The following items are the additions, insertions and changes
to the International Fire Code:
Section 101.1 Title.
Delete all and insert "These regulations shall be known as the
Fire Code of the Village of Lincolnwood hereinafter referred to as 'this
code.' The Village of Lincolnwood shall be inferred whenever
the term 'Village' is used in this code."
Add (new section) 105.4.2.2 Hydraulically calculated automatic
fire sprinkler system areas.
Insert "For each hydraulically calculated automatic fire sprinkler
system area identified, on submitted shop drawings, provide a copy
of the hydraulic nameplate."
Add (new section) 106.5 Recovery of third party fees.
Insert "The Village may recover all third-party vendor and consultant
fees incurred by the Village for fire plan review and fire inspection.
Said costs may be added to the permit fees or collected prior to the
issuance of a certificate of occupancy."
Section 109 Board of Appeals.
Delete in its entirety and insert new section title 109
Appeals.
Add (new section) 109.1 General.
Insert lines (A, 1 through 3, B and C) as follows:
Section 110.4 Violation penalties.
Delete all and insert "Any person who violates a provision of
this code or fails to comply with any of the requirements thereof
or who erects, constructs, alters, repairs or does work in violation
of the approved construction documents or directive of the Fire Code
Official, or of a permit or certificate issued under the provisions
of this code, shall be subject to penalties as prescribed by law or
as set forth in the Village's Annual Fee Resolution."
Section 112.4 Failure to comply.
Delete all and insert "Any person who shall continue any work
after having been served with a stop-work order, except such work
as that person is directed to perform to remove a violation or unsafe
condition, shall be subject to either penalties as prescribed by law
or as set forth in the Village's Annual Fee Resolution."
Section 202 Definitions. Fire Area.
Delete all and insert "The aggregate floor area bounded by the
exterior walls of a building or structure, regardless of fire walls,
fire barriers or fire-resistance-rated horizontal assemblies."
Section 507.5.1 Where required.
Delete all and insert "Where a portion of the facility or building
hereafter constructed or moved into or within the jurisdiction is
more than 300 feet from a hydrant on a fire apparatus access road,
as measured by an approved route around the exterior of the facility
or building, on-site fire hydrants and mains shall be provided where
required by the fire code official."
Section 507.5.1.1 Hydrant for standpipe system.
Delete in its entirety and insert new section title "507.5.1.1
Hydrant for sprinkler or standpipe systems."
Add (new section) 507.5.1.1 Hydrant for sprinkler or standpipe
systems.
Insert "Buildings equipped with a sprinkler or standpipe system
installed in accordance with Section 905 shall have a fire hydrant
within 100 feet of the Fire Department connection."
Add (new section) 507.5.1.2 Fire Hydrant Locations and
Distribution.
Insert "Appendix C of the 2015 International Fire Code is adopted
in full and shall be made a part of this Code."
Add (new section) 901.6.4 Inspection and maintenance reports.
Insert "All inspection and maintenance reports shall be forwarded
annually to the Lincolnwood Fire Department using the Department's
third party inspection report service. Any company or agent doing
inspection and maintenance of fire protection systems shall be required
to register with the third party inspection report service, as well
as all buildings that have fire protection systems installed."
Section 903.2.1.1 Group A-1.1.
Delete and insert "1. A Group A-1 fire area exceeds 5,000 square
feet."
Section 903.2.1.3 Group A-3. 1.
Delete and insert "1. A Group A-3 fire area exceeds 5,000 square
feet."
Section 903.2.1.4 Group A-4. 1.
Delete and insert "1. A Group A-4 fire area exceeds 5,000 square
feet."
Add (new section) 903.2.2.1 Group B.
Insert "An automatic sprinkler system shall be provided throughout
all buildings containing a Group B fire area exceeding 5,000 square
feet."
Section 903.2.3 Group E. 1.
Delete and insert "1. A Group E fire area exceeds 5,000 square
feet."
Section 903.2.4 Group F-1.
Delete in its entirety and add (new section) 903.2.4 Group
F-1, F-2.
Section 903.2.4 Group F-1, F-2.
Insert "An automatic sprinkler system shall be provided throughout
all buildings containing a Group F-1 or F-2 occupancy where one of
the following conditions exists:
Add (new section) 903.2.4.2 Group F "Spec" buildings.
Insert "All 'spec' buildings with a Group F use having
a ceiling or roof height of 25 feet or greater shall be protected
with an ESFR fire sprinkler system or a hydraulically calculated fire
sprinkler system for Class IV commodities with rack storage calculated
to the greatest storage height."
Section 903.2.7 Group M. 1.
Delete and insert "1. A Group M fire area exceeds 5,000 square
feet."
Section 903.2.9 Group S-1.
Delete in its entirety and add (new section) 903.2.9 Group
S-1, S-2.
Section 903.2.9 Group S-1, S-2.
Insert "An automatic sprinkler system shall be provided throughout
all buildings containing a Group S-1 or S-2 occupancy where one of
the following conditions exists:
Add (new section) 903.2.9.3 Group S "Spec" buildings.
