[CC 1988 §40.650; Ord. No. 578 §1, 10-17-1988; Ord. No. 692 §1, 7-2-1990; Ord. No. 920 §1, 12-20-1993; Ord. No. 2278 §1, 4-17-2006; Ord. No. 2594 §1, 5-5-2008; Ord.
No. 2748 §1, 6-15-2009; Ord. No. 2911 §1, 11-1-2010; Ord. No. 3707 §1, 6-19-2017]
A.
Comprehensive Building Code Adoption Including Building, Residential,
Fire, Plumbing, Mechanical, Fuel Gas, Swimming Pool And Spa, Existing
Building, Property Maintenance, Energy Conservation And Electrical
Regulations.
[Ord. No. 3776, 12-4-2017]
1.
Certain documents, one (1) copy of which are filed in the office of the City Clerk of the City of Lake Saint Louis, being marked and designated as the International Building Code, 2015 Edition, the International Residential Code, 2015 Edition, the International Fire Code, 2015 Edition, the International Plumbing Code, 2015 Edition, the International Mechanical Code, 2015 Edition, the International Fuel Gas Code, 2015 Edition, the International Property Maintenance Code, 2015 Edition, the International Energy Conservation Code, 2015 Edition, the International Swimming Pool and Spa Code, 2015 Edition, the International Existing Building Code, 2015 Edition, all as published by the International Code Council, and the National Electrical Code, 2014 Edition, as published by the National Fire Protection Association, along with all additions, deletions, insertions and changes identified herein, are hereby adopted as the Comprehensive Building Code of the City of Lake Saint Louis in the State of Missouri, for regulating and governing the conditions and maintenance of all property, buildings and structures; by providing the standards for supplied utilities and facilities and other physical things and conditions essential to ensure that structures are safe, sanitary and fit for occupation and use; and the condemnation of buildings and structures unfit for human occupancy and use and the demolition of such structures as herein provided; providing for the issuance of permits and collection of fees therefor; and each and all of the regulations, provisions, penalties, conditions and terms of said Building Code on file in the office of the City Clerk are hereby referred to, adopted, and made a part hereof, as if fully set out in this ordinance, with the additions, insertions, deletions and changes prescribed in Subsection (A)(2) of this Section.
2.
The Chief Building Official for the City of Lake Saint Louis
shall serve as the Official Administrator of the Comprehensive Building
Code of the City of Lake Saint Louis. Whenever and wherever reference
is made in any of the documents comprising the Comprehensive Building
Code of the City of Lake Saint Louis to the Building Official or the
Code Official or the Fire Code Official or the authority having jurisdiction,
that reference shall mean the Chief Building Official.
3.
Comprehensive Building Code additions, deletions, insertions
and changes.
a.
The following Sections of the 2015 International Building Code,
as published by the International Code Council, are hereby revised
as follows:
[A] 101.1 Title. These regulations shall be known as the Building
Code of the City of Lake Saint Louis, Missouri, and shall be cited
as such and will be referred to herein as "this code."
[A] 105.2 Work exempt from permit. Exemptions from permit requirements
of this code shall not be deemed to grant authorization for any work
to be done in any manner in violation of the provisions of this code
or any other laws or ordinances of this jurisdiction. Permits shall
not be required for the following:
Building:
1. Retaining walls that are not over four (4) feet (1,219 mm)
in height measured from the bottom of the footing to the top of the
wall, unless supporting a surcharge.
2. Sidewalks and driveways.
3. Painting, papering, tiling, carpeting, cabinets, counter
tops and similar finish work.
Electrical:
1. Listed cord-and-plug connected temporary decorative lighting.
2. Reinstallation of attachment plug receptacles but not the
outlets therefor.
3. Replacement of branch circuit overcurrent devices of the
required capacity in the same location.
4. Electrical wiring, devices, appliances, apparatus or equipment
operating at less than 25 volts and not capable of supplying more
than 50 watts of energy.
5. Minor repair work, including the replacement of lamps or
the connection of approved portable electrical equipment to approved
permanently installed receptacles.
Gas:
1. Portable heating, cooking or clothes drying appliances.
2. Replacement of any minor part that does not alter approval
of equipment or make such equipment unsafe.
3. Portable-fuel-cell appliances that are not connected to a
fixed piping system and are not interconnected to a power grid.
Mechanical:
1. Portable heating appliance.
2. Portable ventilation equipment.
3. Portable cooling unit.
4. Steam, hot or chilled water piping within any heating or
cooling equipment regulated by this code.
5. Replacement of any part that does not alter its approval
or make it unsafe.
6. Portable evaporative cooler.
7. Self-contained refrigeration system containing ten (10) pounds
(4.54 kg) or less of refrigerant and actuated by motors of 1 horsepower
(0.75 kW) or less.
8. Portable-fuel-cell appliances that are not connected to a
fixed piping system and are not interconnected to a power grid.
Plumbing:
1. The stopping of leaks in drains, water, soil, waste or vent
pipe, provided, however, that if any concealed trap, drain pipe, water,
soil, waste or vent pipe becomes defective and it becomes necessary
to remove and replace the same with new material, such work shall
be considered as new work and a permit shall be obtained and inspection
made as provided in this code.
2. The clearing of stoppages or the repairing of leaks in pipes,
valves or fixtures and the removal and reinstallation of water closets,
provided such repairs do not involve or require the replacement or
rearrangement of valves, pipes or fixtures.
[A] 109.4 Work commencing before permit issuance. Any person
who commences any work on a building, structure, electrical, gas,
mechanical or plumbing system before obtaining the necessary permits
shall be subject to penalties as prescribed by law. Each day that
a violation continues after due notice has been served shall be deemed
a separate offense.
Upon the request of a permit holder, the Building Official is
authorized to issue a temporary certificate of occupancy for a building
or structure, or part thereof, before the entire work covered by the
permit shall have been completed, provided that such portion or portions
shall be occupied safely and provided that the permit holder shall
provide to the City a cash surety bond in the form of cash, cashier's
check or certified check in an amount sufficient to cover the cost
of completion of the unfinished portion of the work covered by the
permit, but in no case less than one thousand dollars ($1,000.00),
prior to the issuance of the temporary certificate of occupancy, in
order to assure completion of construction work and site restoration.
The Building Official shall establish a date by which the incomplete
work shall be completed. All construction and site restoration work
shall be completed within no more than six (6) months of the date
the temporary certificate of occupancy is issued. In the event all
the construction and site restoration work covered by the permit has
not been completed to the satisfaction of the Building Official by
the date established, the temporary certificate of occupancy shall
be void and the cash bond shall be forfeited. In the event the unfinished
portion of the work has been completed to the satisfaction of the
Building Official by the date established, the cash bond shall be
returned. Failure to comply with these requirements shall be deemed
a violation of this Chapter and subject to penalties as prescribed
by law. Each day that a violation continues after due notice has been
served shall be deemed a separate offense.
[A] 113.1 General. The Lake Saint Louis Building Appeals Board
shall hear and decide appeals of orders, decisions or determinations
made by the Building Official relative to the application and interpretation
of this code. All rules and requirements associated with such an appeal,
as specified in the Lake Saint Louis Municipal Code, shall apply.
Application to appeal any order, decision or determination made by
the Building Official shall be filed with the Building Official within
twenty (20) days after the order, decision or determination was served,
on a form obtained from the Building Official.
[A] 113.1.1 Limitation of authority. The Lake Saint Louis Building
Appeals Board shall not have authority relative to interpretation
of the administration of this code nor shall such board be empowered
to waive requirements of this code.
1612.3 Establishment of flood hazard areas. To establish flood
hazard areas, the applicable governing authority shall adopt a flood
hazard map and supporting data. The flood hazard map shall include,
at a minimum, areas of special flood hazard as identified by the Federal
Emergency Management Agency in an engineering report entitled "The
Flood Insurance Study for the City of Lake Saint Louis, Missouri,"
dated January 20, 2016, as amended or revised with the accompanying
Flood Insurance Rate Map (FIRM) and Flood Boundary and Floodway Map
(FBFM) and related supporting data along with any revisions thereto.
The adopted flood hazard map and supporting data are hereby adopted
by reference and declared to be part of this Section.
b.
The following Sections of the 2015 International Residential Code,
as published by the International Code Council, are hereby revised
as follows:
R101.1 Title. These regulations shall be known as the Residential
Code for One- and Two-Family Dwellings of the City of Lake Saint Louis,
Missouri, and shall be cited as such and will be referred to herein
as "this code."
R105.2 Work exempt from permit. Exemption from permit requirements
of this code shall not be deemed to grant authorization for any work
to be done in any manner in violation of the provisions of this code
or any other laws or ordinances of this jurisdiction. Permits shall
not be required for the following:
Building:
1. Retaining walls that are not over four (4) feet (1219 mm)
in height measured from the bottom of the footing to the top of the
wall, unless supporting a surcharge.
2. Sidewalks and driveways.
3. Painting, papering, tiling, carpeting, cabinets, counter
tops and similar finish work.
R106.3.1 Approval of construction documents. Where the Building
Official issues a permit, the construction documents shall be approved
in writing or by a stamp that states "REVIEWED FOR CODE COMPLIANCE."
One (1) set of construction documents so reviewed shall be retained
by the Building Official. The other set may be kept at the site of
work or shall be made available at the time of inspection and shall
be open to inspection by the Building Official or a duly authorized
representative.
R108.6 Work commencing before permit issuance. Any person who
commences any work before obtaining the necessary permits shall be
subject to penalties as prescribed by law. Each day that a violation
continues after due notice has been served shall be deemed a separate
offense.
Exceptions:
1. Emergencies as defined in the Lake Saint Louis Municipal
Code.
2. Stakeouts and other necessary planning procedures, including
installation of BMPs or other erosion control methods.
R112.1 General. The Lake Saint Louis Building Appeals Board
shall hear and decide appeals of orders, decisions or determinations
made by the Building Official relative to the application and interpretation
of this code. All rules and requirements associated with such an appeal,
as specified in the Lake Saint Louis Municipal Code, shall apply.
Application to appeal any order, decision or determination made by
the Building Official shall be filed with the Building Official within
twenty (20) days after the order, decision or determination was served,
on a form obtained from the code official.
R112.1.1 Limitation of authority. The Lake Saint Louis Building
Appeals Board shall not have authority relative to interpretation
of the administration of this code nor shall such board be empowered
to waive requirements of this code.
Table R301.2(1). Included as an attachment to this Chapter.
R302.2 Townhouses. Common walls separating townhouses shall
be assigned a fire-resistance rating in accordance with Section R302.2,
Item 1 or 2. The common wall shared by two (2) townhouses shall be
constructed without plumbing or mechanical equipment, ducts or vents
in the cavity of the common wall. The wall shall be rated for fire
exposure from both sides and shall extend to and be tight against
exterior walls and the underside of the roof sheathing. Electrical
installations shall be in accordance with Chapters 34 through 43.
Penetrations of the membrane of common walls for electrical outlet
boxes shall be in accordance with Section R302.4.
1. Where a fire sprinkler system in accordance with Section
P2904 is provided, the common wall shall be not less than a 1-hour
fire-resistance-rated wall assembly tested in accordance with ASTM
E 119 or UL 263.
2. Where a fire sprinkler system in accordance with Section
P2904 is not provided, the common wall shall be not less than a 2-hour
fire-resistance-rated wall assembly tested in accordance with ASTM
E 119 or UL 263, or the common wall shall be two (2) independent 1-hour
fire-resistance-rated wall assemblies.
R302.5.1 Opening protection. Openings from a private garage
directly into a room used for sleeping purposes shall not be permitted.
Other openings between the garage and residence shall be equipped
with solid wood doors not less than one and three eighths (1 3/8)
inches (35 mm) in thickness, solid or honeycomb-core steel doors not
less than one and three eighths (1 3/8) inches (35 mm) thick,
or 20-minute fire-rated doors.
R302.13 Fire protection of floors. Floor assemblies that are
not required elsewhere in this code to be fire-resistance rated, shall
be provided with one and one-half (1/2) inch (12.7 mm) gypsum wallboard
membrane, five-eights (5/8) inch (6 mm) wood structural panel membrane,
or equivalent on the underside of the floor framing member. Penetrations
or openings for ducts, vents, electrical outlets, lighting, devices,
luminaires, wires, speakers, drainage, piping and similar openings
or penetrations shall be permitted. It is not the intent of this Section
that a fire-rated assembly be created for this purpose.
Exceptions:
1. Floor assemblies located directly over a space protected
by an automatic sprinkler system in accordance with Section P2904,
NFPA 13D, or other approved equivalent sprinkler system.
2. Floor assemblies located directly over a crawl space not
intended for storage or fuel-fired appliances.
3. Portions of floor assemblies shall be permitted to be unprotected
where complying with the following:
3.1 The aggregate area of the unprotected floor assembly does
not exceed one hundred (100) square feet (9.3m2) per story.
3.2 Fireblocking in accordance with Section 302.11.1 is installed
along the perimeter of the unprotected portion to separate the unprotected
portion from the remainder of the floor assembly. Areas of the floor
assembly covered by HVAC metal plenum, trunk lines, and steel structural
beams shall be considered protected. Gypsum wallboard membrane shall
be within two (2) inches of all previously listed items.
4. Wood floor assemblies using dimension lumber or structural
composite lumber equal to or greater than 2-inch by 10-inch (50.8
mm by 254 mm) nominal dimension, or other approved floor assemblies
demonstrating equivalent fire performance.
R303.4 Mechanical ventilation. Where the air infiltration rate
of a dwelling unit is three (3) air changes per hour or less where
tested with a blower door at a pressure of two tenths (0.2) inch w.c.
(50 Pa) in accordance with Section N1102.4.1.2, the dwelling unit
shall be provided with whole-house mechanical ventilation in accordance
with Section M1507.3.
R303.8 Exterior stairway illumination. Exterior stairways shall
be provided with an artificial light source. Exterior stairways providing
access to a basement from the outdoor grade level shall be provided
with an artificial light source located at the bottom landing of the
stairway.
R309.5 Fire sprinklers. Private garages shall be protected by
fire sprinklers where the garage wall has been designed based on Table
302.1(2), Footnote a, and the homeowner has opted to purchase a fire
sprinkler system for their residence, as per Missouri Revised Statutes
67.281. Sprinklers in garages shall be connected to an automatic sprinkler
system that complies with Section P2904. Garage sprinklers shall be
residential sprinklers or quick-response sprinklers, designed to provide
a density of 0.05 gpm/ft2. Garage doors
shall not be considered obstructions with respect to sprinkler placement.
