Require for all new construction and substantial improvements. That fully enclosed areas below the lowest floor that are usable
solely for parking of vehicles, building access or storage in an area
other than a basement and which are subject to flooding shall be designed
to automatically equalize hydrostatic flood forces on exterior walls
by allowing for the entry and exit of floodwaters. Designs for meeting
this requirement must either be certified by a registered professional
engineer or architect or meet or exceed the following minimum criteria:
A minimum of two (2) openings having a total net area of not less
than one (1) square inch of every square foot of enclosed area subject
to flooding shall be provided. The bottom of all openings shall be
no higher than one (1) foot above grade. Openings may be equipped
with screens, louvers, valves, or other coverings or devices provided
that they permit the automatic entry and exit of floodwaters.