pan or
stoppage in the condensate drain piping. Such piping shall maintain
a minimum horizontal slope in the direction of discharge or not less
than 1/8 unit vertical in 12 units horizontal (one-percent slope).
Drain piping shall be not less than 3/4-inch (19 mm) nominal pipe
size. One (1) of the following methods shall be used:
1.
|
An auxiliary drain pan with a separate
drain shall be installed under the coils on which condensation will
occur. The auxiliary pan drain shall discharge to a conspicuous point
of disposal to alert occupants in the event of a stoppage of the primary
drain. The pan shall have a minimum depth of one and one-half (1.5)
inches (38 mm), shall be not less than three (3) inches (76 mm) larger
than the unit or the coil dimensions in width and length and shall
be constructed of corrosion-resistant material. Galvanized sheet steel
pans shall have a minimum thickness of not less than (No. 26 Gage).
Non-metallic pans shall have a minimum thickness of not less than
0.0625 inch (1.6 mm).
|
2.
|
A separate overflow drain line shall
be connected to the drain pan installed with the equipment. This overflow
drain shall discharge to a conspicuous point of disposal to alert
occupants in the event of a stoppage of the primary drain. The overflow
drain line shall connect to the drain pan at a higher level than the
primary drain connection.
|
3.
|
An auxiliary drain pan without a
separate drain line shall be installed under the coils on which condensation
will occur. This pan shall be equipped with a water level detection
device conforming to UL 508 that will shut off the equipment served
prior to overflow of the pan. The pan shall be equipped with a fitting
to allow for drainage. The auxiliary drain pan shall be constructed
in accordance with Item 1 of this Section.
|
4.
|
A water level detection device conforming
to UL 508 shall be installed that will shut off the equipment served
in the event that the primary drain is blocked. The device shall be
installed in the primary drain line, the overflow drain line or the
equipment-supplied rain pan, located at a point higher than the primary
drain line connection and below the overflow rim of such pan.
|
121.
M1502.4.1 Material And Size. Exhaust
ducts shall have a smooth interior finish and be constructed of metal
having a minimum thickness of 0.0157 inch (Answer: 0.3950 mm). The
duct shall be four (4) inches (102 mm) nominal in diameter.
122.
M1502.4.2 Duct Installation. Exhaust
ducts shall be supported at intervals not to exceed twelve (12) feet
(3,658 mm) and shall be secured in place. The insert end of the duct
shall extend into the adjoining duct or fitting in the direction of
airflow. Exhaust duct joints shall be sealed in accordance with Section
M1601.4.1.
123.
M1503.4 Makeup Air Required. Exhaust
hood systems capable of exhausting in excess of six hundred (600)
cubic feet per minute (0.28 m3/s) shall
be mechanically or naturally provided with makeup air at a rate approximately
equal to the exhaust air rate. Such makeup air systems shall be equipped
with not less than one (1) damper. Each damper shall be a gravity
damper or an electrically operated damper that automatically opens
when the exhaust system operates. Damper shall be accessible for inspection,
service, repair and replacement without removing permanent construction
or any other ducts not connected to the damper being inspected, serviced,
repaired or replaced.
124.
M1601.1.1 Above-Ground Duct Systems.
Above-ground duct systems shall conform to the following:
1.
|
Equipment connected to duct systems
shall be designed to limit discharge air temperature to not greater
than 250° F. (121° C.)
| |
2.
|
Factory-made ducts shall be listed
and labeled, as produced by the manufacturer and prior to use in the
field, in accordance with UL 181 and installed in accordance with
the manufacturer's instructions.
| |
3.
|
Fibrous glass duct construction shall
conform to the SMACNA Fibrous Glass Duct Construction Standards or
NAIMA Fibrous Glass Duct Construction Standards.
| |
4.
|
Field-fabricated and shop-fabricated
metal and flexible duct constructions shall conform to the SMACNA
HVAC Duct Construction Standards — Metal and Flexible except
as allowed by Table M1601.1.1. Galvanized steel shall conform to ASTM
A 653.
| |
5.