R311.3 Floors and landings at exterior doors. There shall be
a landing or floor on each side of exterior doors that lead to the
outdoors. The width of each landing shall not be less than the door
served. Every landing shall have a dimension of not less than thirty-six
(36) inches (914 mm) measured in the direction of travel. The slope
at exterior landings shall not to exceed one fourths (1/4) unit vertical
in twelve (12) units horizontal two percent (2%).
Exception: Exterior balconies less than sixty (60) square feet
(5.6 m2) and only accessible from a door
are permitted to have a landing less than thirty-six (36) inches (914
mm) measured in the direction of travel.
R311.3.2 Floor elevations for other exterior doors. Doors other
than the required egress door shall be provided with landings or floors
not more than seven and three-fourths (7 3/4) inches (196 mm)
below the top of the threshold.
Exception: A top landing is not required where a stairway of
four (4) or fewer risers is located on the exterior side of the door,
provided that door does not swing over the stairway.
R311.7.5 Stair treads and risers. Stair treads and risers shall
meet the requirements of this Section. For the purposes of this Section,
dimensions and dimensioned surfaces shall be exclusive of carpets,
rugs or runners.
Exception: For remodeling projects inside existing dwelling
units, stair tread and riser dimensions are permitted to match previous
or existing conditions.
R311.7.6 Landings for stairways. There shall be a floor or landing
at the top and bottom of each stairway. The width perpendicular to
the direction of travel shall be not less than the width of the flight
served. Landings of shapes other than square or rectangular shall
be permitted provided the depth at the walk line and the total area
is not less than that of a quarter circle with a radius equal to the
required landing width. Where the stairway has a straight run, the
depth in the direction of travel shall not be less than thirty-six
(36) inches (914 mm).
Exception: A floor or landing is not required at the top of
an interior or exterior flight of stairs, including stairs in an enclosed
garage, provided that a door does not swing over the stairs.
R313.1 Townhouse automatic fire sprinkler systems. An automatic
residential fire sprinkler system shall be installed in townhouses,
in accordance with Section 67.281 of the Missouri Revised Statutes.
Exception: An automatic residential fire sprinkler system shall
not be required where additions or alterations are made to existing
townhouses that do not have an automatic residential fire sprinkler
system installed.
R313.2 One- and two-family dwellings automatic fire systems.
A builder of a single-family dwelling or residence or multi-unit dwellings
of four (4) or fewer units shall offer to any purchaser on or before
the time of entering into the purchase contract the option, at the
purchaser's cost, to install or equip fire sprinklers in the
dwelling, residence, or unit. Notwithstanding any other provision
of law to the contrary, no purchaser of such a single-family dwelling,
residence, or multi-unit dwelling shall be denied the right to choose
or decline to install a fire sprinkler system in such dwelling or
residence being purchased by any code, ordinance, rule, regulation,
order, or resolution by any County or other political subdivision.
Any County or other political subdivision shall provide in any such
code, ordinance, rule, regulation, order, or resolution the mandatory
option for purchasers to have the right to choose and the requirement
that builders offer to purchasers the option to purchase fire sprinklers
in connection with the purchase of any single-family dwelling, residence,
or multi-unit dwelling of four (4) or fewer units.
Exception: An automatic residential fire sprinkler system shall
not be required for additions or alterations to existing buildings
that are not already provided with an automatic residential sprinkler
system.
R403.1.1 Minimum size. The minimum width, W, and thickness,
T, for concrete footings shall be in accordance with Tables R403.1(1)
through R403.1(4) and Figure R403.1(1) or R403.1.3, as applicable.
The footing width shall be based on the load-bearing value of the
soil in accordance with Table R401.4.1. Footing projections, P, shall
be not less than two (2) inches (51 mm) and shall not exceed the thickness
of the footing. Footing thickness and projection for fireplaces shall
be in accordance with Section R1001.2. The size of footings supporting
piers and columns shall be based on the tributary load and allowable
soil pressure in accordance with Table R401.4.1. Footings for wood
foundations shall be in accordance with the details set forth in Section
R403.2, and Figures R403.1(2) and R403.1(3).
Minimum Width of Concrete, Precast, or Masonry Footings (inches)
for Light-Frame Construction with Pre-Fabricated Roof Trussesa,b
| ||||
---|---|---|---|---|
Table R403.1(4)
| ||||
Load-Bearing Value of Soil (psf)
| ||||
1500
|
2000
|
3000
|
>4000
| |
Conventional light-frame construction with pre-fabricated trusses
| ||||
1 story
|
12
|
12
|
12
|
12
|
2 story
|
15
|
12
|
12
|
12
|
3 story
|
23
|
17
|
12
|
12
|
4-inch brick veneer over light frame or 8-inch hollow concrete
masonry
| ||||
1 story
|
12
|
12
|
12
|
12
|
2 story
|
21
|
16
|
12
|
12
|
3 story
|
32
|
24
|
16
|
12
|
8-inch solid or fully grouted masonry
| ||||
1 story
|
16
|
12
|
12
|
12
|
2 story
|
29
|
21
|
14
|
12
|
3 story
|
42
|
32
|
21
|
16
|
For SI: 1 inch = 25.4 mm, 1 pound per square foot = 0.0479 kPa
| |
a.
|
Where minimum footing width is twelve (12) inches, use of a
single wythe of solid or fully grouted 12-inch nominal concrete masonry
units is permitted.
|
b.
|
Snow Load or Roof Live Load shall not exceed twenty (20) psf.
If load exceeds twenty (20) psf, designs must be completed by a licensed
design professional.
|
R403.1.7 Footings on or adjacent to slopes. The placement of
buildings and structures on or adjacent to slopes steeper than one
(1) unit vertical in three (3) units horizontal (thirty-three and
three tenths percent (33.3%) slope) shall conform to Sections R403.1.7.1
through R403.1.7.4 or plans as signed and sealed by a structural engineer
licensed by the State of Missouri.
|
R404.1.3.2 Reinforcement for foundation walls. Concrete foundation
walls shall be laterally supported at the top and bottom. Horizontal
reinforcement shall be provided in accordance with Table R404.1.2(1).
Vertical reinforcement shall be provided in accordance with Table
R404.1.2(2), R404.1.2(3), R404.1.2(4), R404.1.2(5), 404.1.2(6), R404.1.2(7)
or R404.1.2(8). Vertical reinforcement for flat basement walls retaining
four (4) feet (1,219 mm) or more of unbalanced backfill is permitted
to be determined in accordance with Table R404.1.2(9). For basement
walls supporting above-grade concrete walls, vertical reinforcement
shall be the greater of that required by Tables R404.1.2(2) through
R404.1.2(8) or by Section R608.6 for the above-grade wall. In buildings
assigned to Seismic Design Category D0, D1 or D2, concrete foundation walls
shall also comply with Section R404.1.4.2.
|
Exception: Where a licensed Missouri engineer's geotechnical
report confirms that unstable soil or ground water conditions do not
exist on an individual home site, concrete foundation walls may be
constructed in accordance with Table R404.1.2(10).
|
Table R404.1.2(10) Concrete Foundation Walls
| ||
---|---|---|
Maximum Wall Height
|
Maximum Depth of Unbalanced Backfill
|
Minimum Nominal Wall Thickness
|
8'-0"
|
7'-6" or less
|
8" (Note a)
|
9'-0"
|
8'-6" or less
|
10" (Note b)
|
10'0"
|
9'-6" or less
|
12" (Note c)
|
Note a: Concrete foundation walls may be constructed a minimum
of nominal eight (8) inches thick where the wall height from the top
of the footing to the top of the wall does not exceed eight (8) feet.
A minimum of two (2) #4 reinforcing bars shall be placed horizontally
in the top and bottom of the foundation wall. A minimum of two (2)
#5 reinforcing bars shall be provided around all window and door openings
in concrete foundation and basement walls; bars shall extend a minimum
of twenty-four (24) inches beyond the corners of the openings.
|
Note b: Concrete foundation walls may be constructed a minimum
of nominal ten (10) inches thick. A minimum of two (2) #5 reinforcing
bars shall be placed horizontally in the top, middle, and bottom of
the foundation wall. A minimum of two (2) #5 reinforcing bars shall
be provided around all window and door openings in concrete foundation
and basement walls; bars shall extend a minimum of twenty-four (24)
inches beyond the corners of the openings.
|
Note c: Concrete foundation walls may be constructed a minimum
of nominal twelve (12) inches thick. A minimum of three (3) #5 reinforcing
bars shall be placed horizontally in the top, middle, and bottom of
the foundation wall. A minimum of two (2) #5 reinforcing bars shall
be provided around all window and door openings in concrete foundation
and basement walls; bars shall extend a minimum of twenty-four (24)
inches beyond the corners of the openings.
|
Note d: The concrete minimum wall thickness shall be eight (8)
inches for foundation walls in soil classes SC, MH, ML-CL and inorganic
CL when maximum wall height is eight (8) feet.
|
Note e: The concrete minimum wall thickness shall be ten (10)
inches for foundation walls in soil classes SC, MH, ML-CL and inorganic
CL when the maximum wall height is nine (9) feet.
|
Note f: The concrete minimum wall thickness shall be twelve
(12) inches for foundation walls in soil classes SC, MH, ML-CL and
inorganic CL when the maximum wall height is ten (10) feet.
|
405.1 Concrete or masonry foundations. Drains shall be provided
around concrete or masonry foundation that retain earth and enclose
habitable or usable spaces located below grade. Drainages tiles, gravel
or crushed stone drains, perforated pipe or other approved systems
or materials shall be installed at or below the area to be protected
and shall discharge by gravity or mechanical means into an approved
drainage system. Gravel or crushed stone drains shall extend not less
than one (1) foot (305 mm) beyond the outside edge of the footing
and six (6) inches (152 mm) above the top of the footing and be covered
with an approved filter membrane material. The top of open joints
of drain tiles shall be protected with strips of building paper. Except
where otherwise recommended by the drain manufacturer, perforated
drains shall be surrounded with an approved filter membrane or the
filter membrane shall cover the washed gravel or crushed rock covering
the drain. Drainage tiles or perforated pipe shall be placed on a
minimum of two (2) inches (51 mm) of washed gravel or crushed rock
not less than one (1) sieve size larger than the tile joint opening
or perforation and covered with not less than six (6) inches (152
mm) of the same material.
| |
Exceptions:
| |
1.
|
A drainage system is not required where the foundation is installed
on well-drained ground or sand-gravel mixture soils according to the
Unified Soil Classification System, Group I soils, as detailed in
Table R405.1.
|
2.
|
Drains provided as detailed in Section R405.1.2 are approved
as an alternative method to meet the requirements of this Section.
|
R405.1.2 Soil evaluations. An evaluation of the soil by a geotechnical
engineer for the presence or absence of groundwater is required. The
evaluation report shall be based on either a subsurface soil investigation
or satisfactory data from adjacent areas together with an inspection
of the excavation prior to pouring concrete.
|
R405.1.2.1 Groundwater present. Provide drain tile, perforated
pipe or other approved foundation drainage systems (such as water
channel system) around perimeter of the outside of the foundation
and inside the foundation. Drain discharge shall be by gravity to
daylight or be connected to a basement floor sump.
|
R405.1.2.2 No groundwater present. Provide drain tile, perforated
pipe or other approved foundation drainage systems (such as water
channel system) around perimeter of the outside of the foundation
or inside the foundation. Drain discharge shall be by gravity to daylight
or be connected to a basement floor sump.
|
R405.1.2.3 Filter membranes. An approved filter membrane shall
be placed over the top of the joints/pipe perforations. The tile/pipe
shall be placed on two (2) inches minimum of gravel or crushed stone
and have six (6) inches of minimum cover.
|
R405.1.2.4 Drainage system. A drainage system shall discharge
by gravity to daylight or be connected to an approved sump (eighteen
(18) inches in diameter x twenty-four (24) inches deep with fitted
cover). A sump pump shall be provided if the basement is finished
or partially finished with pump discharge by an approved method.
|
R602.7.5 Supports for headers. Headers shall be supported on
each end with one (1) or more jack studs or with approved framing
anchors in accordance with Table R602.7(1) or R602.7.(2). The full-height
stud adjacent to each end of the header shall be end nailed to each
end of the header with four-16d nails (three and five tenths (3.5)
inches x one hundred thirty-five thousandths (0.135) inches). The
minimum number of full-height studs at each end of a header shall
be in accordance with Table R602.7.5.
|
Table R602.7.5
| ||
---|---|---|
Minimum Number of Full Height Studs at Each End of Headers in
Exterior Wallsa
| ||
Maximum Header Span
(feet)
|
Ultimate Design Wind Speed and Exposure Category
| |
<140 mph, Exposure B or
<130 mph, Exposure C
|
<115mph, Exposure Bb
| |
4
|
1
|
1
|
6
|
2
|
1
|
8
|
2
|
1
|
10
|
3
|
2
|
12
|
3
|
2
|
14
|
3
|
2
|
16
|
4
|
2
|
18
|
4
|
2
|
a.
|
For header spans between those given above, use the minimum
number of full-height studs associated with the larger header span.
The tabulated minimum number of full-height studs is applicable where
jack studs are provided to support the header at each end in accordance
with Table R602.7.(1). Where a framing anchor is used to support the
header in lieu of a jack stud in accordance with footnote "d" of Table
R602.7.(1), the minimum number of full-height studs at each end of
a header shall be in accordance with requirements for wind speed <140mph,
Exposure B.
|
R905.2.8.2 Valleys. Valley linings shall be installed in accordance
with the manufacturer's instructions before applying shingles.
