In all areas of special flood hazard, the following standards are required:
A. 
Anchoring.
(1) 
All new construction and substantial improvements shall be anchored to prevent flotation, collapse or lateral movement of the structure.
(2) 
All manufactured homes shall be installed using methods and practices which minimize flood damage. Manufactured homes must be elevated and anchored to resist flotation, collapse or lateral movement. Manufactured homes shall be elevated in accordance with § 46-14B. Methods of anchoring may include, but are not to be limited to, use of over-the-top or frame ties to ground anchors. This requirement is in addition to applicable state and local anchoring requirements for resisting wind forces.
(3) 
All recreational vehicles placed on site for longer than 180 consecutive days and not fully licensed and ready for highway use must be elevated and anchored to resist flotation, collapse or lateral movement. Recreational vehicles shall be elevated in accordance with § 46-14B.
B. 
Construction materials and methods.
(1) 
All new construction and substantial improvements shall be constructed with materials and utility equipment resistant to flood damage.
(2) 
All new construction and substantial improvements shall be constructed using methods and practices that minimize flood damage.
C. 
Utilities.
(1) 
Electrical, heating, ventilation, plumbing, air-conditioning equipment and other service facilities shall be designed and/or located so as to prevent water from entering or accumulating within the components during conditions of flooding. When designed for location below the base flood elevation, a professional engineer's or architect's certification is required.
(2) 
All new and replacement water supply systems shall be designed to minimize or eliminate infiltration of floodwaters into the system.
(3) 
New and replacement sanitary sewage systems shall be designed to minimize or eliminate infiltration of floodwaters.
(4) 
On-site waste disposal systems shall be located to avoid impairment to them or contamination from them during flooding.
D. 
Subdivision proposals.
(1) 
All subdivision proposals shall be consistent with the need to minimize flood damage.
(2) 
All subdivision proposals shall have public utilities and facilities such as sewer, gas, electrical and water systems located and constructed to minimize flood damage.
(3) 
All subdivision proposals shall have adequate drainage provided to reduce exposure to flood damage.
(4) 
Base flood elevation data shall be provided by the permit applicant for subdivision proposals and other proposed developments (including proposals for manufactured home and recreational vehicle parks and subdivisions) greater than either 50 lots or five acres.
E. 
Encroachments.
(1) 
All proposed development in riverine areas where no flood elevation data are available (unnumbered A Zones) shall be reviewed as set forth in § 46-12A(3) to determine the effects of the encroachment on the flood-carrying capacity of the stream. The local administrator may require submission of additional technical analyses and data necessary to complete the determination.
(2) 
In all areas of special flood hazard in which base flood elevation data are available pursuant to § 46-12B or Subsection D(4) and no floodway has been determined, the cumulative effects of any proposed development, when combined with all other existing and anticipated development, shall not increase the water surface elevation of the base flood more than one foot at any point.
(3) 
In all areas of special flood hazard where floodway data are provided or available pursuant to § 46-12B, the requirements of § 46-15, Floodways, shall apply except as provided in Subsection E(4).
(4) 
Notwithstanding any other provisions of this chapter, certain development in Zones A1 - 30, AE and AH may be permitted to increase the water surface elevation of the base flood (e.g. dams, levees, etc.), provided that the Mayor endorses application to the Federal Emergency Management Agency (FEMA), the permit applicant provides all necessary data and analyses and pays all fees and FEMA approval is received.
(5) 
The local administrator shall require within Zones AH and AO adequate drainage paths around structures on slopes to guide floodwaters around and away from proposed structures.
In all areas of special flood hazard where base flood elevation data has been provided as set forth in § 46-6, Basis for establishing areas of special flood hazard, and § 46-12B, Use of other base flood and floodway data, the following standards are required:
A. 
Residential construction. New construction and substantial improvements of residential structures shall:
(1) 
In Zones A1 - 30, AE and AH, have the lowest floor, including basement or cellar, elevated to or above the base flood elevation.
(2) 
In all areas of special flood hazard, have fully enclosed areas below the lowest floor that are usable solely for parking of vehicles, building access or storage in an area other than a basement and which are subject to flooding designed to automatically equalize hydrostatic flood forces on exterior walls by allowing for the entry and exit of floodwaters. Designs for meeting this requirement must either be certified by a licensed professional engineer or architect or meet or exceed the following minimum criteria:
(a) 
A minimum of two openings having a total net area of not less than one square inch for every square foot of enclosed area subject to flooding shall be provided.
(b) 
The bottom of all such openings shall be no higher than one foot above the lowest adjacent finished grade.