|
The use of gypsum products to construct
return air ducts or plenums is permitted, provided that the air temperature
does not exceed 125° F. (52° C.) and exposed surfaces are
not subject to condensation.
| |
6.
|
Duct systems shall be constructed
of materials having a flame spread index of not greater than two hundred
(200).
| |
7.
|
Stud wall cavities and the spaces
between solid floor joists to be used as air plenums shall comply
with the following conditions:
| |
7.1.
|
These cavities or spaces shall not
be used as a plenum for air supply.
| |
7.2.
|
These cavities or spaces shall not
be a part of required fire-resistance-rated assembly.
| |
7.3.
|
Stud wall cavities shall not convey
air from more than one (1) floor level.
| |
7.4.
|
Stud wall cavities and joist-space
plenums shall be isolated from adjacent concealed spaces by tight-fitting
fireblocking in accordance with Section R602.8.
| |
7.5.
|
Stud wall cavities in the outside
walls of building envelope assemblies shall not be utilized as air
plenums.
|
125.
Table M1601.1.1.
Table M1601.1.1
| ||||
---|---|---|---|---|
Gages of Metal Ducts and Plenums
Used For Heating or Cooling
| ||||
Type of Duct
|
Size
(inches)
|
Minimum Thickness
(inch)
|
Equivalent Galvanized Sheet
|
Approximate Aluminum B & S Gage
|
Round ducts and enclosed rectangular
ducts
|
14 or less
|
0.013
|
30
|
26
|
over 14
|
0.016
|
28
|
24
| |
Exposed rectangular ducts
|
14 or less
|
0.016
|
28
|
24
|
over 14
|
0.019
|
26
|
22
|
For S1 (1 inch = 25.4 mm).
|
126.
M1601.4.1 Joints, Seams And Connections.
Joints of duct systems shall be made substantially airtight in an
unconditioned area by means of tapes, mastics, liquid sealants, gasketing
or other approved closure systems. Closure systems used with rigid
fibrous glass ducts shall comply with UL 181A and shall be marked
18 A-P for pressure-sensitive tape, 181A-M for mastic or 181A-H for
heat-sensitive tape. Closure systems used with flexible air ducts
and flexible air connectors shall comply with UL181B and shall be
marked 181B-FX for pressure-sensitive tape or 181B-M for mastic. Duct
connections to flanges of air distribution system equipment or sheet
metal fitting shall be mechanically fastened. Mechanical fasteners
for use with flexible non-metallic air ducts shall comply with UL
181B and shall be marked 181B-C. Crimp joints for round metal ducts
shall have a contact lap of at least one (1) inch and shall be mechanically
fastened with at least three (3) sheet metal screws or rivets equally
spaced around the joint. Closure systems used to seal metal ductwork
shall be installed in accordance with the manufacturer's installation
instructions.
Exceptions:
1.
|
Spray polyurethane foam shall be
permitted to be applied without additional joint seals.
|
2.
|
Where a duct connection is made that
is partially inaccessible, three (3) screws or rivets shall be equally
spaced on the exposed portion of the joint so as to prevent a hinge
effect.
|
3.
|
Continuously welded and locking-type
longitudinal joints and seam in ducts operating at static pressure
less than two (2) inches of water column (500 Pa) pressure classification
shall not require additional closure systems.
|
127.
M1602.2 Return Air Openings. Return
air openings for heating, ventilation and air conditioning systems
shall comply with all of the following:
1.
|
Openings shall not be located less
than ten (10) feet (3,048 mm) measured in any direction from an open
combustion chamber or draft hood of another appliance located in the
same room or space.
|
2.
|
Return and transfer openings shall
be sized in accordance with the appliance or equipment manufacturer's
installation instructions, Manual D or the design of the registered
design professional.
|
3.
|
Return air shall not be taken from
a bathroom, toilet room, kitchen, garage, mechanical room, boiler
room, furnace room or unconditioned attic.
|
Exceptions:
| |
1.
|
Taking return air from a kitchen
is not prohibited where such return air openings serve the kitchen
only, and are located not less than ten (10) feet (3,048 mm) from
the cooking appliances.
|
2.
|
Dedicated forced-air systems serving
only the garage shall not be prohibited from obtaining return air
from the garage.
|
3.
|
Taking return air from an unconditioned
crawl space shall not be accomplished through a direct connection
to the return side of a forced-air furnace. Transfer openings in the
crawl space enclosure shall not be prohibited.
|
4.
|
Return air from one (1) dwelling
unit shall not be discharged into another dwelling unit.
|
5.
|
Return air may be taken from a bedroom
closet over sixty-four (64) square feet in area.
|
128.