Valley linings of the following types shall be permitted:
| |
1.
|
For open valleys (valley lining exposed) lined with metal, the
valley lining shall be not less than twenty four (24) inches (610
mm) wide and of any of the corrosion-resistant metals in Table R905.2.8.2.
|
2.
|
For open valleys, valley lining of two (2) plies of mineral-surfaced
roll roofing, complying with ASTM D3909 or ASTM D6380 Class M, shall
be permitted. The bottom layer shall be eighteen (18) inches (457
mm) and the top layer not less than thirty-six (36) inches (914 mm)
wide.
|
3.
|
For closed valleys (valley covered with shingles), valley lining
of two (2) ply of No. 15 felt complying with ASTM D226 Type I, ASTM
D4869 Type I, or ASTM D6757 and not less than thirty six (36) inches
wide (914 mm) or valley lining as described in Item 1 and 2 shall
be permitted. Self-adhering polymer modified bitumen underlayment
complying with ASTM D1970 shall be permitted in lieu of the lining
material.
|
R905.2.8.5 Drip Edge. A drip edge, or equivalent approved by
the jurisdiction, shall be provided at eaves and rake edges of shingle
roofs. Adjacent segments of drip edge shall be overlapped not less
than two (2) inches (51 mm). Drip edges shall extend not less than
one fourths (1/4) inch (6.4 mm) below the roof sheathing and extend
up back onto the roof deck not less than two (2) inches (51 mm). Drip
edges shall be mechanically fastened to the roof deck at not more
than twelve (12) inches (305 mm) o.c. with fasteners as specified
in Section R905.2.5. Underlayment shall be installed over the drip
edge along eaves and under the underlayment along rake edges.
|
R1005.7 Factory-built chimney offsets. Where a factory-built
chimney assembly incorporates offsets, no part of the chimney shall
be at an angle of more than thirty degrees (30°) (0.52 rad) from
vertical at any point in the assembly and the chimney assembly shall
not include more than four (4) elbows.
|
Exception: Chimneys installed per manufacturer's installation
instructions
|
R1006.1.1 Factory-built fireplaces. Exterior combustion air
ducts for factory-built fireplaces shall be a listed component of
the fireplace, or equivalent approved by the jurisdiction, and shall
be installed according to the fireplace manufacturer's instructions.
|
N1101.4 (R102.1.1) Above code programs. The Building Official
or other authority having jurisdiction shall be permitted to deem
a national, State or local energy-efficiency program to exceed the
energy efficiency required by this code. Buildings approved in writing
by such an energy-efficiency program shall be considered in compliance
with this code. Applicant must provide adequate information to the
Lake Saint Louis Building Official to demonstrate that the above code
program satisfies all necessary code requirements.
|
N1101.6 (R202) Defined terms.
|
PROJECTION FACTOR. The ratio of the horizontal depth of an overhang,
eave, or permanently attached shading device, divided by the distance
measured vertically from the bottom of the fenestration glazing to
the underside of the overhang, eave, or permanently attached shading
device.
|
Table N1102.1.2 (R402.1.2)
| ||||||||||
---|---|---|---|---|---|---|---|---|---|---|
Insulation and Fenestration Requirements by Componenta
| ||||||||||
Climate Zone
|
Fenes- tration U-Factorb
|
Skylightb U-Factor
|
Glazed Fenes- tration SHGCb e
|
Ceiling R-Value
|
Wood Frame Wall R-Value
|
Mass Wall R-Valuei
|
Floor R-Value
|
Base- mentc Wall R-Value
|
Slabd R-Value & Depth
|
Crawl Spacec Wall R-Value
|
1
|
NR
|
0.75
|
0.25
|
30
|
13
|
3/4
|
13
|
0
|
0
|
0
|
2
|
0.40
|
0.65
|
0.25
|
38
|
13
|
4/6
|
13
|
0
|
0
|
0
|
3
|
0.35
|
0.55
|
0.25
|
38
|
20 or 13 + 5h
|
8/13
|
19
|
5/13f
|
0
|
5/13
|
4 except Marine
|
0.40
|
0.55
|
NR
|
38
|
5h 13
|
8/13
|
19
|
0i
|
10, 2 ft
|
10/13
|
5 and Marine 4
|
0.32
|
0.55
|
NR
|
49
|
20 or 13 + 5h
|
13/17
|
30g
|
15/19
|
10, 2 ft
|
15/19
|
6
|
0.32
|
0.55
|
NR
|
49
|
20 + 5 or 13 + 10h
|
15/20
|
30g
|
15/19
|
10, 4 ft
|
15/19
|
7 and 8
|
0.32
|
0.55
|
NR
|
49
|
20 + 5 or 13 + 10h
|
19/21
|
38g
|
15/19
|
10, 4 ft
|
15/19
|
F or SI: 1 foot = 304.8mm.
| |
a.
|
R-values are minimums. U-factors and SHGC are maximums. When
insulation is installed in a cavity which is less than the label or
design thickness of the insulation, the installed R-value of the insulation
shall not be less than the R-value specified in the table.
|
b.
|
The fenestration U-factor column excludes skylights. The SHGC
column applies to all glazed fenestration Exception: Skylights may
be excluded from glazed fenestration SHGC requirements in Climate
Zones 1 through 3 where the SHGC for such skylights does not exceed
0.30.
|
c.
|
"15/19" means R-15 continuous insulation on the interior or
exterior of the home or R-19 cavity insulation at the interior of
the basement wall. "15/19" shall be permitted to be met with R-13
cavity insulation on the interior of the basement wall plus R-5 continuous
insulation on the interior or exterior of the home. "10/13" means
R-10 continuous insulation on the interior or exterior of the home
or R-13 cavity insulation at the interior of the basement wall.
|
d.
|
R-5 shall be added to the required slab edge R-values for heated
slabs. Insulation depth shall be the depth of the footing or two (2)
feet, whichever is less in Zones 1 through 3 for heated slabs.
|
e.
|
There are no SHGC requirements in the Marine Zone.
|
f.
|
Basement wall insulation is not required in warm-humid locations
as defined by Figure N1101.10 or Table N1101.10.
|
g.
|
Or insulation sufficient to fill the framing cavity, R-19 minimum.
|
h.
|
The first value is cavity insulation, the second value is continuous
insulation, so "13+5" means R-13 cavity insulation plus R-5 continuous
insulation.
|
i.
|
The second R-value applies when more than half of the insulation
is on the interior of the mass wall.
|
j.
|
Exception: Unfinished basements may have up to a maximum of
twenty percent (20%) of the total basement wall area exposed above
the outside finished grade/ground level as uninsulated concrete foundation
walls. The foundation wall area above the outside grade/ground level
that may be uninsulated is determined by the formula [.20 times the
basement wall height of all walls (including insulated exterior frame
walls for walkout basements and walls common to both basement and
attached garages) times the perimeter of these basement walls]. In
unfinished areas, the basement foundation wall insulation shall extend
down to the basement floor slab or to a minimum of twenty-four (24)
inches below outside finished grade when the grade is above the floor
slab elevation.
|
N1102.1.3 (R402.1.3) R-value computation. Insulation material
used in layers, such as framing cavity insulation, or continuous insulation
shall be summed to compute the corresponding component R-value. The
manufacturer's settled R-value shall be used for blown insulation.
Computed R-values may include an R-value for other building materials
or air films. Where insulated siding is used for the purpose of complying
with the continuous insulation requirements of Table N1102.1.2, the
manufacturer's labeled R-Value for insulated siding shall be
reduced by R-0.6.
|
N1102.1.5 (R402.1.5) Total UA alternative. If the total building
envelope UA (sum of U-factor times assembly area) is less than or
equal to the total UA resulting from using the U-factors in Table
N1102.1.4 (multiplied by the same assembly area as in the proposed
building), the building shall be considered in compliance with Table
N1102.1.2. The UA calculation shall be done using a method consistent
with the ASHRAE Handbook of Fundamentals and shall include the thermal
bridging effects of framing materials. The SHGC requirements shall
be met in addition to UA compliance.
|
Exception: Glazed fenestration SHGC. In Climate Zone 4, permanently
shaded vertical fenestration shall be permitted to satisfy SHGC requirements.
Jurisdiction will require a separate sealed submission for each proposed
home to use shaded vertical fenestration. The projection factor of
an overhang, eave, or permanently attached shading device shall be
greater than or equal to the value listed in Table N1102.2.2.1 for
the appropriate orientation. The minimum projection shall extend beyond
each side of the glazing a minimum of twelve (12) inches. Each orientation
shall be rounded to the nearest cardinal orientation (+/- 45°
or 0.79 rad) for purposes of calculations and demonstrating compliance.
|
Table N1102.1.5
| |
---|---|
Minimum Projection Factor Required by Orientation for SHGC Exception
| |
Orientation
|
Projection Factor
|
North
|
>=0.40a
|
South
|
>=0.20
|
East
|
>=0.50
|
West
|
>=0.50
|
For the north orientation, a vertical projection located on
the west-edge of the fenestration with the equivalent of PF>=0.15
shall also satisfy the minimum projection factor requirement
|
N1102.2.4 (R402.2.4) Access hatches and doors. Access doors
from conditioned spaces to unconditioned spaces such as attics and
crawl spaces shall be insulated to a level equivalent to the insulation
on the surrounding surfaces. Access shall be provided to all equipment
that prevents damaging or compressing the insulation. A wood-framed
or equivalent baffle or retainer is required to be provided when loose-fill
insulation is installed, the purpose of which is to prevent the loose-fill
insulation from spilling into the living space when the attic access
is opened, and to provide the permanent means of maintaining the installed
R-value of the loose-fill insulation.
|
Exception: Vertical doors that provide access from the conditioned
to unconditioned spaces shall be permitted to meet the fenestration
requirements of Table R1102.1.2 based on the applicable climate zone
specified in Chapter 3.
|
N1102.4 (R402.4) Air leakage. The building thermal envelope
may be designed and constructed to limit air leakage in accordance
with the requirements of Sections R1102.4.1 through R1102.4.4.
|
N1102.4.1.2 (R402.4.1.2) Testing Option. If testing is elected,
the building or dwelling unit shall be tested and verified as having
an air leakage rate of not exceeding five (5) air changes per hour
in Climate Zone 4. Testing shall be conducted in accordance with ASTM
E779 or ASTM E1827 and reported at a pressure of two tenths (0.2)
inches w.g. (50 Pascals). Where required by the code official, testing
shall be conducted by an approved third party. A written report of
the results of the test shall be signed by the party conducting the
test and provided to the code official. Testing shall be performed
at any time after creation of all penetrations of the building thermal
envelope.
| |
During testing:
| |
1.
|
Exterior windows and doors, fireplace and stove doors shall
be closed, but not sealed, beyond the intended weatherstripping or
other infiltration control measures.
|
2.
|
Dampers including exhaust, intake, makeup air, backdraft and
flue dampers shall be closed, but not sealed beyond intended infiltration
control measures.
|
3.
|
Interior doors, if installed at the time of the test, shall
be open.
|
4.
|
Exterior doors for continuous ventilation systems and heat recovery
ventilators shall be closed and sealed.
|
5.
|
Heating and cooling systems, if installed at the time of the
test, shall be turned off.
|
6.
|
Supply and return registers, if installed at the time of the
test, shall be fully open.
|
Table N1102.4.1.1 (402.4.1.1)
| ||
---|---|---|
Air Barrier and Insulation Installation
| ||
Component
|
Air Barrier Criteria
|
Insulation Installation Criteria
|
General Requirements
|
A continuous air barrier shall be installed in the building
envelope.
The exterior thermal envelope contains a continuous air barrier.
Breaks or joints in the air barrier shall be sealed.
|
Air-permeable insulation shall not be used as a sealing material.
|
Ceiling/attic
|
The air barrier in any dropped ceiling/soffit shall be aligned
with the insulation and any gaps in the air barrier sealed.
Access openings, drop down stairs or knee wall doors to unconditioned
attic spaces shall be sealed.
|
The insulation in any dropped ceiling/soffit shall be aligned
with the air barrier.
|
Walls
|
The junction of the foundation and sill plate shall be sealed.
The junction of the top plate and the top of the exterior walls
shall be sealed.
Knee walls shall be sealed.
|
Cavities within corners and headers of frame walls shall be
insulated by completely filling the cavity with a material having
a thermal resistance of R-3 per inch minimum.
Exterior thermal envelope insulation for framed walls shall
be installed in substantial contact and continuous alignment with
the air barrier.
|
Windows, skylights and doors
|
The space between window/door jambs and framing, and skylights
and framing shall be sealed.
| |
Rim joists
|
Rim joists shall include the air barrier.
|
Rim joists shall be insulated.
|
Floors (including above garage and cantilevered floors)
|
The air barrier shall be installed at any exposed edge of insulation.
|
Floor framing cavity insulation shall be installed to maintain
permanent contact with the underside of subfloor decking, or floor
framing cavity insulation shall be permitted to be in contact with
the top side of sheathing, or continuous insulation installed on the
underside of floor framing; and extends from the bottom to the top
of all perimeter floor framing members.
|
Crawl space walls
|
Exposed earth in unvented crawl spaces shall be covered with
Class I vapor retarder with overlapping joists taped.
|
Where provided instead of floor insulation, insulation shall
be permanently attached to the crawl space walls.
|
Narrow cavities
|
Batts in narrow cavities shall be cut to fit, or narrow cavities
shall be filled by insulation that on installation readily conforms
to the available cavity space.
| |
Garage separation
|
Air sealing shall be provided between the garage and conditioned
spaces.
| |
Plumbing and wiring
|
Batt insulation shall be cut neatly to fit around wiring and
plumbing in exterior walls, or insulation that on installation readily
conforms to available space shall extend behind piping and wiring.
| |
Shower/tub on exterior wall
|
The air barrier installed at exterior walls adjacent to showers
and tubs shall separate them from showers and tubs.
|
Exterior walls adjacent to showers and tubs shall be insulated.
|
Electrical/phone box on exterior walls
|
The air barrier shall be installed behind electrical or communication
boxes or air-sealed boxes shall be installed.
| |
Concealed sprinklers
|
When required to be sealed, concealed fire sprinklers shall
only be sealed in a manner that is recommended by the manufacturer.
Caulking or other adhesive sealants shall not be used to fill voids
between fire sprinkler cover plates and walls or ceilings.
| |
a.
|
In addition, inspection of log walls shall be in accordance
with the provisions of ICC 400.
|
N1102.4.5 (R402.4.5) Recessed lighting. Recessed luminaires
installed in the building thermal envelope may be sealed to limit
air leakage between conditioned and unconditioned spaces. All recessed
luminaires may be IC-rated and labeled as having an air leakage rate
not more than 2.0 cfm (0.944 L/s) when tested in accordance with ASTM
E283 at a 1.57 psf (75 Pa) pressure differential. All recessed luminaires
may be sealed with a gasket or caulk between the housing and interior
wall or ceiling covering.
| |
N1103.3.2 (R403.3.2) Sealing. Ducts, air handlers and filter
boxes shall be sealed. Joints and seams shall comply with either the
International Mechanical Code or Section M1601.4.1 of this code, as
applicable.
| |
Exceptions:
| |
1.
|
Air-impermeable spray foam products shall be permitted to be
applied without additional joint seals.
|
2.
|
Continuously welded and locking-type longitudinal joints and
seams in ducts operating at static pressure less than two (2) inches
of water column (500 Pa) pressure classification shall not require
additional closure systems.
|
N1103.4.1 (R403.4.1) Protection of piping insulation. Piping
insulation exposed to weather shall be protected from damage, including
that caused by sunlight, moisture, equipment maintenance and wind,
and shall provide shielding from solar radiation that can cause degradation
of the material. Adhesive tape which otherwise meets the requirements
of this Section shall be permitted.
|
N1103.5.3 (R405.5.3) Hot water pipe insulation (Prescriptive).
