[Added 10-5-81 by L.L. No. 2-1981]
[Amended 12-3-1990 by L.L. No. 15-1990; 9-8-1992 by L.L. No. 7-1992]
A. 
The Board of Trustees of the Village of Ardsley recognizes that during the past few years the Ardsley Volunteer Fire Department has experienced an increase in the number of alarms. At the same time the number of active participating firemen has decreased, leaving the village vulnerable to fires. With an automatic fire sprinkler system, fires are extinguished at their inception and alarms are sounded to alert those in danger. Property damage and the loss of lives is also drastically reduced. It is the purpose of this section to supplement the mandatory program of installing a fire sprinkler system in all new construction, in effect since October 5, 1981.
B. 
All new buildings which are constructed after the effective date of this Article shall be required to have approved fire sprinkler systems in accordance with nationally accepted standards.
C. 
Day-care centers, as defined by the New York State Department of Social Services, licensed after the effective date of this section, regardless of location, shall be required to have approved fire sprinkler systems in accordance with nationally accepted standards.
D. 
All buildings and occupancies required by this section to install approved automatic fire sprinkler systems, must do so, irrespective of installation in a basement area.
E. 
No building permit shall be issued for the construction of any building unless compliance is met by submission of an approved fire sprinkler system design drawing.
F. 
No certificate of occupancy shall be issued for occupancy or use of any building required to have an approved fire sprinkler system, unless such system is installed, inspected, tested and approved.
G. 
Fire sprinklers shall not be required to be installed in spaces where the discharge of water would be hazardous. In such places, other approved fire-extinguishing equipment shall be provided, as approved by the Zoning Board of Appeals.
H. 
In addition to meeting the fire sprinkler requirements as herein before defined, all buildings more than two stories in height, constructed after the effective date of this section, other than single-family detached dwellings, shall conform to the following:
(1) 
All walls enclosing elevator shafts, except the walls with elevator door openings, shall be constructed to approved masonry materials.
(2) 
Walls enclosing all stairwells and vertical shafts shall be constructed of approved masonry materials.
(3) 
A standpipe system shall be provided in a manner approved by the Fire Prevention Bureau. It shall meet all the requirements of NFPA Standards No. 14. The system shall have internal threaded swivel fittings composed of two-and-one-half-inch New York Corporation thread.
I. 
All fire sprinkler systems other than those in one- and two-family detached residences shall be inspected, tested and certified annually by an approved fire sprinkler company.
J. 
The controlling fire prevention standards for the Village of Ardsley are on file in the office of the Village Clerk.
K. 
The only accepted thread is two-and-one-half-inch New York Corporation.
L. 
Where practical difficulties or unnecessary hardship may result from enforcement of the strict letter of any provision of this section, applications for variances consistent with the spirit of this section may be made to and acted upon by the Zoning Board of Appeals of the Village of Ardsley. The Board is empowered to grant a variance when it has found the application of a strict letter of this section would create a practical difficulty or unnecessary hardship for the applicant and the omission of an approved sprinkler system for all or part of the building will not significantly jeopardize human life.
M. 
In granting any variances, the Zoning Board of Appeals may impose such conditions as such Board may reasonably determine necessary to mitigate the consequences of the omission of an approved sprinkler system from all or part of any building, including the requirement that alternative forms of fire-extinguishing equipment shall be provided or a requirement of additional alarms or other devices to ameliorate the effects of having no sprinkler systems.
N. 
The provisions of this article shall apply to an entire existing commercial building or individual leased spaced or use, as if newly erected, where the square footage of any renovations, alterations, additions or interior repairs exceed 50% of the entire building, leased premises or individual use, whichever shall be smaller, or when any change or partial change in the use of the premises occurs which requires the issuance of a building permit.
[Added 5-18-1998 by L.L. No. 2-1998]
As used in this article, the following terms shall have the meanings indicated:
HEAT DETECTOR
The minimal permissible heat detector shall be of single-station type, approved by Underwriters Laboratories, Inc. (UL), and/or Factory Mutual and shall be either mechanically, electrically or gas powered.
SMOKE AREA
An area totally enclosed which contains at least 50 square feet of area but not more than 600 square feet of area.
