A. 
Where such provisions for service connections have been originally constructed as part of the public sewer construction, the Sewer District shall locate the connection point and the user shall excavate and connect to such point, subject to inspection and acceptance of the Sewer District.
B. 
For new connection points where provisions for service connections have not been originally constructed as part of the public sewer construction, the Sewer District shall establish the connection point location and the user shall ensure appropriate connection is made, subject to inspection and acceptance of the Sewer District.
A. 
Any septic tanks, cesspools and similar private wastewater disposal facilities shall be cleaned of sludge and filled with a suitable material or excavated and removed or demolished in accordance with accepted procedures to minimize health risk. Such works shall be covered by earth, concrete or suitable material to exclude rodents and flies and to prevent odors and prevent other nuisance conditions. The point on the privately owned collection system sewer where wastewater is to be intercepted and diverted to the public system shall be broken and separated from the private system and shall be permanently plugged.
B. 
No sewer shall be covered until after it has been inspected, tested and accepted by the Town Sewer Department.
A. 
In all buildings in which any building sewer is too low to permit gravity flow to the public sewer, sanitary sewage carried by such sewer shall be lifted by a grinder pump unit and discharged to the public sanitary sewer at the expense of the owner.
B. 
When a control manhole is required, the manhole will be located such that no other direct or indirect connections shall exist between the control manhole and the connection point.
C. 
All plumbing work performed and materials used shall conform to the Town of Somerset and New York State Building Codes.
A. 
Gravity sewers shall be PVC nonpressure pipe, labeled SDR35, ASTM Specification D3034. All joints shall be compression-type joints with Neoprene or rubber, circular gaskets. The gasket shall be factory installed and locked in such that no displacement occurs during the joining of the pipe.
B. 
Size, slope, alignment and depth.
(1) 
The size, slope and alignment of the gravity sewer shall be subject to approval of the Sewer District. Grade or slope for various pipe sizes shall not be less than the following:
(a) 
Four-inch pipe: 1/8 inch per foot.
(b) 
Six-inch pipe: 1/16 inch per foot.
(c) 
Over six inches: plan required for engineering review and acceptance.
(2) 
The depth shall be sufficient to afford protection from freezing and against physical damage (normally four-foot minimum depth). The gravity sewer shall be laid at a uniform grade. The line shall be straight or laid with properly curved pipe and fittings. Changes in alignment direction greater than 45° shall be provided with cleanouts accessible for cleaning.
C. 
The gravity sewer shall have sufficient horizontal and vertical separation from the water service or any potable waterline.
D. 
All gravity sewers shall be bedded to six inches above the pipe barrel and six inches below. The bedding material shall be stone of a maximum dimension of one inch and shall be placed to eliminate voids between the pipe and the disturbed soil. If the soil conditions appear unstable, the Sewer District may require additional methods of support for the pipe.
E. 
All gravity sewers shall be tested for leakage after installation. The test shall be conducted on all joints that would be exposed to infiltration of groundwater, surface water or other extraneous sources of nonpolluted waters. The test shall be conducted from the trap and vent to the building plumbing system. The test shall be conducted by the Town Sewer Department. If an air test is required, the sewers shall be charged with air to pressure of four pounds per square inch. The sewer shall show a loss of no greater than 0.5 pounds per square inch over a ten-minute period.
F. 
In certain cases where a gravity sewer is being replaced, the Sewer District may allow the use of high-density polyethylene pipe, by placing the polyethylene pipe inside the existing sewer. In this situation, the pipe shall have a minimum SDR of 18 and shall conform to all applicable ASTM specifications for this material. The joints shall be thermal butt fused between lengths of polyethylene pipe with the inner bead removed. Joints between the polyethylene and other pipe materials or the trap and vent shall be by a coupling acceptable to the Sewer District. Express permission of the Sewer District shall be obtained prior to proceeding with this type of installation. Application for permission shall be accomplished by a plan and a list of materials, sizes and depths.
A. 
Installation of grinder pumps.
(1) 
The dimensions of the grinder pump basin are two feet in diameter by six feet high. The excavation should be kept as small as possible while allowing enough room for installation.
(2) 
The grinder pump basin should be aligned so that the connections for the incoming sewer line as well as the discharge line (polyethylene tubing) are facing in proper directions.
(3) 
The top of the grinder pump basin should be kept two inches above the adjacent ground level with the ground graded up to it.
(4) 
The grinder pump must be set on a minimum of three inches of sand (for leveling the unit as well as for protection of the base).
(5) 
A minimum of 17 cubic feet of concrete must be poured around the base of the grinder pump basin prior to backfilling. This concrete is necessary to prevent the unit from floating when the groundwater level rises. Concrete shall be confined to the area directly adjacent to the basin and not allowed to spread out.
B. 
Installation of polyethylene tubing.
(1) 
Polyethylene tubing is used to transport the sewage from the grinder pump to the main sewer at the street. For outside grinder pump units, it is connected directly to the discharge pipe and the unit. For inside grinder pump units, it is connected to the PVC piping which is installed through the basement wall. At the street, it is connected to a redundant check valve.
(2) 
When possible, the polyethylene tubing shall be installed in one continuous length. If necessary, splices are to be made with compression fittings manufactured by Mueller.