Insulation for hot water pipe with a minimum thermal resistance (R-value)
of R-3 shall be applied to the following:
| |
1.
|
Metallic piping larger than or equal to three fourths (3/4)
inch (19 mm) in nominal diameter.
|
2.
|
Piping serving more than one (1) dwelling unit.
|
3.
|
Piping located outside the conditioned space.
|
4.
|
Piping from the water heater to a distribution manifold.
|
5.
|
Piping located under a floor slab.
|
6.
|
Buried in piping.
|
7.
|
Supply and return piping in recirculation systems other than
demand recirculation systems.
|
N1103.6 (R403.6) Mechanical ventilation. If, in accordance with
previous code sections or as part of an above code program, the resulting
air changes per hour (ACH) at 50 Pascals is three (3) air changes
or less, the building shall be provided with ventilation that meets
the requirements of Section M1507 of this code or the International
Mechanical Code, as applicable, or with other approved means of ventilation.
Outdoor air intakes and exhausts shall have automatic or gravity dampers
that close when the ventilation system is not operating.
|
N1103.7 (R403.7) Equipment sizing and efficiency rating (mandatory).
Heating and cooling equipment shall be sized in accordance with ACCA
Manual J or other approved heating and cooling calculation methodologies.
New or replacement heating and cooling equipment shall have an efficiency
rating equal to or greater than the minimum required by Federal law
for the geographic location where the equipment is installed.
|
Table N1105.5.2(1) [R405.5.2(1)]
| |||
---|---|---|---|
Specifications for the Standard Reference and Proposed Designs
| |||
Building Component
|
Standard Reference Design
|
Proposed Design
| |
Above-grade walls
|
Type: mass wall if proposed wall is mass; otherwise wood frame
|
As proposed
| |
Gross area: same as proposed
|
As proposed
| ||
U-factor: as specified in Table N1102.1.4
|
As proposed
| ||
Solar absorptance = 0.75
|
As proposed
| ||
Remittance = 0.90
|
As proposed
| ||
Basement and crawl space walls
|
Type: same as proposed
|
As proposed
| |
Gross area: same as proposed
|
As proposed
| ||
U-factor: from Table N1102.1.4, with insulation layer on interior
side of walls
|
As proposed
| ||
Above-grade floors
|
Type: wood frame
|
As proposed
| |
Gross area: same as proposed
|
As proposed
| ||
U-factor: as specified in Table N1102.1.4
|
As proposed
| ||
Ceilings
|
Type: wood frame
|
As proposed
| |
Gross area: same as proposed
|
As proposed
| ||
U-factor: as specified in Table N1102.1.4
|
As proposed
| ||
Roofs
|
Type: composition shingle on wood sheathing
|
As proposed
| |
Gross area: same as proposed
|
As proposed
| ||
Solar absorptance = 0.75
|
As proposed
| ||
Emittance = 0.90
|
As proposed
| ||
Attics
|
Type: vented with aperture = 1 ft2 per 300 ft2 ceiling area
|
As proposed
| |
Foundations
|
Type: same as proposed
|
As proposed
| |
Foundation wall area above and below grade and soil characteristics:
same as proposed
|
As proposed
| ||
Opaque doors
|
Area: 40 ft2
|
As proposed
| |
Orientation: North
|
As proposed
| ||
U-factor: same as fenestration from Table N1102.1.4
|
As proposed
| ||
Vertical fenestration other than opaque doors
|
Total areab =
| ||
a)
|
15% of the conditioned floor area.
|
As proposed
| |
Orientation: equally distributed to four cardinal compass orientations
(N, E, S & W)
|
As proposed
| ||
U-factor: as specified in Table N1102.1.4
|
As proposed
| ||
SHGC: as specified in Table N1102.1.2 except that for climates
with no requirement (NR) SHGC = 0.40 shall be used
|
As proposed
| ||
Interior shade fraction: 0.92 - (0.21 x SHGC for the standard
reference design)
|
0.92 - (0.21 x SHGC as proposed)
| ||
External shading: none
|
As proposed
| ||
Skylights
|
None
|
As proposed
| |
Thermally isolated sunrooms
|
None
|
As proposed
| |
Air exchange rate
|
Air leakage rate of 5 air changes per hour in Climate Zones
4. The mechanical ventilation rate shall be in addition to the air
leakage rate and the same as in the proposed design, but no greater
than 0.01 x CFA + 7.5 x (Nbr + 1)
where:
CFA = conditioned floor area
Nbr = number of bedrooms
Energy recovery shall not be assumed for mechanical ventilation
Air leakage rate of 5 air changes per hour in at a pressure
of 0.2
where:
co ventilation
|
For residences that are not tested, the same air leakage rate
as the standard reference design.
For tested residences, the measured air exchange ratea.
The mechanical ventilation rateb shall
be in addition to the air leakage rate and shall be proposed.
| |
Mechanical ventilation
|
None, except where mechanical ventilation is specified by the
proposed design, in which case:
Annual vent fan energy use:
kWh/yr = 0.03942 x CFA + 29.565 x (Nbr + 1)
where:
CFA = conditioned floor area
Nbr = number of bedrooms
|
As proposed
| |
Internal gains
|
IGain = 17,900 + 23.8 x CFA + 4104 x Nbr (Btu/day per dwelling unit)
|
Same as standard reference design.
| |
Internal mass
|
An internal mass for furniture and contents of 8 pounds per
square foot of floor area
|
Same as standard reference design, plus any additional mass
specifically designed as a thermal storage elementc but not integral to the building envelope or structure.
| |
Structural mass
|
For masonry floor slabs, 80% of floor area covered by R-2 carpet
and pad, and 20% of floor directly exposed to room air
|
As proposed
| |
For masonry basement walls, as proposed, but with insulation
required by Table R402.1.4 located on the interior side of the walls
|
As proposed
| ||
For other walls, for ceilings, floors, and interior walls, wood
frame construction
|
As proposed
| ||
Heating systemsd, e
|
Fuel type: same as the proposed design
|
As proposed
| |
Efficiencies:
| |||
Electric: air-source heat pump with prevailing Federal minimum
standards
| |||
Non-electric furnaces: natural gas furnace with prevailing Federal
minimum standards
| |||
Non-electric boilers: natural gas boiler with prevailing Federal
minimum standards
| |||
Capacity: sized in accordance with Section N1103.7
| |||
Cooling systemsd, f
|
Fuel type: electric
|
As proposed
| |
Efficiency: in accordance with prevailing Federal minimum standards
| |||
Capacity: sized in accordance with Section N1103.7
| |||
Service water heatingd, e, f
|
Fuel type: same as proposed design
Efficiency: in accordance with prevailing Federal minimum standards
Use: gal/day = 30 + 10 x Nbr
Tank temperature: 120° F.
|
As proposed
Same as standard reference
| |
Thermal distribution systems
|
Duct insulation: from Section N1103.2.1
A thermal distribution system efficiency (DSE) of 0.88 shall
be applied to both the heating and cooling system efficiencies for
all systems other than tested duct systems. For tested duct systems,
the leakage rate shall be 4 cfm (113.3 L/min) per 100 ft2 (9.29 m2) of conditioned
floor area at a pressure of differential of one tenths (0.1) inches
w.g. (25 Pa)
|
As tested or specified in Table R405.5.2(2) if not tested. Duct
insulation shall be as proposed.
| |
Thermostat
|
Type: Manual, cooling temperature setpoint = 75° F.;
Heating temperature setpoint = 72° F.
|
Same as standard reference
|
For SI: 1 square foot = 0.93 m2,
1 British thermal unit = 1055 J, 1 pound per square foot = 4.88 kg/m2, 1 gallon (US) = 3.785 L, ° C. = (° F.-32)/1.8,
1° = 0.79 rad
| |
a.
|
Where required by the code official, testing shall be conducted
by an approved party. Hourly calculations as specified in the ASHRAE
Handbook of Fundamentals, or the equivalent shall be used to determine
the energy loads resulting from infiltration.
|
b.
|
The combined air exchange rate for infiltration and mechanical
ventilation shall be determined in accordance with Equation 43 of
2001 ASHRAE Handbook of Fundamentals, page 26.24 and the "Whole-house
Ventilation" provisions of 2001 ASHRAE Handbook of Fundamentals, page
26.19 for intermittent mechanical ventilation.
|
c.
|
Thermal storage element shall mean a component not part of the
floors, walls or ceilings that is part of a passive solar system,
and that provides thermal storage such as enclosed water columns,
rock beds, or phase-change containers. A thermal storage element must
be in the same room as fenestration that faces within fifteen degrees
(15°) (twenty-six hundredths (0.26) rad) of true south, or must
be connected to such a room with pipes or ducts that allow the element
to be actively charged.
|
d.
|
For a proposed design with multiple heating, cooling or water
heating systems using different fuel types, the applicable standard
reference design system capacities and fuel types shall be weighted
in accordance with their respective loads as calculated by accepted
engineering practice for each equipment and fuel type present.
|
e.
|
For a proposed design without a proposed heating system, a heating
system with the prevailing Federal minimum efficiency shall be assumed
for both the standard reference design and proposed design.
|
f.
|
For a proposed design home without a proposed cooling system,
an electric air conditioner with the prevailing Federal minimum efficiency
shall be assumed for both the standard reference design and the proposed
design.
|
g.
|
For a proposed design with a non-storage-type water heater,
a 40-gallon storage-type water heater with the prevailing Federal
minimum energy factor for the same fuel as the predominant heating
fuel type shall be assumed. For the case of a proposed design without
a proposed water heater, a 40-gallon storage-type water heater with
the prevailing Federal minimum efficiency for the same fuel as the
predominant heating fuel type shall be assumed for both the proposed
design and standard reference design.
|
M1301.2 Identification. Each length of pipe and tubing and each
pipe fitting utilized in a mechanical system shall bear the identification
of the manufacturer.
|
Exception: Line sets and similar materials provided the installer
can provide documentation related to the material used such as, but
not limited to, a receipt, invoice, or container.
|
M1305.1.4.1 Ground clearance. Equipment and appliances supported
from the ground shall be level and firmly supported on a concrete
slab or other approved material extending not less than two (2) inches
(50.8 mm) above the adjoining ground. Such support shall be in accordance
with the manufacturer's installation instructions. Appliances
suspended from the floor shall have a clearance of not less than six
(6) inches (152 mm) from the ground.
|
M1305.1.4.3 Electrical requirements. A luminaire controlled
by a switch located at the required passageway opening and a receptacle
outlet shall be installed at or near the appliance location in accordance
with Chapter 39. Exposed lamps shall be protected from damage by location
or lamp guards.
|
Exception: Basements
|
M1401.3 Equipment and appliance sizing. Heating and cooling
equipment and appliances shall be sized in accordance with ACCA Manual
J or other approved heating and cooling calculation methodologies.
| |
Exception: Heating and cooling equipment and appliance sizing
shall not be limited to the capacities determined in accordance with
Manual S where either of the following conditions applies:
| |
1.
|
The specified equipment or appliance utilizes multistage technology
or variable refrigerant flow technology and the loads calculated in
accordance with the approved heating and cooling calculation methodology
are within the range of the manufacturer's published capacities
for that equipment or appliance.
|
2.
|
The specified equipment or appliance manufacturer's published
capacities cannot satisfy both the total and sensible heat gains calculated
in accordance with the approved heating and cooling calculation methodology
and the next larger standard size unit is specified.
|
M1411.3.1 Auxiliary and secondary drain systems. In addition
to the requirements of Section M1411.3, a secondary drain or auxiliary
drain pan shall be required for each cooling or evaporator coil where
damage to any building components will occur as a result of overflow
from the equipment drain pan or stoppage in the condensate drain piping.
Such piping shall maintain a minimum horizontal slope in the direction
of discharge or not less than one-eighth (1/8) unit vertical in twelve
(12) units horizontal (one percent (1%) slope). Drain piping shall
be not less than three fourths (3/4) inch (19 mm) nominal pipe size.
One (1) of the following methods shall be used:
| |
1.
|
An auxiliary drain pan with a separate drain shall be installed
under the coils on which condensation will occur. The auxiliary pan
drain shall discharge to a conspicuous point of disposal to alert
occupants in the event of a stoppage of the primary drain. The pan
shall have a minimum depth of one and five tenths (1.5) inches (38
mm), shall be not less than three (3) inches (76 mm) larger than the
unit or the coil dimensions in width and length and shall be constructed
of corrosion-resistant material. Galvanized sheet steel pans shall
have a minimum thickness of not less than (No. 26 Gage). Non-metallic
pans shall have a minimum thickness of not less than 0.0625 inch (1.6
mm).
|
M1502.4.1 Material and size. Exhaust ducts shall have a smooth
interior finish and be constructed of metal having a minimum thickness
of 0.0157 inch (0.3950 mm) (No. 30 gage). The duct shall be four (4)
inches (102 mm) nominal in diameter.
|
M1502.4.2 Duct installation. Exhaust ducts shall be supported
at intervals not to exceed twelve (12) feet (3,658 mm) and shall be
secured in place. The insert end of the duct shall extend into the
adjoining duct or fitting in the direction of airflow. Exhaust duct
joints shall be sealed in accordance with Section M1601.4.1 and shall
be mechanically fastened or fastened by other methods as approved
by the authority having jurisdiction. Ducts shall not be joined with
screws or similar fasteners that protrude more than one-eighth (1/8)
inch (3.2 mm) into the inside of the duct.
|
M1503.4 Makeup air required. Exhaust hood systems capable of
exhausting in excess of four hundred (400) cubic feet per minute (0.19
m3/s) shall be mechanically or naturally
provided with makeup air at a rate approximately equal to the exhaust
air rate. Such makeup air systems shall be equipped with not less
than one (1) damper. Each damper shall be a gravity damper or an electrically
operated damper that automatically opens when the exhaust system operates.
