The purpose of these regulations is to safeguard potable water
supplies by preventing backflow into public water systems. The regulations
are to be reasonably interpreted. It is the intent of these regulations
to recognize that there are varying degrees of hazard and to apply
the principle that the degree of protection should be commensurate
with the degree of hazard.
As used in this article, the following terms shall have the
meanings indicated:
AIR-GAP SEPARATION
A physical break between a supply pipe and a receiving vessel.
The air gap shall be at least double the diameter of the supply pipe,
measured vertically above the top rim of the vessel, in no case less
than one inch.
APPROVED CHECK VALVE
A check valve that seats readily and completely. It must
be carefully machined to have free moving parts and assured watertightness.
The face of the closure element and valve seat must be bronze, composition
or other noncorrodible material which will seat tightly under all
prevailing conditions of field use. Pins and bushings shall be of
bronze or other noncorrodible, nonsticking material, machined for
easy, dependable operation. The closure element, e.g., clapper, shall
be internally weighted or otherwise internally equipped to promote
rapid and positive closure in all sizes, where this feature is obtainable.
APPROVED DOUBLE CHECK VALVE ASSEMBLY
An assembly of at least two independently acting check valves,
including tightly closing shutoff valves on each side of the check
valve assembly and suitable leak-detector drains plus connections
available for testing the watertightness of each check valve. This
device must be approved as a complete assembly.
APPROVED REDUCED-PRESSURE-PRINCIPLE BACKFLOW PREVENTION DEVICE
A device incorporating two or more check valves and an automatically
operating differential relief valve located between the two checks,
two shutoff valves and equipped with necessary appurtenances for testing.
The device shall operate to maintain the pressure in the zone between
the two check valves at less than the pressure on the public water
supply side of the device. At cessation of normal flow, the pressure
between check valves shall be less than the supply pressure. In case
of leakage of either check valve, the differential relief valve shall
operate to maintain this reduced pressure by discharging to the atmosphere.
When the inlet pressure is two pounds per square inch or less, the
relief valve shall open to the atmosphere, thereby providing an air
gap in the device. To be approved, these devices must be readily accessible
for maintenance and testing and installed in a location where no part
of the valve will be submerged. The enclosure must be self-draining,
so that the large amount of water which the relief valve may vent
will be disposed of reliably without submergence of the relief valve.
This device must also be approved as a complete assembly.
AUXILIARY SUPPLY
Any water supply on or available to be subjected to static
line pressure.
BAROMETRIC LOOP
A loop of pipe rising approximately 35 feet, at its topmost
point, above the highest fixture it supplies.
CERTIFIED BACKFLOW-PREVENTION-DEVICE TESTER
A person who is examined annually by the water purveyor and
found competent for the testing of backflow-prevention devices. He
shall be provided with an appropriate identification card, which must
be renewed annually. Failure to perform his duties competently and
conscientiously will result in prompt withdrawal of his certification.
CROSS-CONNECTIONS
Any unprotected connection between any part of a water system
used or intended to supply water for drinking purposes and any source
or system containing water or substance that is not or cannot be approved
as equally safe, wholesome and potable for human consumption.
WATER SUPERVISOR
That consumer or a person on the premises charged with the
responsibility of complete knowledge and understanding of the water
supply piping within the premises and for maintaining the consumer's
water system free from cross-connections and other sanitary defects,
as required by regulations and laws.
The protective device required shall depend on the degree of
hazard as tabulated below:
A. At the service connection to any premises where there is an auxiliary
water supply handled in a separate piping system with no known cross-connection,
the public water supply shall be protected by an approved double check
valve assembly.
B. At the service connection on any premises on which there is an auxiliary
water supply where cross-connections are known to exist which cannot
be presently eliminated, the public water supply system shall be protected
by an air-gap separation or an approved reduced-pressure-principle
backflow-prevention device.
C. At the service connection to any premises on which a substance that
would be objectionable, but not necessarily hazardous to health, if
introduced into the public water supply, is handled so as to constitute
a cross-connection, the public water supply shall be protected by
an approved double check valve assembly.
D. At the service connection to any premises on which a substance of
unusual toxic concentration or danger to health is or may be handled,
but not under any pressure, the public water supply shall be protected
by an air-gap separation or an approved reduced-pressure backflow-prevention
device. This device shall be located as close as practicable to the
water meter, and all piping between the water meter and receiving
tanks shall be entirely visible.