SMOKE DETECTOR
The minimal permissible smoke detector shall be of the single-station type, approved by Underwriters Laboratories, Inc. (UL), and/or Factory Mutual and shall be powered by ordinary current or by a battery having a usable life of at least 12 months' duration.
A. 
All buildings, other than those used as dwellings, which do not contain approved sprinkler systems shall contain (except in areas where heat detection devices are separately required) one smoke detector for each smoke area and, in the case of enclosed hallways, corridors and vestibules, one smoke detector for each 50 linear feet.
B. 
All buildings, other than those used as dwellings, which do not contain approved sprinkler systems shall contain, in each room with cooking facilities, boilers, furnaces or other heat-producing units, one heat detection device for each smoke area.
C. 
All multiple-family dwellings shall have smoke detectors in the following locations:
(1) 
At the top of any stairwell if such stairwell is open to common hallways and/or corridors.
(2) 
One smoke detector for each 50 linear feet in common hallways and/or corridors.
(3) 
Storage areas: in areas exceeding 50 square feet, a minimum of one smoke detector for each smoke area or portion thereof.
D. 
All multiple-family dwellings shall be required to have at least one heat detector in each boiler room.
E. 
Working order. All smoke and heat detection devices required hereunder must, at all times, be in good working order.
F. 
Effective date.
(1) 
Except as provided in Subsection F(2) herein, this section shall take effect November 1, 1981, for all new construction in the Village of Ardsley.
(2) 
This section shall take effect in all existing buildings in the Village of Ardsley in the following manner:
(a) 
Fifty percent of the total smoke and heat detectors required in a building shall be installed with 12 months of the effective date of this article.
(b) 
The remaining 50% of the smoke and heat detectors shall be installed within 24 months of the effective date of this Article.
A. 
All occupancies within the Village of Ardsley, other than one- or two-family residences, shall have auxiliary rechargeable battery lighting of at least 90 minutes duration in all approved routes of egress. Such lighting shall be designed to provide safe passage under emergency conditions. A minimum standard of two footcandles shall be supplied for each area to be illuminated.
[Amended 12-3-1990 by L.L. No. 15-1990; 9-8-1992 by L.L. No. 7-1992]
B. 
Applicability; when effective.
(1) 
The provisions of this section shall apply to all new construction or new occupancies immediately.
(2) 
As to existing multiple dwellings, this section shall become effective in the following manner:
(a) 
Fifty percent of the total required emergency lighting in a building shall be installed within 12 months of the effective date of this Article.
(b) 
The remaining 50% of the total required emergency lighting shall be installed within 24 months of the effective date of this Article.
(3) 
The provisions of this section shall apply to all existing occupancies six months after the effective date of this Article.
A. 
All motor fuel storage tank installations must be provided with a constant monitoring electronic leak-detecting system that gives visual and audible warning signals and is approved by the Fire Marshal. All motor fuel storage tanks installed prior to the enactment of this Article must be in compliance within 12 months of the effective date of this Article.
B. 
Whenever there is reason to believe that flammable liquid tanks or lines are leaking, the owners thereof shall advise the Ardsley Fire Department. Upon the request of the Fire Marshal or his assistant(s), the owner or operator of the facility shall have such suspect tank or lines tested for tightness. All costs for such testing shall be borne by either the owner, operator or supplier. Reason for giving notice of possible flammable liquid leak shall include, but not be limited to, warning signals provided by leak-detecting devices, discovery of inventory losses in excess of metered sales or use, the presence of liquid seepage in the reasonable vicinity of the tanks or lines or persistent odors in adjacent premises. Tank and line tests shall be those approved by the Ardsley Fire Department and shall include those meeting the criteria of National Fire Protection Association Bulletin No. 329, as amended, as to accuracy and method. Air tests shall not be made on existing underground tanks and lines. During installation of tanks where all joints, fittings and seams may be air-tested in the presence of the Fire Marshal or his assistant(s), a soap solution or other bubble-producing material shall be applied to the new tank fittings and piping. The recommended pressure for new tanks and piping shall not exceed 10 pounds per square inch.