Dampers shall be accessible for inspection, service, repair and replacement
without removing permanent construction or any other ducts not connected
to the damper being inspected, serviced, repaired or replaced. Such
makeup air systems shall be equipped with a means of closure and shall
be automatically controlled to start and operate simultaneously with
the exhaust system.
|
M1601.1.1 Above-ground duct systems. Above-ground duct systems
shall conform to the following:
| ||
1.
|
Equipment connected to duct systems shall be designed to limit
discharge air temperature to not greater than 250° F. (121°
C.).
| |
2.
|
Factory-made ducts shall be listed and labeled in accordance
with UL 181 and installed in accordance with the manufacturer's
instructions.
| |
3.
|
Fibrous glass duct construction shall conform to the SMACNA
Fibrous Glass Duct Construction Standards or NAIMA Fibrous Glass Duct
Construction Standards.
| |
4.
|
Field-fabricated and shop-fabricated metal and flexible duct
constructions shall conform to the SMACNA HVAC Duct Construction Standards
— Metal and Flexible except as allowed by Table M1601.1.1. Galvanized
steel shall conform to ASTM A653.
| |
5.
|
The use of gypsum products to construct return air ducts or
plenums is permitted, provided that the air temperature does not exceed
125° F. (52° C.) and exposed surfaces are not subject to condensation.
| |
6.
|
Duct systems shall be constructed of materials having a flame
spread index of not greater than two hundred (200).
| |
7.
|
Stud wall cavities and the spaces between solid floor joists
to be used as non-ducted air plenums shall comply with the following
conditions:
| |
7.1.
|
These cavities or spaces shall not be used as a plenum for air
supply.
| |
7.2.
|
These cavities or spaces shall not be a part of required fire-resistance-rated
assembly.
| |
7.3.
|
Stud wall cavities shall not convey air from more than one (1)
floor level.
| |
7.4.
|
Stud wall cavities and joist-space plenums shall be isolated
from adjacent concealed spaces by tight-fitting fireblocking in accordance
with Section R602.8.
| |
7.5.
|
Stud wall cavities in the outside walls of building envelope
assemblies shall not be utilized as air plenums.
|
Table M1601.1.1
| ||||||
---|---|---|---|---|---|---|
Duct Construction Minimum Sheet Metal Thickness for Single Dwelling
Unitsa
| ||||||
Static Pressure
| ||||||
Round Duct Diameter
(inches)
|
1/2 inch water gage
|
1 inch water gage
| ||||
Thickness (inches)
|
Thickness (inches)
| |||||
Galvanized
|
Aluminum
|
Galvanized
|
Aluminum
| |||
< 12
|
0.013
|
0.018
|
0.013
|
0.018
| ||
12 to 14
|
0.013
|
0.018
|
0.016
|
0.023
| ||
15 to 17
|
0.016
|
0.023
|
0.019
|
0.027
| ||
18
|
0.016
|
0.023
|
0.024
|
0.034
| ||
19 to 20
|
0.019
|
0.027
|
0.024
|
0.034
| ||
Rectangular Duct Dimension
(largest dimension)
|
Static Pressure
| |||||
1/2 inch water gage
|
1 inch water gage
| |||||
Thickness
(inches)
|
Thickness
(inches)
| |||||
Galvanized
|
Aluminum
|
Galvanized
|
Aluminum
| |||
< 8
|
0.013
|
0.018
|
0.013
|
0.018
| ||
9 to 10
|
0.013
|
0.018
|
0.016
|
0.023
| ||
11 to 12
|
0.016
|
0.023
|
0.019
|
0.027
| ||
13 to 16
|
0.016
|
0.027
|
0.019
|
0.027
| ||
17 to 18
|
0.019
|
0.027
|
0.024
|
0.034
| ||
19 to 20
|
0.019
|
0.034
|
0.024
|
0.034
| ||
For SI: 1 inch = 25.4 mm, 1 inch water gage = 249 Pa.
| ||||||
a.
|
Ductwork that exceeds twenty (20) inches by dimension or exceeds
a pressure of one (1) inch water gage (250 Pa) shall be constructed
in accordance with SMACNA HVAC Duct Construction Standards Metal and
Flexible.
|
M1601.4.1 Joints, seams and connections.
| |
Joints of duct systems shall be made substantially airtight
in an unconditioned area by means of tapes, mastics, liquid sealants,
gasketing or other approved closure systems. Closure systems used
with rigid fibrous glass ducts shall comply with UL 181A and shall
be marked 181A-P for pressure-sensitive tape, 181A-M for mastic or
181A-H for heat-sensitive tape. Closure systems used with flexible
air ducts and flexible air connectors shall comply with UL 181B and
shall be marked 181B-FX for pressure-sensitive tape or 181B-M for
mastic. Duct connections to flanges of air distribution system equipment
or sheet metal fittings shall be mechanically fastened. Mechanical
fasteners for use with flexible non-metallic air ducts shall comply
with UL 181B and shall be marked 181B-C. Crimp joints for round metal
ducts shall have a contact lap of at least one (1) inch and shall
be mechanically fastened with at least three (3) sheet metal screws
or rivets equally spaced around the joint. Closure systems used to
seal metal ductwork shall be installed in accordance with the manufacturer's
installation instructions.
| |
Exceptions:
| |
1.
|
Spray polyurethane foam shall be permitted to be applied without
additional joint seals.
|
2.
|
Where a duct connection is made that is partially inaccessible,
three (3) screws or rivets shall be equally spaced on the exposed
portion of the joint so as to prevent a hinge effect.
|
3.
|
Continuously welded and locking-type longitudinal joints and
seams in ducts operating at static pressure less than two (2) inches
of water column (500 Pa) pressure classification shall not require
additional closure systems.
|
M1602.2 Return air openings. Return air openings for heating,
ventilation and air conditioning systems shall comply with all of
the following:
| ||
1.
|
Openings shall not be located less than ten (10) feet (3,048
mm) measured in any direction from an open combustion chamber or draft
hood of another appliance located in the same room or space.
| |
2.
|
Return and transfer openings shall be sized in accordance with
the appliance or equipment manufacturers' installation instructions,
Manual D or the design of the registered design professional.
| |
3.
|
Return air shall not be taken from a closet space smaller than
sixty-four (64) square feet, bathroom, toilet room, kitchen, garage,
mechanical room, boiler room, furnace room or unconditioned attic.
| |
Exceptions:
| ||
1.
|
Taking return air from a kitchen is not prohibited where such
return air openings serve the kitchen only, and are located not less
than ten (10) feet (3,048 mm) from the cooking appliances.
| |
2.
|
Dedicated forced-air systems serving only the garage shall not
be prohibited from obtaining return air from the garage.
| |
4.
|
Taking return air from an unconditioned crawl space shall not
be accomplished through a direct connection to the return side of
a forced-air furnace. Transfer openings in the crawl space enclosure
shall not be prohibited.
| |
5.
|
Return air from one (1) dwelling unit shall not be discharged
into another dwelling unit.
|
M2105.4 Piping and tubing materials standards. Ground-source
heat-pump ground-loop pipe and tubing shall conform to the standards
listed in Table M2105.4. However, polyvinyl chloride (PVC) and chlorinated
polyvinyl chloride (CPVC) shall not be used for any geothermal application.
|
M2105.19 Pipe penetrations. Openings for pipe penetrations in
walls, floors and ceilings shall be larger than the penetrating pipe.
Openings in the foundation wall underground shall be sealed to not
allow groundwater into a building.
|
G2408.4 (305.7) Clearances from grade. Equipment and appliances
installed at grade level shall be supported on a level concrete slab
or other approved material extending not less than two (2) inches
(50.8 mm) above adjoining grade or shall be suspended not less than
six (6) inches (152 mm) above adjoining grade. Such supports shall
be installed in accordance with the manufacturer's installation
instructions.
|
G2409.1 (308.1) Scope. This Section shall govern the reduction
in required clearances to combustible materials, and combustible assemblies
for chimneys, vents, appliances, devices and equipment. Clearance
requirements for air-conditioning equipment and central heating boilers
and furnaces shall comply with Sections G2409.3 and G2409.4 and shall
follow the manufacturer's installation instructions.
|
G2412.9 (401.9) Identification. Each length of pipe and tubing
and each pipe fitting, utilized in a fuel gas system, shall bear the
identification of the manufacturer.
|
Exception: Line sets and similar materials provided the installer
can provide documentation related to the material used such as, but
not limited to, a receipt, invoice, or container.
|
G2442.4 (618.4) Prohibited sources. Outdoor or return air for
forced-air heating and cooling systems shall not be taken from the
following locations:
| |||
1.
|
Closer than ten (10) feet (3,048 mm) from an appliance vent
outlet, a vent opening from a plumbing drainage system or the discharge
outlet of an exhaust fan, unless the outlet is three (3) feet (914
mm) above the outside air inlet.
| ||
2.
|
Where there is the presence of objectionable odors, fumes or
flammable vapors; or where located less than ten (10) feet (3,048
mm) above the surface of any abutting public way or driveway; or where
located at grade level by a sidewalk, street, alley or driveway.
| ||
3.
|
A hazardous or insanitary location or a refrigeration machinery
room as identified in the International Mechanical Code.
| ||
4.
|
A room or space, the volume of which is less than twenty-five
percent (25%) of the entire volume served by such system. Where connected
by a permanent opening having an area sized in accordance with Section
G2442.2, adjoining rooms or spaces shall be considered as a single
room or space for the purpose of determining the volume of such rooms
or spaces.
| ||
Exception: The minimum volume requirement shall not apply where
the amount of return air taken from a room or space is less than or
equal to the amount of supply air delivered to such room or space.
| |||
5.
|
A room or space containing an appliance where such a room or
space serves as the sole source of return air.
| ||
Exception: This shall not apply where:
| |||
1.
|
The appliance is a direct-vent appliance or an appliance not
requiring a vent in accordance with Section G2425.8.
| ||
2.
|
The room or space complies with the following requirements:
| ||
2.1.
|
The return air shall be taken from a room or space having a
volume exceeding one (1) cubic foot for each ten (10) Btu/h (9.6L/W)
of combined input rating of all fuel-burning appliances therein.
| ||
2.2.
|
The volume of supply air discharged back into the same space
shall be approximately equal to the volume of return air taken from
the space.
| ||
2.3.
|
Return-air inlets shall not be located within ten (10) feet
(3,048 mm) of a draft hood in the same room or space or the combustion
chamber of any atmospheric burner appliance in the same room or space.
| ||
3.
|
Rooms or spaces containing solid fuel-burning appliances, provided
that return-air inlets are located not less than ten (10) feet (3,048
mm) from the firebox of such appliances.
| ||
6.
|
A closet, bathroom, toilet room, kitchen, garage, boiler room,
furnace room or unconditioned attic.
| ||
Exceptions:
| |||
1.
|
Where return air intakes are located not less than ten (10)
feet (3,048 mm) from cooking appliances and serve only the kitchen
area, taking return air from a kitchen area shall not be prohibited.
| ||
2.
|
Dedicated forced air systems serving only a garage shall not
be prohibited from obtaining return air from the garage
| ||
3.
|
Where an enclosed space other than a bathroom, toilet room,
kitchen, garage, furnace room or unconditioned attic is provided with
a supply register, taking return air from that space shall not be
prohibited.
| ||
7.
|
A crawl space by means of direct connection to the return side
of a forced-air system. Transfer openings in the crawl space enclosure
shall not be prohibited.
|
P2903.5 Water hammer. The flow velocity of the water distribution
system shall be controlled to reduce the possibility of water hammer.
A water-hammer arrestor shall be installed where quick-closing valves
are used. Water-hammer arrestors shall be installed in accordance
with the manufacturer's installation instructions. Water-hammer
arrestors shall conform to ASSE 1010.
|
P2904.1 General. When installed, the design and installation
of residential fire sprinkler systems shall be in accordance with
NFPA 13D or Section 2904, which shall be considered equivalent to
NFPA 13D. Partial residential sprinkler systems shall be permitted
to be installed only in buildings not required to be equipped with
a residential sprinkler system. Section P2904 shall apply to stand-alone
and multipurpose wet-pipe sprinkler systems that do not include the
use of antifreeze. A multipurpose fire sprinkler system shall provide
domestic water to both fire sprinklers and plumbing fixtures. A stand-alone
sprinkler system shall be separate and independent from the water
distribution system. A backflow preventer shall not be required to
separate a stand-alone system from the water distribution system.
|
E3902.2 Garage and accessory building receptacles. 125-volt,
single-phase, 15- or 20-ampere receptacles installed in garage and
grade-level portions of unfinished accessory buildings used for storage
or work areas shall have ground-fault circuit-interrupter protection
for personnel. [210.8(A)(2)]
|
Exception: Fastened in place appliances or outlets designated
for refrigerators or freezers on a dedicated circuit.
|
E3902.5 Unfinished basement receptacles. 125-volt, single-phase,
15- and 20-ampere receptacles installed in unfinished basements shall
have ground-fault circuit-interrupter protection for personnel. For
purposes of this Section, unfinished basements are defined as portions
or areas of the basement not intended as habitable rooms and limited
to storage areas, work areas, and similar areas. [210.8(A)(5)]
| |
Exceptions:
| |
1.
|
A receptacle supplying only a permanently installed fire alarm
or burglar alarm system. Receptacles installed in accordance with
this exception shall not be considered as meeting the requirements
of Section E3901.9.
|
2.
|
Fastened in place appliances or outlets designated for refrigerators
or freezers on a dedicated circuit.
|
E3902.6 Kitchen receptacles. 125-volt, single-phase, 15- and
20-ampere receptacles that serve countertop surfaces shall have ground-fault
circuit-interrupter protection for personnel. [210.8(A)(6)]
|
Exception: Simplex receptacles on dedicated circuits serving
fastened in place appliances or refrigerators/freezers.
|
E3902.9 Laundry areas. 125-volt, single-phase, 15- and 20-ampere
receptacles, other than simplex receptacles on dedicated circuits
serving clothes washing machines installed in laundry areas shall
have ground-fault circuit-interrupter protection for personnel. [210.8(A)(9)]
|
E3902.14 Location of ground-fault circuit interrupters. Ground-fault
circuit interrupters shall be installed only in a readily accessible
location. [210.8(A)]
|
c.
The following Sections of the 2015 International Fire Code,
as published by the International Code Council, are hereby revised
as follows:
[A] 101.1 Title. These regulations shall be known as the Fire
Code of the City of Lake Saint Louis, Missouri, hereinafter referred
to as "this code."
[A] 108.1 Appeals. The Lake Saint Louis Building Appeals Board
shall hear and decide appeals of orders, decisions or determinations
made by the fire code official relative to the application and interpretation
of this code. All rules and requirements associated with such an appeal,
as specified in the Lake Saint Louis Municipal Code, shall apply.
Application to appeal any order, decision or determination made by
the fire code official shall be filed with the fire code official
within twenty (20) days after the order, decision or determination
was served, on a form obtained from the code official.