Insert "All 'spec' buildings with a Group S use having
a ceiling or roof height of 25 feet or greater shall be protected
with an ESFR fire sprinkler system or a hydraulically calculated fire
sprinkler system for Class IV commodities with rack storage calculated
to the greatest storage height."
Section 903.2.10 Group S-2 Enclosed parking garages.
Delete in its entirety.
Section 903.3.5 Water supplies.
Delete all and insert "Water supplies for automatic sprinkler
systems shall comply with this section and the standards referenced
in Section 903.3.1. The potable water supply shall be protected against
backflow in accordance with the requirements of this section and the
International Plumbing Code. For connections to public waterworks
systems, the water supply test used for design of fire protection
systems shall be adjusted to account for seasonal and daily pressure
fluctuations based on information from the water supply authority
and as approved by the fire code official. Hydrant water flow data
used for the design of any fire sprinkler system shall not be more
than one year old."
Section 903.3.5.2. Residential combination services.
Delete all and add (new section) 903.3.5.2 Domestic water separation.
903.3.5.2 Domestic water separation.
Insert "The domestic water service shall be separated from the
fire service in accordance with the Illinois Plumbing Code, most current
edition."
Add (new section) 903.3.5.3 Design safety factor.
Insert "The design of the fire sprinkler system shall provide
a minimum five psi safety factor in the fire protection system hydraulic
calculation. The system demand shall be minimum five psi below the
seasonal low water flow test supply."
Section 903.3.8.5 Calculations.
Delete all and insert "Provide a minimum 10% but not less than
5 psi minimum safety factor in the fire protection system hydraulic
calculation. The system demand shall be 5 psi minimum below the seasonal
low water flow test supply."
Section 903.4 Sprinkler system supervision and alarms.
Delete all and insert "Valves controlling the water supply for
automatic sprinkler systems, pumps, tanks, water levels and temperatures,
critical air pressures and water flow switches on all sprinkler systems
shall be electrically supervised by a fire alarm system."
Section 903.4.1 Monitoring.
Delete all and insert "Alarm, supervisory and trouble signals
shall be distinctly different and shall be automatically transmitted
to the Fire Department's communication center, via communication
method(s) approved by the Fire Code Official."
Add (new section) 903.4.2.1 Outside alarm indicators.
Insert "For commercial properties and residential buildings
with a Fire Department connection a weatherproof clear 75 cd audio/visual
device shall be mounted on the outside of a building or structure
over the location of the Fire Department connection in the immediate
area of the sprinkler system bell. The weatherproof clear 75 cd audio/visual
device shall activate on all alarms. The sprinkler system bell shall
activate on water flow only."
Add (new section) 903.4.2.2 Interior appliances, audible
and visible alarms.
Insert "Interior appliances, interior audible and visible alarms
supervised by a fire alarm system shall be provided in accordance
with Section 90."
Add (new section) 903.4.2.3 Inspector test valves.
Insert "Fire sprinkler system inspector test valves shall be
accessible at all times and shall be located no more than six feet
zero inches above the finished floor. For sprinkler systems with multiple
risers, each inspector test valve shall be marked for the riser and
area it serves."
Section 903.4.3 Floor control valves.
Delete all and insert "Indicating control valves and water flow
switches shall be provided at the point of connection to the riser
on each floor in multiple-story buildings."
Add (new section) 903.4.4 Automatic sprinklers.
Insert "When a building has numerous rooms protected by the
zoned sprinkler system, the Fire Department may require additional
smoke detectors for a more rapid means to identify the location of
smoke or fire."
Add (new section) 903.6 Outside access door.
Insert "Provide an outside access door, no less than 36 inches
in width and six feet eight inches in height, at all fire sprinkler
riser valve rooms and fire pump rooms."
Add (new section) 903.7 Sprinkler valve room.
Insert "All fire sprinkler main risers and valves shall be enclosed
within a room constructed with minimum one-hour fire barriers. Said
room shall be sized to maintain all required clearances to maintain,
repair and operate the system and all valves, and shall be sized to
maintain all required door clearances."
Add (new section) 903.8 Fire hydrants.
Insert "Fire hydrants shall be provided around the perimeter
of a building in no more than three-hundred-foot increments, and at
least one fire hydrant shall be located within 100 feet of the Fire
Department connection on the fire protection water supply to the building."
Add (new section) 903.9 Fire flow requirements.
Insert "Appendix B of the 2015 International Fire Code is adopted
in full and shall be made a part of this code."
Add (new section) 903.13 NFPA standards.
Insert "Whenever NFPA standards are listed or referenced within
this code, that entire list of NFPA standards, hereby adopted as Appendix
A, to this Article 5 shall be considered a part of this code."
Section 905.3.1 Height.
Delete all and insert "Class III standpipe systems shall be
installed throughout buildings where more than two stories in height,
or more than two stories below grade."
Add (new section) 905.3.9 Warehouse storage areas.