M2105.19 Pipe Penetrations. Openings
for pipe penetrations in walls, floors and ceilings shall be larger
than the penetrating pipe. Openings in the foundation wall underground
shall be sealed to not allow groundwater into a building.
129.
G2408.4 (305.7) Clearances From Grade.
Equipment and appliances installed at grade level shall be supported
on a level concrete slab or other approved material extending not
less than two (2) inches (50.8 mm) above adjoining grade or shall
be suspended not less than six (6) inches (152 mm) above adjoining
grade. Such supports shall be installed in accordance with the manufacturer's
installation instructions.
130.
G2409.1 (308.1) Scope. This Section
shall govern the reduction in required clearances to combustible materials;
and combustible assemblies for chimneys, vents, appliances, devices
and equipment. Clearance requirements for air-conditioning equipment
and central heating boilers and furnaces shall comply with Sections
G2409.3 and G2409.4.
131.
G2412.9 (401.9) Identification. Each
length of pipe and tubing, as produced by the manufacturer and prior
to use in the field, and each pipe fitting, utilized in a fuel gas
system, shall bear the identification of the manufacturer.
132.
G2412.10 (401.10) — Delete.
133.
G2439.7.4.1 (614.8.4.1) Specified
Length. The maximum length of the exhaust duct shall be thirty-five
(35) feet (10,688 mm) from the connection to the transition duct from
the dryer to the outlet terminal. Where fittings are used, the maximum
length of the exhaust duct shall be reduced in accordance with Table
G2439.7.4.1. The maximum length of the exhaust duct does not include
the transition duct.
134.
G2442.4 (618.4) Prohibited Sources.
Outdoor or return air for forced-air heating and cooling systems shall
not be taken from the following locations:
1.
|
Closer than ten (10) feet (3,048
mm) from an appliance vent outlet, a vent opening from a plumbing
drainage system or the discharge outlet of an exhaust fan, unless
the outlet is three (3) feet (914 mm) above the outside air inlet.
|
2.
|
Where there is the presence of objectionable
odors, fumes or flammable vapors; or where located less than ten (10)
feet (3,048 mm) above the surface of any abutting public way or driveway;
or where located at grade level by a sidewalk, street, alley or driveway.
|
3.
|
A hazardous or insanitary location
or a refrigeration machinery room as identified in the International
Mechanical Code.
|
4.
|
A room or space, the volume of which
is less than twenty-five percent (25%) of the entire volume served
by such system. Where connected by a permanent opening having an area
sized in accordance with Section G2442.2, adjoining rooms or spaces
shall be considered as a single room or space for the purpose of determining
the volume of such rooms or spaces.
|
Exception: The minimum volume requirement
shall not apply where the amount of return air taken from a room or
space is less than or equal to the amount of supply air delivered
to such room or space.
|
5.
|
A room or space containing an appliance
where such a room or space serves as the sole source of return air.
|
Exception: This shall not apply where:
|
1.
|
The appliance is a direct-vent appliance
or an appliance not requiring a vent in accordance with Section G2425.8.
| |
2.
|
The room or space complies with the
following requirements:
| |
2.1
|
The return air shall be taken from
a room or space having a volume exceeding one (1) cubic foot for each
ten (10) Btu/h (9.6L/W) of combined input rating of all fuel-burning
appliances therein.
| |
2.2
|
The volume of supply air discharged
back into the same space shall be approximately equal to the volume
of return air taken from the space.
| |
2.3
|
Return-air inlets shall not be located
within ten (10) feet (3,048 mm) of a draft hood in the same room or
space or the combustion chamber of any atmospheric burner appliance
in the same room or space.
| |
3.