[A] 109.3 Violation penalties. Persons who shall violate a provision
of this code or shall fail to comply with any of the requirements
thereof or who shall erect, install, alter, repair or do work in violation
of the approved construction documents or directive of the fire code
official, or of a permit or certificate used under provisions of this
code, shall be subject to penalties as prescribed by law. Each day
that a violation continues after due notice has been served shall
be deemed a separate offense.
[A] 111.4 Failure to comply. Any person who shall continue any
work after having been served with a stop work order, except such
work as that person is directed to perform to remove a violation or
unsafe condition, shall be subject to penalties as prescribed by law.
[A] 113.3 Work commencing before permit issuance. A person who
commences any work, activity or operation regulated by this code before
obtaining the necessary permits shall be subject to penalties as prescribed
by law. Each day that a violation continues after due notice has been
served shall be deemed a separate offense.
d.
The following Sections of the 2015 International Plumbing Code,
as published by the International Code Council, are hereby revised
as follows:
[A] 101.1 Title. These regulations shall be known as the International
Plumbing Code of the City of Lake Saint Louis, Missouri, herein after
referred to as "this code."
[A] 106.6.1 Work commencing before permit issuance. Any person
who commences any work before obtaining the necessary permits shall
be subject to penalties as prescribed by law. Each day that a violation
continues after due notice has been served shall be deemed a separate
offense.
[A] 106.6.2 Fees schedule. The fees for all plumbing permits
shall be as indicated in the Lake Saint Louis Municipal Code.
[A] 106.6.3 Fee refunds. The code official may approve the refunding
of permit and/or inspection fees only as permitted by the Lake Saint
Louis Municipal Code and City policy.
[A] 108.4 Violation penalties. Any person who shall violate
a provision of this code or shall fail to comply with any of the requirements
thereof or who shall erect, construct, alter or repair plumbing work
in violation of the approved construction documents or directive of
the Building Official, or of a permit or certificate issued under
the provisions of this code, shall be subject to penalties as prescribed
by law. Each day that a violation continues after due notice has been
served shall be deemed a separate offense.
[A] 108.5 Stop work orders. Upon notice from the code official,
work on any plumbing system that is being performed contrary to the
provisions of this code or in a dangerous or unsafe manner shall immediately
cease. Such notice shall be in writing and shall be given to the owner
of the property, or to the owner's authorized agent, or to the
person performing the work. The notice shall state the conditions
under which work is authorized to resume. Where an emergency exists,
the code official shall not be required to give a written notice prior
to stopping the work. Any person who shall continue any work in or
about the structure after having been served with a stop work order,
except such work as that person is directed to perform to remove a
violation or unsafe condition, shall be subject to penalties as prescribed
by law.
[A] 109.1 Application for appeal. Any aggrieved person with
a material interest in the decision of the code official shall have
the right to appeal such a decision to the Lake Saint Louis Building
Appeals Board. All rules and requirements associated with such an
appeal, as specified in the Lake Saint Louis Municipal Code, shall
apply. An application for appeal shall be based on a claim that the
true intent of this code or the rules legally adopted thereunder have
been incorrectly interpreted, the provisions of this code do not fully
apply, or an equally good or better form of construction is proposed.
The application for appeal shall be filed with the code official within
twenty (20) days after the decision of the code official was given
on a form obtained from the code official.
[A] 109.1.1 Limitation of authority. The Lake Saint Louis Building
Appeals Board shall not have authority relative to interpretation
of the administration of this code nor shall such board be empowered
to waive requirements of this code.
305.4.1 Sewer depth. Building sewers that connect to private
sewage disposal systems shall be installed not less than thirty (30)
inches (762 mm) below finished grade at the point of septic tank connection.
Building sewers shall be installed not less than thirty (30) inches
(762 mm) below grade.
903.1 Roof extension. Open vent pipes that extend through a
roof shall be terminated not less than fourteen (14) inches (356 mm)
above the roof. Where a roof is to be used for assembly or as a promenade,
observation deck, sunbathing deck or similar purposes, open vent pipes
shall terminate not less than seven (7) feet (2,134 mm) above the
roof.
e.
The following Sections of the 2015 International Mechanical
Code, as published by the International Code Council, are hereby revised
as follows:
[A] 101.1 Title. These regulations shall be known as the Mechanical
Code of the City of Lake Saint Louis, Missouri, hereinafter referred
to as "this code."
[A] 106.5.1 Work commencing before permit issuance.
Any person who commences work on a mechanical system before
obtaining the necessary permits shall be subject to penalties as prescribed
by law. Each day that a violation continues after due notice has been
served shall be deemed a separate offense.
[A] 106.5.2 Fees schedule. The fees for all mechanical permits
shall be as indicated in the Lake Saint Louis Municipal Code.
[A] 106.5.3 Fee refunds. The code official may approve the refunding
of permit and/or inspection fees only as permitted by the Lake Saint
Louis Municipal Code and City policy.
[A] 108.4 Violation penalties. Persons who shall violate a provision
of this code or shall fail to comply with any of the requirements
thereof or who shall erect, construct, alter or repair mechanical
work in violation of the approved construction documents or directive
of the code official, or of a permit or certificate issued under the
provisions of this code, shall be subject to penalties as prescribed
by law. Each day that a violation continues after due notice has been
served shall be deemed a separate offense.
[A] 108.5 Stop work orders. Upon notice from the code official
that mechanical work is being performed contrary to the provisions
of this code or in a dangerous or unsafe manner, such work shall immediately
cease. Such notice shall be in writing and shall be given to the owner
of the property, or to the owner's authorized agent, or to the
person doing the work. The notice shall state the conditions under
which work is authorized to resume. Where an emergency exists, the
code official shall not be required to give a written notice prior
to stopping the work. Any person who shall continue any work on the
system after having been served with a stop work order, except such
work as that person is directed to perform to remove a violation or
unsafe condition, shall be subject to penalties as prescribed by law.
[A] 109.1 Application for appeal. Any aggrieved person with
a material interest in the decision of the code official shall have
the right to appeal such a decision to the Lake Saint Louis Building
Appeals Board. An application for appeal shall be based on a claim
that the true intent of this code or the rules legally adopted thereunder
have been incorrectly interpreted, the provisions of this code do
not fully apply, or an equally good or better form of construction
is proposed. All rules and requirements associated with such an appeal,
as specified in the Lake Saint Louis Municipal Code, shall apply.
The application for appeal shall be filed with the code official within
twenty (20) days after the decision of the code official was given
on a form obtained from the code official.
[A] 109.1.1 Limitation of authority. The Lake Saint Louis Building
Appeals Board shall not have authority relative to interpretation
of the administration of this code nor shall such board be empowered
to waive requirements of this code.
f.
The following Sections of the 2015 International Fuel Gas Code,
as published by the International Code Council, are hereby revised
as follows:
[A] 101.1 Title. These regulations shall be known as the Fuel
Gas Code of the City of Lake Saint Louis, Missouri, hereinafter referred
to as "this code."
[A] 106.5.1 Work commencing before permit issuance.
Any person who commences work on a fuel gas system before obtaining
the necessary permits shall be subject to penalties as prescribed
by law. Each day that a violation continues after due notice has been
served shall be deemed a separate offense.
[A] 106.5.2 Fees schedule. The fees for all mechanical permits
shall be as indicated in the Lake Saint Louis Municipal Code.
[A] 106.5.3 Fee refunds. The code official may approve the refunding
of permit and/or inspection fees only as permitted by the Lake Saint
Louis Municipal Code and City policy.
[A] 108.4 Violation penalties. Persons who shall violate a provision
of this code or shall fail to comply with any of the requirements
thereof or who shall erect, construct, alter or repair fuel gas system
work in violation of the approved construction documents or directive
of the code official, or of a permit or certificate issued under the
provisions of this code, shall be subject to penalties as prescribed
by law. Each day that a violation continues after due notice has been
served shall be deemed a separate offense.
[A] 108.5 Stop work orders. Upon notice from the code official
that fuel gas system work is being performed contrary to the provisions
of this code or in a dangerous or unsafe manner, such work shall immediately
cease. Such notice shall be in writing and shall be given to the owner
of the property, or to the owner's authorized agent, or to the
person doing the work. The notice shall state the conditions under
which work is authorized to resume. Where an emergency exists, the
code official shall not be required to give a written notice prior
to stopping the work. Any person who shall continue any work on the
system after having been served with a stop work order, except such
work as that person is directed to perform to remove a violation or
unsafe condition, shall be subject to penalties as prescribed by law.
[A] 109.1 Application for appeal. Any aggrieved person with
a material interest in the decision of the code official shall have
the right to appeal such a decision to the Lake Saint Louis Building
Appeals Board. An application for appeal shall be based on a claim
that the true intent of this code or the rules legally adopted thereunder
have been incorrectly interpreted, the provisions of this code do
not fully apply, or an equally good or better form of construction
is proposed. All rules and requirements associated with such an appeal,
as specified in the Lake Saint Louis Municipal Code, shall apply.
The application for appeal shall be filed with the code official within
twenty (20) days after the decision of the code official was given
on a form obtained from the code official.
[A] 109.1.1 Limitation of authority. The Lake Saint Louis Building
Appeals Board shall not have authority relative to interpretation
of the administration of this code nor shall such board be empowered
to waive requirements of this code.
g.
The following Sections of the 2015 International Property Maintenance
Code, as published by the International Code Council, are hereby revised
as follows:
[A] 101.1 Title. These regulations shall be known as the Property
Maintenance Code of the City of Lake Saint Louis, Missouri, hereinafter
referred to as "this code."
Section 103.5 Fees. The fees for activities and services performed
by the department in carrying out its responsibilities under this
code shall be as indicated in the Lake Saint Louis Municipal Code.
[A] 111.1 Application for appeal. Any person directly affected
by a decision of the code official or a notice or order issued under
this code shall have the right to appeal to the Lake Saint Louis Building
Appeals Board, provided that a written application for appeal is filed
within twenty (20) days after the day the decision, notice or order
was served. All rules and requirements associated with such an appeal,
as specified in the Lake Saint Louis Municipal Code, shall apply.
An application for appeal shall be based on a claim that the true
intent of this code or the rules legally adopted thereunder have been
incorrectly interpreted, the provisions of this code do not fully
apply, or the requirements of this code are adequately satisfied by
other means.
[A] 112.4 Failure to comply. Any person who shall continue any
work after having been served with a stop work order, except such
work as that person is directed to perform to remove a violation or
unsafe condition, shall be subject to penalties as prescribed by law.
302.4 Weeds. Premises and exterior property shall be maintained
free from weeds or plant growth in excess of seven (7) inches in height.
Noxious weeds shall be prohibited. Weeds shall be defined as all grasses,
annual plants and vegetation, other than trees or shrubs, provided;
however, this term shall not include cultivated flowers and gardens.
Upon failure of the owner or agent having charge of a property
to cut and destroy weeds after service of a notice of violation, they
shall be subject to prosecution as prescribed by the authority having
jurisdiction. Upon failure to comply with the notice of violation,
any duly authorized employee of the jurisdiction or contractor hired
by the jurisdiction shall be authorized to enter upon the property
in violation and cut and destroy the weeds growing thereon, and the
costs of such removal shall be paid by the owner or agent responsible
for the property.
304.14 Insect screens. Every door, window and other outside
opening required for ventilation of habitable rooms, food preparation
areas, food service areas or any areas where products to be included
or utilized in food for human consumption are processed, manufactured,
packaged or stored shall be supplied with approved tightly fitting
screens of minimum sixteen (16) mesh per inch (16 mesh per 25 mm),
and every screen door used for insect control shall have a self-closing
device in good working condition.
Exception: Screens shall not be required where other approved
means, such as air curtains or insect repellent fans, are employed.
602.3 Heat supply. Every owner and operator of any building
who rents, leases or lets one (1) or more dwelling units or sleeping
units on terms, either expressed or implied, to furnish heat to the
occupants thereof shall supply heat to maintain a minimum temperature
of 68° F. (20° C.) in all habitable rooms, bathrooms and toilet
rooms.
Exceptions:
1. When the outdoor temperature is below the winter outdoor
design temperature for the locality, maintenance of the minimum room
temperature shall not be required provided that the heating system
is operating at its full design capacity. The winter outdoor design
temperature for the locality shall be as indicated in Appendix D of
the International Plumbing Code.
2. In areas where the average monthly temperature is above 30°
F. (-1° C.), a minimum temperature of 65° F. (18° C.)
shall be maintained.
602.4 Occupiable work spaces. Indoor occupiable work spaces
shall be supplied with heat to maintain a minimum temperature of 65°
F. (18° C.) during the period the spaces are occupied.
Exceptions:
1. Processing, storage and operation areas that require cooling
or special temperature conditions.
2. Areas in which persons are primarily engaged in vigorous
physical activities.
h.
The following Sections of the 2015 International Energy Conservation
Code, as published by the International Code Council, are hereby revised
as follows:
C101.1 Title. This code shall be known as the International
Energy Conservation Code of the City of Lake Saint Louis, Missouri,
and shall be cited as such. It is referred to herein as "this code."
C107.3 Work commencing before permit issuance. Any person who
commences any work before obtaining the necessary permits shall be
subject to penalties as prescribed by law. Each day that a violation
continues after due notice has been served shall be deemed a separate
offense.
C108.4 Failure to comply. Any person who shall continue any
work after having been served with a stop work order, except such
work as that person is directed to perform to remove a violation or
unsafe condition, shall be penalties as prescribed by law.
SECTION C109
APPEALS
C109.1 General. Any aggrieved person with a material interest
in the decision of the code official shall have the right to appeal
such a decision to the Lake Saint Louis Building Appeals Board. All
rules and requirements associated with such an appeal, as specified
in the Lake Saint Louis Municipal Code, shall apply. The application
for appeal shall be filed with the code official within twenty (20)
days after the decision of the code official was given on a form obtained
from the code official.
R101.1 Title. This code shall be known as the International
Energy Conservation Code of the City of Lake Saint Louis, Missouri,
and shall be cited as such. It is referred to herein as "this code."
R107.3 Work commencing before permit issuance. Any person who
commences any work before obtaining the necessary permits shall be
subject to penalties as prescribed by law. Each day that a violation
continues after due notice has been served shall be deemed a separate
offense.
R108.4 Failure to comply. Any person who shall continue any
work after having been served with a stop work order, except such
work as that person is directed to perform to remove a violation or
unsafe condition, shall be penalties as prescribed by law.