(c) 
Openings may be equipped with louvers, valves, screens or other coverings or devices, provided that they permit the automatic entry and exit of floodwaters.
(3) 
Within any AO Zone, have the lowest floor, including basement, elevated above the highest adjacent grade at least as high as the depth number specified in feet on the community's FIRM (at least two feet if no depth number is specified).
(4) 
Within any A Zone, when no base flood data are available, have the lowest floor elevated at least three feet above the highest adjacent grade.
B. 
Manufactured homes and recreational vehicles.
(1) 
A manufactured home that is placed or substantially improved on a site in an A1 - 30, AE or AH Zone that is either outside of a manufactured home park or subdivision; in a new manufactured home park or subdivision as herein defined; in an expansion to an existing manufactured home park or subdivision as herein defined; or in an existing manufactured home park or subdivision as herein defined on which a manufactured home has incurred substantial damage as the result of a flood shall be elevated on a permanent foundation such that the lowest floor is elevated to or above the base flood elevation and is securely anchored to an adequately anchored foundation system to resist flotation, collapse and lateral movement.
(2) 
A manufactured home to be placed or substantially improved on a site located in a A1 - 30, AE or AH Zone in a manufactured home park or subdivision, as herein defined, that is not subject to the provisions of Subsection B(1) shall be elevated so that either the lowest floor of the manufactured home is at or above the base flood elevation or the manufactured home chassis is supported by reinforced piers or other foundation elements of at least equivalent strength that are no less than 36 inches in height above grade and are securely anchored to an adequately anchored foundation system.
(3) 
New construction or substantial improvements of manufactured homes in Zone A, where no base flood elevation data are available, shall be elevated at least three feet above the highest adjacent grade.
(4) 
All recreational vehicles placed on site for longer than 180 consecutive days and not fully licensed and ready for highway use must be elevated in accordance with Subsection B(1), (2) or (3).
(5) 
Manufactured homes and recreational vehicles, on site for longer than 180 consecutive days, with fully enclosed areas below the lowest floor, must meet the requirements of Subsection A(2).
C. 
Nonresidential construction.
(1) 
In Zones A1 - 30, AE and AH, new construction and substantial improvements of any commercial, industrial or other nonresidential structure, together with attendant utility and sanitary facilities, shall either:
(a) 
Have the lowest floor, including basement or cellar, elevated to or above the base flood elevation; or
(b) 
Be floodproofed so that the structure is watertight below the base flood level with walls substantially impermeable to the passage of water. All structural components located below the base flood level must be capable of resisting hydrostatic and hydrodynamic loads and the effects of buoyancy.
(2) 
In an AO Zone, all new construction and substantial improvements shall have the lowest floor, including basement, elevated above the highest adjacent grade at least as high as the depth number specified in feet on the community's FIRM (at least two feet if no depth number is specified).
(3) 
In an A Zone, when no base flood data are available, have the lowest floor elevated at least three feet above the highest adjacent grade.
(4) 
If the structure is to be elevated, fully enclosed areas below the lowest floor that are usable solely for parking of vehicles, building access or storage in an area other than a basement and which are subject to flooding shall be designed to automatically (without human intervention) equalize hydrostatic forces on exterior walls by allowing for the entry and exit of floodwaters. Designs for meeting this requirement must either be certified by a licensed professional engineer or a licensed architect or meet the following criteria:
(a) 
A minimum of two openings having a total net area of not less than one square inch for every square foot of enclosed area subject to flooding shall be provided.
(b) 
The bottom of all such openings shall be no higher than one foot above the lowest adjacent finished grade.
(c) 
Openings may be equipped with louvers, valves, screens or other coverings or devices, provided that they permit the automatic entry and exit of floodwaters.
(5) 
If the structure is to be floodproofed, a licensed professional engineer or architect shall develop and/or review structural design, specifications and plans for the construction and shall certify that the design and methods of construction are in accordance with accepted standards of practice for meeting the provisions of Subsection C(1)(b), including the specific elevation (in relation to mean sea level) to which the structure is floodproofed.
(6) 
The local administrator shall maintain on record a copy of all such certificates noted in this section.
Located within areas of special flood hazard are areas designated as floodways (see definition, § 46-4). The floodway is an extremely hazardous area due to high-velocity floodwaters carrying debris and posing additional threats from potential erosion forces. When floodway data is available for a particular site as provided by § 46-6 or, when applicable, § 46-12B, all encroachments, including fill, new construction, substantial improvements and other development, are prohibited within the limits of the floodway unless a technical evaluation demonstrates that such encroachments shall not result in any increase in flood levels during the occurrence of the base flood discharge.