|
Rooms or spaces containing solid
fuel-burning appliances, provided that return-air inlets are located
not less than ten (10) feet (3,048 mm) from the firebox of such appliances.
|
6.
|
A closet, bathroom, toilet room,
kitchen, garage, boiler room, furnace room or unconditioned attic.
|
Exceptions:
| |
1.
|
Where return air intakes are located
not less than ten (10) feet (3,048 mm) from cooking appliances and
serve only the kitchen area, taking return air from a kitchen area
shall not be prohibited.
|
2.
|
Dedicated forced-air systems serving
only a garage shall not be prohibited from obtaining return air from
the garage.
|
3.
|
Where a closet is provided with a
supply register, taking return air from the closet shall not be prohibited
where such closet is sixty-four (64) square feet or greater.
|
7.
|
A crawl space by means of direct
connection to the return side of a forced-air system. Transfer openings
in the crawl space enclosure shall not be prohibited.
|
135.
P2501.3 Licensing Of Plumbing Contractors. For licensing requirement refer to Section 520.040 of the Municipal Code of the City of St. Peters.
136.
P2503.5.1 Rough Plumbing. DWV systems
shall be tested on completion of the rough piping installation by
water or by air without evidence of leakage. Either test shall be
applied to the drainage system in its entirety or in sections after
rough-in piping has been installed, as follows:
1.
|
Water test. Each section shall be
filled with water to a point not less than five (5) feet (1,524 mm)
above the highest fitting connection in that section, or to the highest
point in the completed system. Water shall be held in the section
under test for a period of fifteen (15) minutes. The system shall
prove leak free by visual inspection.
|
2.
|
Air test. The portion under test
shall be maintained at a gauge pressure of five (5) pounds per square
inch (psi) (34 kPa) or ten (10) inches of mercury column (34 kPa).
This pressure shall be held without introduction of additional air
for a period of fifteen (15) minutes.
|
137.
P2609.1 Identification. Factory-made
pipes shall be listed and labeled, as produced by the manufacturer
and prior to use in the field, and installed in accordance with the
manufacturer's instructions.
Exception: Where the manufacturer
identification cannot be marked on pipe fitting and pipe nipples because
of the small size of such fittings, the identification shall be printed
on the item packaging or on documentation provided with the item.
138.
P2801.8 Water Heater Seismic Bracing.
In Seismic Design Categories D0, D1 and D2, water heaters shall
be anchored or strapped in the upper one-third (1/3) and in the lower
one-third (1/3) of the appliance to resist a horizontal force equal
to one-third (1/3) of the operating weight of the water heater, acting
in any horizontal direction, or in accordance with the appliance manufacturer's
recommendations.
139.
P2804.6.1 Requirements For Discharge
Pipe. The discharge piping serving a pressure-relief valve, temperature-relief
valve or combination valve shall:
1.
|
Not be directly connected to the
drainage system.
|
2.
|
Discharge through an air gap located
in the same room as the water heater.
|
3.
|
Not be smaller than the diameter
of the outlet of the valve served and shall discharge full size to
the air gap.
|
4.
|
Serve a single relief device and
shall not connect to piping serving any other relief device or equipment.
|
5.
|
Discharge to the floor, to the pan
serving the water heater or storage tank, to a waste receptor or to
the outdoors.
|
6.
|
Discharge in a manner not to be a
hazard; does not cause personal injury, structural damage, or otherwise
a nuisance.
|
7.
|
Discharge to a termination point
that is readily observable by the building occupants.
|
8.
|
Not be trapped.
|
9.
|
Be installed to flow by gravity.
|
10.
|
Terminate not more than six (6) inches
(152 mm) and not less than two (2) times the discharge pipe diameter
above the floor or waste receptor flood level rim.
|
11.
|
Not have a threaded connection at
the end of the piping.
|
12.
|
Not have valves or tee fittings.
|
13.
|
Be constructed of those materials
indicated in Section P2906.5 or materials tested, rated and approved
for such use in accordance with ASME A112.4.1.
|
14.
|
Be one (1) nominal size larger than
the size of the relief-valve outlet, where the relief-valve discharge
piping is constructed of PEX or PE-RT tubing. The outlet end of such
tubing shall be fastened in place.
|
140.