SECTION C109
APPEALS
R109.1 General. Any aggrieved person with a material interest
in the decision of the code official shall have the right to appeal
such a decision to the Lake Saint Louis Building Appeals Board. An
application for appeal shall be based on a claim that the true intent
of this code or the rules legally adopted thereunder have been incorrectly
interpreted, the provisions of this code do not fully apply, or an
equally good or better form of construction is proposed. All rules
and requirements associated with such an appeal, as specified in the
Lake Saint Louis Municipal Code, shall apply. The application for
appeal shall be filed with the code official within twenty (20) days
after the decision of the code official was given on a form obtained
from the code official.
i.
The following Sections of the 2015 International Existing Building
Code, as published by the International Code Council, are hereby revised
as follows:
[A] 101.1 Title. These regulations shall be known as the Existing
Building Code of the City of Lake Saint Louis, hereinafter referred
to as "this code."
[A] 105.2 Work exempt from permit. Exemptions from permit requirements
of this code shall not be deemed to grant authorization for any work
to be done in any manner in violation of the provisions of this code
or any other laws or ordinances of this jurisdiction. Permits shall
not be required for the following:
Building:
1. Sidewalks and driveways.
2. Painting, papering, tiling, carpeting, cabinets, counter
tops, and similar finish work.
3. Retaining walls that are not over four (4) feet (1,219 mm)
in height measured from the bottom of the footing to the top of the
wall, unless supporting a surcharge.
Electrical:
1. Listed cord-and-plug connected temporary decorative lighting.
2. Reinstallation of attachment plug receptacles but not the
outlets therefor.
3. Replacement of branch circuit overcurrent devices of the
required capacity in the same location.
4. Electrical wiring, devices, appliances, apparatus or equipment
operating at less than twenty-five (25) volts and not capable of supplying
more than fifty (50) watts of energy.
5. Minor repair work, including the replacement of lamps or
the connection of approved portable electrical equipment to approved
permanently installed receptacles.
Gas:
1. Portable heating, cooking or clothes drying appliances.
2. Replacement of any minor part that does not alter approval
of equipment or make such equipment unsafe.
3. Portable-fuel-cell appliances that are not connected to a
fixed piping system and are not interconnected to a power grid.
Mechanical:
1. Portable heating appliance.
2. Portable ventilation equipment.
3. Portable cooling unit.
4. Steam, hot, or chilled water piping within any heating or
cooling equipment regulated by this code.
5. Replacement of any part that does not alter its approval
or make it unsafe.
6. Portable evaporative cooler.
7. Self-contained refrigeration system containing ten (10) pounds
(4.54 kg) or less of refrigerant and actuated by motors of one (1)
horsepower (746 W) or less.
8. Portable-fuel-cell appliances that are not connected to a
fixed piping system and are not interconnected to a power grid.
Plumbing:
1. The stopping of leaks in drains, water, soil, waste, or vent
pipe; provided, however, that if any concealed trap, drainpipe, water,
soil, waste, or vent pipe becomes defective and it becomes necessary
to remove and replace the same with new material, such work shall
be considered as new work, and a permit shall be obtained and inspection
made as provided in this code.
2. The clearing of stoppages or the repairing of leaks in pipes,
valves, or fixtures, and the removal and reinstallation of water closets,
provided such repairs do not involve or require the replacement or
rearrangement of valves, pipes, or fixtures.
[A] 108.4 Work commencing before permit issuance.
Any person who commences any work before obtaining the necessary
permits shall be subject to penalties as prescribed by law. Each day
that a violation continues after due notice has been served shall
be deemed a separate offense.
SECTION 112
APPEALS
[A] 112.1 General. Any aggrieved person with a material interest
in the decision of the code official shall have the right to appeal
such a decision to the Lake Saint Louis Building Appeals Board. All
rules and requirements associated with such an appeal, as specified
in the Lake Saint Louis Municipal Code, shall apply. The application
for appeal shall be filed with the code official within twenty (20)
days after the decision of the code official was given, on a form
obtained from the code official.
j.
The following Sections of the 2015 International Swimming Pool and
Spa Code, as published by the International Code Council, are hereby
revised as follows:
[A] 101.1 Title. These regulations shall be known as the Swimming
Pool and Spa Code of the City of Lake Saint Louis, Missouri, hereinafter
referred to as "this code."
[A] 105.6.2 Fee schedule. The fees for permits shall be as indicated
in the Lake Saint Louis Municipal Code.
[A] 105.6.3 Fee refunds. The code official may approve the refunding
of permit and/or inspection fees only as permitted by the Lake Saint
Louis Municipal Code and City policy.
[A] 107.4 Violation penalties. Any person who shall violate
a provision of this code or shall fail to comply with any of the requirements
thereof or who shall erect, install, alter or repair a pool or spa
in violation of the approved construction documents or directive of
the code official, or of a permit or certificate issued under the
provisions of this code, shall be subject to penalties as prescribed
by law. Each day that a violation continues after due notice has been
served shall be deemed a separate offense.
[A] 107.5 Stop work orders. Upon notice from the code official,
work on any system that is being performed contrary to the provisions
of this code or in a dangerous or unsafe manner shall immediately
cease. Such notice shall be in writing and shall be given to the owner
of the property, or to the owner's authorized agent, or to the
person performing the work. The notice shall state the conditions
under which work is authorized to resume. Where an emergency exists,
the code official shall not be required to give a written notice prior
to stopping the work. Any person who shall continue any work in or
about the structure after having been served with a stop work order,
except such work as that person is directed to perform to remove a
violation or unsafe condition, shall be subject to penalties as prescribed
by law.
SECTION 108
APPEALS
[A] 108.1 Application for appeal. Any aggrieved person with
a material interest in the decision of the code official shall have
the right to appeal such a decision to the Lake Saint Louis Building
Appeals Board. All rules and requirements associated with such an
appeal, as specified in the Lake Saint Louis Municipal Code, shall
apply. An application for appeal shall be based on a claim that the
true intent of this code or the rules legally adopted thereunder have
been incorrectly interpreted, the provisions of this code do not fully
apply, or an equally good or better form of construction is proposed.
The application for appeal shall be filed with the code official within
twenty (20) days after the decision of the code official was given,
on a form obtained from the code official.
k.
The following Sections of the National Electrical Code, 2014
Edition, as published by the National Fire Protection Association,
are hereby revised as follows:
80.1 Scope. These regulations shall be known as the Electrical
Code of the City of Lake Saint Louis, Missouri, hereinafter referred
to as "this code." The following functions are covered by this code:
(1) The inspection of electrical installations as covered by
90.2.
(2) The investigation of fires caused by electrical installations.
(3) The review of construction plans, drawings, and specifications
for electrical systems.
(4) The design, alteration, modification, construction, maintenance,
and testing of electrical systems and equipment.
(5) The regulation and control of electrical installations at
special events including but not limited to exhibits, trade shows,
amusement parks, and other similar special occupancies.
80.13 Authority Where used in this Article, the term authority
having jurisdiction shall include the chief electrical inspector or
other individuals designated by the governing body. This code shall
be administered and enforced by the authority having jurisdiction
designated by the governing authority as follows.
(13) Whenever any installation subject to inspection prior to
use is covered or concealed without having first been inspected, the
authority having jurisdiction shall be permitted to require that such
work be exposed for inspection. The authority having jurisdiction
shall be notified when the installation is ready for inspection and
shall conduct the inspection within five (5) business days of such
notification.
80.15 Appeals
The Lake Saint Louis Building Appeals Board shall hear and decide
appeals of orders, decisions or determinations made by the authority
having jurisdiction relative to the application and interpretation
of this code. Appeals shall be based only upon an assertion that the
true intent of the codes or ordinances described in this code has
been incorrectly interpreted, or that the provisions of the codes
or ordinances do not fully apply, or that a decision made by the authority
having jurisdiction is unreasonable or arbitrary as it applies to
alternatives or new materials. All rules and requirements associated
with appeals, as specified in the Lake Saint Louis Municipal Code,
shall apply. Application to appeal any order, decision or determination
made by the authority having jurisdiction shall be filed with the
authority having jurisdiction within twenty (20) days after the order,
decision or determination was served, on a form obtained from the
authority having jurisdiction. The Lake Saint Louis Building Appeals
Board shall not have authority relative to interpretation of the administration
of this code nor shall such board be empowered to waive requirements
of this code.
80.19 Permits and Approvals. Permits and approvals shall conform
to (A) through (H).
The fees for all electrical permits shall be as indicated in
the Lake Saint Louis Municipal Code.
(F) Inspection and Approvals.
(3) When any portion of the electrical installation within the
jurisdiction of an Electrical Inspector is to be hidden from view
by the permanent placement of parts of the building, the person, firm
or corporation installing the equipment shall notify the Electrical
Inspector, and such equipment shall not be concealed until it has
been approved by the Electrical Inspector.
(G) Revocation of Permits. Revocation of permits shall conform
to the following:
(1) The authority having jurisdiction shall be permitted to
revoke a permit or approval issued if any violation of this code is
found upon inspection or in case there have been any false statements
or misrepresentations submitted in the application or plans on which
the permit or approval was based.
(2) Any attempt to defraud or otherwise deliberately or knowingly
design, install, service, maintain, operate, sell, represent for sale,
falsify records, reports, or applications, or other related activity
in violation of the requirements prescribed by this code shall be
a violation of this code. Such violations shall be cause for immediate
suspension or revocation of any related licenses, certificates, or
permits issued by this jurisdiction. In addition, any such violation
shall be subject to any other criminal or civil penalties as available
by the laws of this jurisdiction.
(3) Revocation shall be constituted when the permittee is duly
notified by the authority having jurisdiction.
(4) Any person who engages in any business, operation, or occupation,
or uses any premises, after the permit issued therefor has been suspended
or revoked pursuant to the provisions of this code, and before such
suspended permit has been reinstated or a new permit issued, shall
be in violation of this code.
(5) A permit shall be predicated upon compliance with the requirements
of this code and shall constitute written authority issued by the
authority having jurisdiction to install electrical equipment. Any
permit issued under this code shall not take the place of any other
license or permit required by other regulations or laws of this jurisdiction.
(6) The authority having jurisdiction shall be permitted to
require an inspection prior to the issuance of a permit.
(7) A permit issued under this code shall continue until revoked
or for the period of time designated on the permit. The permit shall
be issued to one (1) person or business only and for the location
or purpose described in the permit. Any change that affects any of
the conditions of the permit shall require a new or amended permit.
(H) Applications and Extensions. Applications and extensions
of permits shall conform to the following:
(1) The authority having jurisdiction shall be permitted to
grant an extension of the permit time period upon presentation by
the permittee of a satisfactory reason for failure to start or complete
the work or activity authorized by the permit.
(2) Applications for permits shall be made to the authority
having jurisdiction on forms provided by the jurisdiction and shall
include the applicant's answers in full to inquiries set forth
on such forms. Applications for permits shall be accompanied by such
data as required by the authority having jurisdiction, such as plans
and specifications, location, and so forth. Fees shall be determined
as required by local laws.
(3) The authority having jurisdiction shall review all applications
submitted and issue permits as required. If an application for a permit
is rejected by the authority having jurisdiction, the applicant shall
be advised of the reasons for such rejection. Permits for activities
requiring evidence of financial responsibility by the jurisdiction
shall not be issued unless proof of required financial responsibility
is furnished.
80.23 Notice of Violations, Penalties. Notice of violations
and penalties shall conform to (A) and (B).
(A) Violations.
(1) Whenever the authority having jurisdiction determines that
there are violations of this Code, a written notice shall be issued
to confirm such findings.
(2) Any order or notice issued pursuant to this Code shall be
served upon the owner, operator, occupant, or other person responsible
for the condition or violation, either by personal service or mail
or by delivering the same to, and leaving it with, some person of
responsibility upon the premises. For unattended or abandoned locations,
a copy of such order or notice shall be posted on the premises in
a conspicuous place at or near the entrance to such premises and the
order or notice shall be mailed by registered or certified mail, with
return receipt requested, to the last known address of the owner,
occupant, or both.
(B) Penalties.
(1) Any person who fails to comply with the provisions of this
Code or who fails to carry out an order made pursuant to this Code
or violates any condition attached to a permit, approval, or certificate
shall be subject to the penalties established by this jurisdiction.
(2) Failure to comply with the time limits of an abatement notice
or other corrective notice issued by the authority having jurisdiction
shall result in each day that such violation continues being regarded
as a new and separate offense.
80.25 Connection to Electricity Supply. Connections to the electric
supply shall conform to (A) through (C).
(A) Authorization. Except where work is done under an annual
permit and except as otherwise provided in 80.25, it shall be unlawful
for any person, firm, or corporation to make connection to a supply
of electricity or to supply electricity to any electrical equipment
installation for which a permit is required or that has been disconnected
or ordered to be disconnected.
(B) Special Consideration. By special permission of the authority
having jurisdiction, temporary power shall be permitted to be supplied
to the premises for specific needs of the construction project.
(C) Disconnection. Where a connection is made to an installation
that has not been inspected, as outlined in the preceding paragraphs
of this Section, the supplier of electricity shall immediately report
such connection to the Chief Electrical Inspector. If, upon subsequent
inspection, it is found that the installation is not in conformity
with the provisions of Article 80, the authority having jurisdiction
shall notify the person, firm, or corporation making the installation
to rectify the defects and, if such work is not completed within a
time specified by the authority having jurisdiction, the AHJ shall
have the authority to cause the disconnection of that installation.
80.29 Liability for Damages. Article 80 shall not be construed
to affect the responsibility or liability of any party owning, designing,
operating, controlling, or installing any electrical equipment for
damages to persons or property caused by a defect therein, nor shall
the City of Lake Saint Louis, Missouri, or any of its employees be
held as assuming any such liability by reason of the inspection, reinspection,
or other examination authorized.
4.
Plant Oil And Fat Extraction And Processing Facilities.
[Ord. No. 3984, 5-20-2019]
a.
Intent. The following requirements are intended to help ensure
the extraction and processing of oils and fats from various plants
are conducted in a reasonably safe manner. Extraction by use of a
solvent, desolventizing the raw material, production of a mixture,
in any proportion, of the extracted oil or fat and the extracting
solvent, distillation of the solvent from the miscella and solvent
recovery shall be governed by these requirements. Included within
these requirements are provisions for a technical report prepared
by a registered design professional and site inspections to ensure
equipment and systems are installed as designed and approved.
b.
DESOLVENTIZING
MISCELLA
Definitions. For the purposes of this Section, the following
terms shall have the meanings indicated:
The act of removing a solvent from material.
A mixture, in any proportion, of an extracted oil or fat
and an extracting solvent.
c.