Insert "In all warehouse storage areas exceeding 20,000 square
feet, and where storage exceeds 12 feet in height, inside two-and-one-half-inch
fire hose valves with a one-and-one-half-inch reducer shall be provided
to a one-and-one-half-inch connection. Said valves shall be located
at each entrance door to the warehouse and/or storage area. Additional
two-and-one-half-inch fire hose valves shall be provided such that
no portion of the warehouse and/or storage area is more than 120 feet
of maximum travel distance to a fire hose valve. The location of all
obstructions and racking shall be clearly identified on the permit
drawings."
Add (new section) 905.3.9.1 Fire hose valve system.
Insert lines (A, 1 through 3) as follows:
Add (new section) 907.1.4 Addressable fire alarm systems.
Insert "All fire alarm systems shall be of the addressable type."
Section 907.2 Where required - New buildings and structures.
Delete all, including Exceptions, and insert "A fire alarm system
utilizing automatic fire detectors and manual fire alarm devices shall
be provided throughout all buildings and structures not provided with
an automatic sprinkler system complying with NFPA 13 or NFPA 13R."
Section 907.2.1 Group A.
Delete all including Exception:
Section 907.2.1.1 System initiation in Group A occupancies
with an occupant load of 1,000 or more.
Delete all including Exception:
Section 907.2.1.2 Emergency voice/alarm communication
captions.
Delete all including Exception:
Section 907.2.2 Group B.
Delete all including Exception:
Section 907.2.2.1 Ambulatory care facilities.
Delete all including Exception:
Section 907.2.3 Group E. 3.
Delete all.
Section 907.2.4 Group F.
Delete all including Exception:
Section 907.2.7 Group M.
Delete all and insert "A manual fire alarm system that activates
the occupant notification system in accordance with Section 907.5
shall be installed in Group M occupancies."
Section 907.2.8.1 Manual fire alarm system. Exceptions:
2.
Delete all.
Section 907.2.9.1 Manual fire alarm system. Exceptions:
2.
Delete all.
Section 907.2.10.1 Manual fire alarm system. Exceptions:
2.
Delete all.
Section 907.4.2.5 Protective covers.
Delete all and insert "Protective covers. Listed manual fire
alarm box protective covers shall be provided for all installed manual
fire alarm boxes to prevent malicious false alarms or to provide the
manual fire alarm box with protection from physical damage."
Section 907.5 Occupant notification systems.
Delete in its entirety and insert lines (A, 1 through 4) as
follows:
Add (new section) 907.5.2.3.4 In single-story multitenant
buildings of all use groups.
Insert "Multitenant buildings shall be designed as ring by tenant,
activated by a fire sprinkler system flow switch for that space or
automatic fire detection, and shall include a weatherproof clear 75
cd audio/visual device mounted on the outside of the building or structure
over the entrance to each tenant space as directed by the Fire Code
Official."
Add (new section) 907.6.7 Fire alarm panel location.
Insert "The fire alarm control panel or full function annunciator
panel shall be installed within 10 feet of the main entrance or in
a location approved by the Fire Code Official."
Add (new section) 912.7.1 Connection type.
Insert "All Fire Department connections shall be a five-inch
Storz connection with a thirty-degree turndown."
Add (new section) 913.4.2 Fire pump test header.
Insert lines (A, 1 through 2) as follows:
Section 1008.3.3 Rooms and spaces.
Insert line. "6. All rooms and areas containing the building
fire sprinkler riser(s), fire pump(s) and fire alarm control panel(s)."
Section 1103 Group I-2, Condition 2.
Delete all and insert "In addition to the requirements of section
1103.5.2, existing buildings of Group I-2, Condition 2 occupancy shall
be equipped throughout with an approved automatic sprinkler system
in accordance with Section 903.3.1.1. The automatic sprinkler system
shall be installed as established by the adopting ordinance prior
to final inspection."
Section 5704.2.9.6.1 Locations where above-ground tanks
are prohibited.
Delete all and insert "Storage of Class I and II liquids in
above-ground tanks outside of buildings is prohibited within the limits
established by law as the limits of districts in which such storage
is prohibited."
Section 5706.2.4.4. Locations where above-ground tanks
are prohibited.
Delete all and insert "Storage of Class I and II liquids in
above-ground tanks outside of buildings is prohibited within the limits
established by law as the limits of districts in which such storage
is prohibited."
Section 5806.2 Limitations.
Delete all and insert "Storage of Class I and II liquids in
above-ground tanks outside of buildings is prohibited within the limits
established by law as the limits of districts in which such storage
is prohibited."
Section 6104.2 Maximum capacity within established limits.
Delete all and insert "Within the limits established by law
restricting the storage of liquefied petroleum gas for the protection
of heavily populated or congested areas, the aggregate capacity of
any one installation shall not exceed a water capacity of 2,000 gallons
(7570 L)."
Chapter 80 Referenced Standards: NFPA
Delete all and insert "Reference the Village of Lincolnwood
Appendix A, List of Adopted NFPA Codes.