P2903.5 Water Hammer. The flow velocity
of the water distribution system shall be controlled to reduce the
possibility of water hammer. A water-hammer arrestor shall be installed
where quick-closing valves are used. Water-hammer arrestors shall
be installed in accordance with the manufacturer's installation instructions.
Water-hammer arrestors shall conform to ASSE 1010.
141.
P2904.1 General. When installed,
the design and installation of residential fire sprinkler systems
shall be in accordance with NFPA 13D or Section 2904, which shall
be considered equivalent to NFPA 13D. Partial residential sprinkler
systems shall be permitted to be installed only in buildings not required
to be equipped with a residential sprinkler system. Section P2904
shall apply to stand-along and multipurpose wet-pipe sprinkler systems
that do not include the use of antifreeze. A multipurpose fire sprinkler
system shall provide domestic water to both fire sprinklers and plumbing
fixtures. A stand-along sprinkler system shall be separate and independent
from the water distribution system.
142.
P3201.2.1 Trap Seal Protection. Traps
seals of emergency floor drain traps and traps subject to evaporation
shall be protected by one (1) of the methods in Sections P3201.2.1.1
through P3201.2.1.4.
Exception: Basement floor drains
with a condensate line draining to it, or with a deep trap seal.
143.
E3401.1.1 Licensing Of Electrical Contractors. (Refer to Chapter 510 of the Municipal Code of the City of St. Peters for licensing requirements.)
144.
E3902.2 Garage And Accessory Building
Receptacles. All 125-volt, single-phase, 15- or 20-ampere receptacles
installed in garages and grade-level portions of unfinished accessory
buildings used for storage or work areas shall have ground-fault circuit-interrupter
protection for personnel.
Exception: Fastened in place appliances
or outlets designated for refrigerators/freezers, garage door openers,
etc.
145.
E3902.5 Unfinished Basement Receptacles.
12-volt, single-phase, 15- and 20-ampere receptacles installed in
unfinished basements shall have ground-fault circuit-interrupter protection
for personnel. For purposes of this Section, unfinished basements
are defined as portions or areas of the basement not intended as habitable
rooms and limited to storage areas, work areas, and similar areas.
Exceptions:
1.
|
A receptacle supplying only a permanently
installed fire alarm or burglar alarm system. Receptacles installed
in accordance with this exception shall not be considered as meeting
the requirements of Section E3901.9.
|
2.
|
Fastened in place appliances or outlets
designated for refrigerators/freezers.
|
146.
E3902.6 Kitchen Receptacles. 125-volt,
single-phase, 15- and 20-ampere receptacles that serve countertop
surfaces shall have ground-fault circuit-interrupter protection for
personnel. [210.8(A)(6)]
Exception: Fastened in place appliances
or outlets designated for refrigerators/freezers.
147.
E3902.9 — Delete.
148.
E3902.10 — Delete.
149.
E3902.14 Location Of Ground-Fault
Circuit Interrupters. Ground-fault circuit-interrupters shall be installed
only in a readily accessible location.
150.
E3902.16 Arc-Fault Circuit-Interrupter
Protection. Branch circuits that supply 120-volt, single-phase, 15-
and 20-ampere outlets installed in bedrooms shall be protected by
any of the following: [210.12(A)]
1.
|
A listed combination-type arc-fault
circuit-interrupter, installed to provide protection of the entire
branch circuit. [210.12(A)(1)]
| |
2.
|
A listed branch/feeder-type AFCI
installed at the origin of the branch-circuit in combination with
a listed outlet branch-circuit type arc-fault circuit-interrupter
installed at the first outlet box on the branch-circuit. The first
outlet box in the branch-circuit shall be marked to indicate that
it is the first outlet of the circuit. [210.12(A)(2)]
| |
3.
|
A listed supplemental arc protection
circuit breaker installed at the origin of the branch-circuit in combination
with a listed outlet branch-circuit type are-fault circuit-interrupter
installed at the first outlet box on the branch-circuit where all
of the following conditions are met:
| |
3.1
|
The branch-circuit wiring shall be
continuous from the branch-circuit overcurrent device to the outlet
branch-circuit arc-fault circuit-interrupter.
| |
3.2
|
The maximum length of the branch-circuit
wiring from the branch-circuit overcurrent device to the first outlet
shall not exceed fifty (50) feet (152 m) for 14 AWG conductors and
seventy (70) feet (21.3 m) for 12 AWG conductors.
| |
3.3
|
The first outlet box in the branch-circuit
shall be marked to indicate that it is the first outlet of the circuit.