Scope. Plant processing or extraction facilities shall comply
with this Section, and with the City's most recently adopted
Comprehensive Building Code. Extraction processes include the act
of extraction of the oils and fats by use of a solvent, desolventizing
of the raw material, production of the miscella, distillation of the
solvent from the miscella and solvent recovery. The use, storage,
transfilling and handling of hazardous materials in these facilities
shall comply with all other applicable provisions of the City's
most recently adopted Comprehensive Building Code.
d.
Existing Buildings Or Facilities. Existing buildings or facilities
used for the processing of plants or where the medium of extraction
or solvent is changed shall comply with the requirements of this Section.
e.
Permits. Permits shall be required as set forth in the City's
most recently adopted Comprehensive Building Code.
f.
Construction. Processing shall be located in a building complying
with the City's most recently adopted Comprehensive Building
Code.
g.
Prohibited Occupancies. Extraction processes utilizing flammable
gases or flammable cryogenic fluids shall not be located in any building
containing a Group A, E, I or R occupancy as defined by the City's
most recently adopted edition of the International Building Code.
h.
Location. The extraction equipment and extraction processes
utilizing hydrocarbon solvents shall be located in a room or area
dedicated to extraction.
i.
Post-Process Purification And Winterization. Post-processing
and winterization involving the heating or pressurizing of the miscella
to other than normal pressure or temperature shall be approved and
performed in an appliance listed for such use. Domestic or commercial
cooking appliances shall not be used.
j.
Industrial Ovens. The use of industrial ovens shall comply with
the relevant requirements of the City's most recently adopted
edition of the International Fire Code.
k.
Use Of Flammable And Combustible Liquids. The use of flammable
and combustible liquids for liquid extraction processes where the
liquid is boiled, distilled or evaporated shall be located within
a hazardous exhaust fume hood, rated for exhausting flammable vapors.
Electrical equipment used within the hazardous exhaust fume hood shall
be rated for use in flammable atmospheres. Heating of flammable or
combustible liquids over an open flame is prohibited. Exception: The
use of a heating element not rated for flammable atmospheres, where
documentation from the manufacturer or approved testing laboratory
indicates the element is rated for heating of flammable liquids.
l.
Liquefied Petroleum Gas. Liquefied petroleum gases shall not
be released to the atmosphere except where released in accordance
with Section 7.3 of NFPA 58.
m.
General Requirements. Systems and equipment used with the processing
and extraction of oils and products from plants shall comply with
this and all other relevant portions of the City's most recently
adopted Comprehensive Building Code and the City's Code of Ordinances.
n.
Systems And Equipment. Systems or equipment used for the extraction
of oils from plant material shall be listed or approved for the specific
use. If the system used for extraction of oils and products from plant
material is not listed, the system shall be reviewed by a registered
design professional. The registered design professional shall review
and consider any information provided by the system's designer
or manufacturer. For systems and equipment not listed for the specific
use, a technical report shall be prepared and submitted to the Chief
Building Official for review and approval. The firm or individual
preparing the technical report shall be approved by the Chief Building
Official prior to performing the analysis.
o.
Technical Report. A technical report, reviewed and approved
by the Chief Building Official, is required prior to the equipment
being located or installed at the facility. The technical report shall
contain all of the following:
(1)
Manufacturer information.
(2)
Preparer of record of the technical report.
(3)
Date of review and report revision history.
(4)
Signature page, including author of the report,
date of report, and date and signature of registered design professional
of record performing the design or peer review.
(5)
Model number of the item evaluated. If the equipment
is provided with a serial number, the serial number shall be included
for verification at the time of site inspection.
(6)
Methodology of the design or peer review process
used to determine minimum safety requirements. Methodology shall consider
the basis of design, and shall include a code analysis and code path
to demonstrate whether specific codes or standards are applicable.
(7)
Equipment description. A list of every component
and subassembly, such as fittings, hoses, quick disconnects, gauges,
site glass, gaskets, valves, pumps, vessels, containers and switches,
of the system or equipment, indicating the manufacturer, model number,
material and solvent compatibility. Manufacturer's data sheets
shall be provided.
(8)
A general flow schematic or general process flow diagram of the process. Post-processing or winterization shall be included in this diagram. Primary components of the process equipment shall be identified and match the equipment list required in Subsection (A)(4)(o)(7), above. Operating temperatures, pressures and solvent state of matter shall be identified in each primary step or component. A piping and instrumentation diagram (PID or P&ID) shall be provided.
(9)
Analysis of the vessel(s) if pressurized beyond
standard atmospheric pressure. Analysis shall include purchased and
fabricated components.
(10)
Structural analysis for the frame system supporting
the equipment.
(11)
Process safety analysis of the extraction system,
from the introduction of raw product to the end of the extraction
process.
(12)
Comprehensive process hazard analysis considering
failure modes and points of failure throughout the process. The process
hazard analysis shall include a review of emergency procedure information
provided by the manufacturer of the equipment or process and not that
of the facility, building or room.
(13)
Review of the assembly instructions, operational
and maintenance manuals provided by the manufacturer.
(14)
List of references used in the analysis.
p.
Site Inspection. Prior to operation of the extraction equipment,
where required by the Chief Building Official, the engineer of record
or approved professional shall inspect the site of the extraction
process once equipment has been installed for compliance with the
technical report and the building analysis. The engineer of record
or approved professional shall provide a report of findings and observations
of the site inspection to the Chief Building Official prior to the
approval of the extraction process. The field inspection report authored
by the engineer of record or approved professional shall include the
serial number of the equipment used in the process and shall confirm
that the equipment installed is the same model and type of equipment
identified in the technical report.
q.
Gas Detection. For extraction processes utilizing flammable
gases as solvents, a continuous gas detection system shall be provided.
The gas detection threshold shall be not greater than twenty-five
percent (25%) of the lower explosive limit/lower flammability limit
(LEL/LFL) of the materials.
r.
System Design. The flammable gas detection system shall be listed
or approved and shall be calibrated to the types of fuels or gases
used for the extraction process. The gas detection system shall be
designed to activate when the level of flammable gas exceeds twenty-five
percent (25%) of the LFL.
s.
Gas Detection System Components. Gas detection system control
units shall be listed and labeled in accordance with UL 864 or UL
2017. Gas detectors shall be listed and labeled in accordance with
UL 2075 for use with the gases and vapors being detected.
t.
Operation. Activation of the gas detection system shall result
in all the following:
u.
Failure Of The Gas Detection System. Failure of the gas detection
system shall result in the deactivation of the heating system; activation
of the mechanical ventilation system where the system is interlocked
with the gas detection system; and initiation of a trouble signal
to sound in an approved location.
v.
Interlocks. Electrical components within the extraction room
shall be interlocked with the gas detection system. Activation of
the gas detection system shall disable all light switches and electrical
outlets.
w.
Emergency Shutoff. Extraction processes utilizing gaseous hydrocarbon-based
solvents shall be provided with emergency shutoff systems in accordance
with the relevant requirements of the City's most recently adopted
edition of the International Fire Code.
B.
It
shall be unlawful to construct, enlarge, alter or repair any project,
building or structure without first obtaining a building permit as
required by the Lake Saint Louis Comprehensive Building Code.
C.
Application And Submission Requirements. Every application
for a building permit shall comply with all applicable provisions
of the Lake Saint Louis Comprehensive Building Code and any regulations
issued by the Chief Building Official and filed with the City Clerk
requiring such other information as may be necessary to determine
compliance with this Chapter.
D.
Issuance. No building permit shall be issued until such
permit has been examined by the Chief Building Official and he/she
has affixed to it his/her approval that the application is in proper
form, contains all necessary information and the proposed use of land,
building or structure complies in all respects with Title IV, Land
Use.
[Ord. No. 4190, 2-1-2021]
E.
Uncompleted Structures. No structure shall be permitted
to stand with its exterior in an unfinished condition for longer than
six (6) months after commencement of construction. Upon written request
demonstrating hardship, the City Development Administrator may grant
extensions of the required completion date for up to three (3) additional
months. Upon failure to meet the construction completion date, the
property owner shall be served with written notice of violation. Upon
failure to comply with said written notice of violation, the property
owner shall be guilty of a misdemeanor and, upon conviction thereof,
shall be fined under the stated terms and conditions. Property owners
in violation of this Section shall not be issued any additional building
permits until all violations are satisfied.
[Ord. No. 4190, 2-1-2021]
F.
Professional Residential Builders Registration.
1.
"Professional residential builder" shall mean any
builder who acts as a general building contractor who undertakes to
construct any residential building or buildings for use or occupancy
by others.
A "control entity" shall mean:
a.
Any person who, either alone or in joint tenancy with a spouse or
with a parent, sister, brother, son or daughter, owns a majority of
the voting stock of a corporation or other entity which owns a majority
of the voting stock of a corporation;
b.
A person who is the sole director of a corporation;
c.
A person who, either alone or together with a spouse, parent, sister,
brother, son or daughter, has the ability to nominate and approve
a majority of the directors of a corporation;
d.
A partnership, corporation, association or other entity which has
the ability to nominate and approve a majority of the directors of
a corporation;
e.
A person, partnership, corporation, association or other entity that
is a general partner of a partnership;
f.
A person who, alone or together with a spouse, parent, sister, brother,
son or daughter, has a majority of the votes needed by an association
to make a decision;
g.
A partnership, corporation, association or other entity which has
a majority of the votes needed by an association to made a decision;
or
h.
Any entity which possesses, directly or indirectly, the power to
direct or cause the direction of the management and policies of another
entity, whether through ownership or voting securities, by contract
or otherwise.
|
An "affiliated company" means any entity which,
directly or indirectly through one (1) or more intermediaries, controls
or is controlled by or is under common control with another entity.
|
2.
No building permit shall be issued to any professional residential
builder or general building contractor who does not have a valid,
current residential builder's registration from the City of Lake Saint
Louis.
3.
An annual registration shall be issued by the City Clerk to a professional
residential builder upon compliance with the following conditions:
a.
Filing an application identifying all "control persons" of the applicant
by name and address.
b.
Evidence of an approved merchant's license issued by the City.
c.
Certification by the City Collector that neither the applicant nor
any affiliated company has any outstanding delinquent fees, taxes,
assessments or fines due to the City.
d.
Certification by the Chief Building Official that neither the applicant
nor any control person of the applicant, nor any affiliated company
has, within the preceding three (3) years, abandoned or discontinued
the construction of any building during the period of validity of
a building permit for it, in such fashion as to render the building
a "dangerous building".
e.
Posting of a bond, irrevocable letter of credit or suitable escrow in favor of the City, the form and language to be approved by the City Attorney, in an amount of ten thousand dollars ($10,000.00). The purpose for said bond and the manner and circumstances under which said bond is to be forfeited to the City shall be as set forth in Subsection (F)(3)(f)(2) below.
f.
The builder's registration of any professional builder shall be revoked
by the Chief Building Official and the bond shall be forfeited to
the City:
(1)
If at any time the builder or any control person or affiliated
company of the builder or control person fails to complete structure(s)
within the time limits specified by an approved building permit or
an approved extension thereof;
(2)
If any builder or any control person or affiliated company of
the builder or control person is convicted of any municipal ordinance
violation arising out of such person's building within the City or
is convicted of three (3) or more mud on the street violations in
a twelve (12) month period, or fails to comply in a timely fashion
with any order or notice of any Code Enforcement Official relating
to building that may be authorized by City ordinances.
g.
The disapproval or the revocation of any builder's registration may
be appealed to the Board of Adjustment by serving notice of appeal
on the City Clerk not later than ten (10) days after such disapproval
or revocation.
h.
If the registration of any builder or any control person or affiliated
company shall have been revoked hereunder, no new or future registrations
shall be issued to such builder except by action of the Board of Aldermen
upon such reasonable conditions as it may deem appropriate.
H.
The Director of Public Works or Community Development shall have the power to order all work to be stopped on any building(s) or structure(s) where such work is being done in violation of any provisions of the Municipal Code, or where work in is being done, in the development as a whole, that is in violation of any provision of the Municipal Code. Such order shall stop work on all projects the subject contractor, subcontractor, property owner or other agent is currently engaged in at the discretion of the Community Development Administrator when he/she reasonably believes that the violation that is the subject of the stop work order materially affects the health, safety and welfare of the community and is unlikely to be corrected without such action. For purposes of this provision, the discretion of the Community Development Administrator to extend any stop work order to other work in the development as a whole, or in any other development, shall extend to work being performed under the "control" of the primary entity to which the stop work order applies or is under the control of any entity which is a "control entity" of the primary entity to which the stop work order applies as those terms are defined in Section 135.260 of the Municipal Code. Such stop work orders may be given orally and may be enforced when so given provided, however, that any oral stop work order shall be followed by a written order within two (2) hours. All work that is stopped shall not be resumed except upon permission of the Community Development Administrator. Written stop work orders may be served by any Police Officer, any Public Works Department employee or any Community Development Department employee and may be served by personal service or by posting on the premises affected.
[Ord. No. 3707 § 2, 6-19-2017]
I.
Where
any provision or provisions of the Lake Saint Louis Municipal Code,
properly and lawfully adopted, appears to be in conflict with any
provision of the Comprehensive Building Code, as adopted by this Section,
the more stringent or most stringent of the apparently conflicting
provisions will apply.
J.
Any
person violating any provisions of this Chapter is guilty of a public
offense and upon conviction thereof may be fined in a sum not to exceed
five hundred dollars ($500.00) and/or sentenced to ninety (90) days
imprisonment for each violation. Every day that this Chapter is violated
shall constitute a separate offense. In addition to the imposition
of such penalties, the City shall have available all other remedies
including, but not limited to, revocation of permits and the refusal
to issue future permits.
[CC 1988 §78.500]
A.
The
responsibility for the displaying of the assigned number for each
house and building in the City shall rest with the property owner,
trustee, lessee, agent or occupant of each house or building. Approved
street address numbers shall be the address numbers assigned by the
postmaster.
B.
Such
numbers shall be of such size and in such location to be visible from
the nearest street. Address numbers shall be a minimum of three (3)
inches in height and shall be located either near a building's main
entrance or on a surface that is easily visible from the nearest street.
Additional displays of assigned numbers may be displayed at the property
owner's discretion. Assigned numbers shall be displayed with arabic
numerals in a color that contrasts with the color of the subject house
or building. Address displays in script are prohibited if used exclusively.
Houses or buildings that are setback more than one hundred (100) feet
from a street's curb shall be required to display address numbers
within fifty (50) feet of the street curb.
[CC 1988 §78.510]
Any house or building found to be in violation of this Article
shall be subject to a notice of violation and given ten (10) days
to abate said nuisance.