(3) 
The polyethylene tubing shall be installed deep enough so that there is a minimum of four feet of earth cover over it for its entire length.
(4) 
The polyethylene tubing is not to be bent in a radius smaller than 55 inches.
(5) 
Detectable tape shall be installed eight inches directly above the polyethylene tubing for its entire length.
(6) 
Backfilling must be done with earth that is free of stones, rocks, sharp objects, debris, etc. The backfill shall be carefully tamped as it is being placed to prevent settlement.
C. 
Materials.
(1) 
Polyethylene discharge tubing shall be one-and-one-half-inch nominal copper pipe size water service tubing, Class 160, SDR-9, conforming to ASTM 2737 specifications. The connections to the grinder pump unit and redundant check valve shall be made utilizing Mueller compression fittings and bronze nipples. All other fittings utilized in the installation shall also be bronze.
(2) 
Detectable tape shall be Terra-Tape D as manufactured by the Giffolyln Company of Houston, Texas, or equal; three inches wide; orange-colored and continuously imprinted with the warning "Caution - Sewer Line Buried Below" in black letters. (See Figure 2.)[1]
[1]
Editor's Note: Figure 2 is included as an attachment to this chapter.
(3) 
Curb stop valve and box shall be installed by the Town of Somerset Sewer Department and be located at the highway boundary.
(4) 
Redundant check valve shall be obtained from the Town of Somerset Sewer Department and be located at the curb stop on the grinder pump unit side.
(5) 
Grinder pump units shall be obtained from the Town of Somerset Sewer Department.
D. 
Electrical installation.
(1) 
The electrical load center shall be NEMA No. 1 surface-mounted, two-hundred-fifty-volt, thirty-amp, single-phase, neutral-buss, galvanized steel with gray baked-enamel finish. Feeders from main panel shall be No. 12, including three insulated conductors and one equipment ground. The grinder pump shall be protected by a twenty-amp, double-pole circuit breaker using No. 12 three wire and equipment ground.
(2) 
Emergency-generator enclosure. The emergency-generator enclosure NEMA 3R shall be mounted as described on the grinder-pump control-panel schematic.[2] It shall consist of 16-gauge, galvanized steel with gray baked-enamel finish. The minimum size shall be eight inches by six inches by four inches deep with provisions for a padlock. The plug and receptacle for the emergency-generator connection shall be twist-locked, twenty-amp, two-hundred-fifty-volt, three-pole and NEMA Configuration L10-20. The AC-DC transfer switch shall consist of a double-throw switch, two-hundred-forty-volt AC, three-pole, NEMA Type 3R.
[2]
Editor's Note: See Figure 3, which is included as an attachment to this chapter.
(3) 
The grinder pump control panel shall be mounted (see Figure 3) on the same side of building as the grinder pump is installed. Wiring from the emergency-generator enclosure to the grinder pump shall consist of four No. 12 THHN (power conductors) and 12 No. 14 THHN color-coded control wires into one-inch Schedule 40 PVC conduit.
(4) 
Inside alarm panel. The inside alarm annunciator shall be one-hundred-ten-volt connected to the No. 6 and natural terminals in the grinder pump control panel. This will operate in conjunction with the red light on the outside of the control panel. It shall be mounted on a four-inch round box cover at the best audible location inside the building. Feed wiring for the inside annunciator will come from the emergency-generator enclosure where it enters into the building.
NOTE: Waterproofing material provided with the unit must be applied to conduit from inside of the pump unit reservoir. All electrical work performed and materials used shall be in accordance with the National Electrical Code. All installations require the Board of Fire Underwriters inspection.
[Amended 5-11-2010 by L.L. No. 1-2010; 10-11-2011 by L.L. No. 6-2011]
A. 
The rate schedule is established so that sufficient revenue is collected to meet the debts presently incurred or to be incurred by the Somerset-Barker Sewer District. The rate schedule, as amended from time to time by resolution of the Town Board, is on file with the Town Clerk.
B. 
Billing:
(1) 
The indirect benefit charges, the direct benefit charges and unit charges shall be billed via the county and Town tax bill and shall be payable herewith.
(2) 
The user charges shall be billed quarterly via the Town of Somerset billing system and shall be payable within 30 days of the date of billing. Past-due amounts shall receive a surcharge of 10% added to the following quarterly bill and every past-due unpaid balance thereafter. Any unpaid user charges on or before October 1 shall be assessed against the user's property on the next current Town tax bill.
(3) 
All rates shall be reviewed annually. User charges shall provide sufficient funds for continued operation and maintenance of the publicly owned treatment works. Unexpended revenue shall be transferred to the budget established for the following year.
C. 
An indirect benefit charge shall be levied on all parcels within the Sewer District which do not have sanitary sewers directly available for use.
D. 
The direct benefit charge shall be levied on all parcels within the Sewer District which have sanitary sewers directly available for use, whether or not the owner has made connection to the sewer.
E. 
The unit charge and user charge shall be levied against property owners that have made connection to the sewer.
F. 
The first repair of a vent pipe in the Town-owned portion of a sewer service connection shall be free per homeowner per parcel. Subsequent repairs shall be $50.