E. At the service connection to any premises on which any material dangerous
to health, or toxic substance in toxic concentration, is or may be
handled under pressure, the public water supply shall be protected
by an air-gap separation. The air gap shall be located as close as
practicable to the water meter, and all piping between the water meter
and receiving tanks shall be entirely visible. If these conditions
cannot reasonably be met, the public water supply shall be protected
with an approved reduced-pressure-principle backflow-prevention device,
provided that the alternative is acceptable to the water purveyor.
F. At the service connection to any sewage treatment plant or sewage
pumping station, the public water supply shall be protected by an
air-gap separation. The air gap shall be located as close as practicable
to the water meter and shall be entirely visible. If these conditions
cannot be reasonably met, the public water supply shall be protected
with an approved reduced-pressure-principle backflow-prevention device.
It shall be the duty of the water user on any premises on account
of which backflow protective devices are installed to have competent
inspections made at least once a year or more often in those instances
where successive inspections indicate repeated failure. These devices
shall be repaired, overhauled or replaced at the expense of the water
user whenever they are found to be defective. These tests shall be
performed by a qualified backflow-prevention-device tester, and all
test results will be provided to the water purveyor within 72 hours
after the test is made. Records of such tests, repairs and overhaul
shall also be kept and made available to the water purveyor and the
local health department upon request.
Whenever the Plumbing Inspector determines that it is not practical
to protect drinking water systems on premises against entry of water
from a source or piping system or equipment that cannot be approved
as safe or potable for human use, an entirely separate drinking water
system shall be installed to supply water at points convenient for
consumers.
Water systems for fighting fire, derived from a supply that cannot be approved as safe or potable for human use, shall, wherever practicable, be kept wholly separate from drinking water pipelines and equipment. In cases where the domestic water system is used for both drinking and firefighting purposes, approved backflow-prevention devices shall be installed to protect such individual drinking-water lines as are not used for firefighting purposes. Any auxiliary firefighting water supply which is not approved for the potable purposes, but which is so connected that it may be introduced into potable water piping during an emergency, shall be equipped with an approved automatic chlorination machine. It is hereby declared that it is the responsibility of the person or persons causing the introduction of said unapproved or unsafe water into the pipelines to see that a procedure be developed and carried out to notify and protect users of this piping system during the emergency and that special precautions be taken to disinfect thoroughly and flush out all pipelines which may become contaminated before they are again used to furnish drinking water. In the event that the means of protection of water consumers is by disinfection of the auxiliary firefighting supply, the installation and its use shall be thoroughly reliable. The public water supply must be protected against backflow from such dual domestic fire systems, as detailed in §§
336-112 through
336-114.
Potable water pipelines connected to equipment for industrial
processes or operations shall be protected by a suitable backflow-prevention
device located beyond the last point from which drinking water may
be taken, which device shall be provided on the feedline to process
piping or equipment. In the event that the particular process liquid
is especially corrosive or apt to prevent reliable action of a backflow-prevention
device, air-gap separation shall be provided. These devices shall
be tested by the water user at least once a year or more often in
those instances where successive inspections indicate repeated failure.
The devices shall be repaired, overhauled or replaced whenever they
are found to be defective. These tests must be performed by a qualified
backflow-prevention-device tester and records of tests, repairs and
replacement shall be kept and made available to the water purveyor
and the Health Department upon request.
Sewage pumps shall not have priming connections directly off
any drinking water systems. No connections shall exist between the
drinking water system and any other piping equipment or tank in any
sewage treatment plant or sewage pumping station.
No water service connection to any premises shall be installed
or maintained by the water purveyor, unless the water supply is protected
as required by state regulations and this article.
Service of water to any premises may be discontinued by the
water purveyor if a backflow preventive device required by this rule
and regulation is not installed, tested and maintained; if any defect
is found in an installed backflow preventive device; if it is found
that a backflow preventive device has been removed or bypassed; or
if unprotected cross-connections exist on the premises, and service
will not be restored until such conditions or defects are corrected.
[Amended 11-24-1987 by L.L. No. 3-1987; 4-29-2020 by L.L. No. 3-2020]
Except as otherwise provided herein, any person committing an
offense against any provision of this article shall be guilty of a
violation punishable by a fine not exceeding $1,000 or by imprisonment
for a term not exceeding 15 days, or by both such fine and imprisonment.
The continuation of an offense against the provisions of this article
shall constitute, for each day the offense is continued, a separate
and distinct offense hereunder.