[210.12(A)(3)]
| |
4.
|
A listed outlet branch-circuit type
arc-fault circuit-interrupter installed at the first outlet on the
branch circuit in combination with a listed branch-circuit overcurrent
protective device where all of the following conditions are met:
| |
4.1
|
The branch-circuit wiring shall be
continuous from the branch-circuit overcurrent device to the outlet
branch-circuit arc-fault circuit-interrupter.
| |
4.2
|
The maximum length of the branch-circuit
wiring from the branch-circuit overcurrent device to the first outlet
shall not exceed fifty (50) feet (15.2 m) for 14 AWG conductors and
seventy (70) feet (21.3 m) for 12 AWG conductors.
| |
4.3
|
The first outlet box in the branch-circuit
shall be marked to indicate that it is the first outlet on the circuit.
| |
4.4
|
The combination of the branch-circuit
overcurrent device and outlet branch-circuit AFCI shall be identified
as meeting the requirements for a system combination-type AFCI and
shall be listed as such. [210.12(A)(4)]
| |
5.
|
Where metal outlet boxes and junction
boxes and RMC, IMC, EMT, Type MC or steel-armored Types AC cables
meeting the requirements of Section E3908.8, metal wireways or metal
auxiliary gutters are installed for the portion of the branch-circuit
between the branch-circuit overcurrent device and the first outlet,
a listed outlet branch-circuit type AFCI installed at the first outlet
shall be considered as providing protection for the remaining portion
of the branch-circuit. [210.12(A)(5)]
| |
6.
|
Where a listed metal or non-metallic
conduit or tubing or Type MC cable is encased in not less than two
(2) inches (50.8 mm) of concrete for the portion of the branch-circuit
between the branch-circuit overcurrent device and the first outlet,
a listed outlet branch-circuit type AFCI installed at the first outlet
shall be considered as providing protection for the remaining portion
of the branch circuit. [210.12(A)(6)]
|
Exception: AFCI protection is not
required for an individual branch-circuit supplying only a fire alarm
system where the branch-circuit is wired with metal outlet and junction
boxes and RMC, IMC, EMT or steel-sheathed armored cable Type AC or
Type MC meeting the requirements of Section E3908.8.
|
151.
E3902.17 Arc-Fault Circuit-Interrupter
Protection For Branch-Circuit Extensions Or Modifications. Where branch-circuit
wiring is modified, replaced, or extended in any of the areas specified
in Section E3902.16, the branch-circuit shall be protected by one
(1) of the following:
1.
|
A combination-type AFCI located at
the origin of the branch-circuit.
|
2.
|
An outlet branch-circuit type AFCI
located at the first receptacle outlet of the existing branch-circuit.
|
Exception: AFCI protection shall
not be required where the extension of the existing conductors is
not more than thirty (30) feet (9.5 m) in length and does not include
any additional outlets or devices. [210.12(B) Exception]
|
152.
E4002.14 — Delete.
[R.O. 2007 § 504.050; Ord. No. 4626 §§ 1—2, 9-14-2006; Ord.
No. 5543 §§ 1—2 (Exh. A(504.050)), 2-10-2011]
Any person violating any of the provisions
of the Code adopted in this Chapter shall be deemed guilty of an offense
and upon conviction thereof shall be fined in an amount not exceeding
five hundred dollars ($500.00) or be imprisoned in the City or County
Jail for a period of not exceeding ninety (90) days, or both such
fine and imprisonment. Each day such violation is committed or permitted
to continue shall constitute a separate offense and shall be punishable
as such hereunder.