A. 
Work included.
(1) 
The work of this article includes, but is not limited to the installation of conduits, poles, controls, lighting fixtures, lamps and wire necessary for a complete and functioning streetlighting system.
(2) 
Related work specified elsewhere.
(a) 
Trenching, backfilling and compacting: Article VII.
(b) 
Trench paving and restoration: Article XIII.
(c) 
Plain and reinforced cement concrete: Article XXVII.
(d) 
Cement concrete for utility construction: Article XXVIII.
(3) 
Definitions: none.
(4) 
Applicable Standard Details: DT 16500-1, Street Lighting Installation Details.
B. 
Quality assurance.
(1) 
Reference standards.
(a) 
ANSI, American National Standard Institute.
(b) 
ASTM, American Society for Testing and Materials.
(c) 
NEMA, National Electrical Manufacturers Association.
(d) 
NECS, National Electrical Safety Code.
(e) 
NFPA, National Fire Protection Association.
(f) 
UL, Underwriters' Laboratories, Inc.
(g) 
IESNA, Illuminating Engineering Society of North America.
(h) 
IEEE, Institute of Electrical and Electronics Engineers.
(i) 
IPCEA, Insulated Power Cable Engineers Association.
(j) 
OSHA, Occupational Safety and Health Administration.
(k) 
NEC, National Electrical Code.
(2) 
Inspections. Upon completion of work, the customer/developer shall secure an electrical inspection from an electrical inspection agency acceptable to the authority having jurisdiction and the local electric company.
(3) 
Testing:
(a) 
All electrical conductors, after installation of wiring and apparatus has been completed, shall be tested by this contractor to insure continuity, proper splicing, freedom from ground (except made ground and those required for protection) and insulation resistance in accordance with Underwriters' requirements. This contractor shall furnish and employ suitable instruments such as ammeters, volt meters, meggars, etc. Preliminary testing with magnetos will be permitted but will not be accepted as a final or conclusive test.
(b) 
Prior to testing or adjusting, this contractor shall consult with the municipality to determine the intended function of any equipment, wiring or systems. This contractor shall then perform such tests and make the necessary adjustments to ensure that the required function is obtained.
(c) 
Equipment and wiring systems not specified as requiring a specific test shall be tested in operation to determine that all design functions are satisfactorily performed.
C. 
Submittals.
(1) 
Submit (in triplicate) the certificate of compliance following electrical inspection.
(2) 
Voltage drop calculations, prepared by a professional engineer licensed in Pennsylvania.
(3) 
Photometric data for lighting fixtures and point-by-point maintained footcandle printout that includes maximum maintained footcandles, minimum maintained footcandles, average maintained footcandles, maximum: minimum ratio, average: minimum ratio.
(4) 
Efficiency and candle power distribution curve for each type of lighting fixture.
(5) 
Catalog cuts and dimensional data for poles and lighting fixtures proposed.
(6) 
Concrete base design.
D. 
Job conditions.
(1) 
Codes and standards.
(a) 
All electrical work shall meet the requirements of the National Electric Code of the National Fire Protection Association. In addition, any state, municipal or other authorities laws, rules or regulations applicable to the work shall be followed.
(b) 
Where applicable, all materials and equipment shall bear the label of approval of the Underwriters Laboratory, Inc.
(c) 
Photometric performance of the installed lighting system shall be within guidelines established by the Illuminating Society of North America.
(d) 
Reference to the codes and standards listed herein shall constitute the minimum acceptable requirements. Where drawings and specification requirements exceed those of the codes listed herein, the contractor shall follow the drawings and specifications.
E. 
Coordination and development of streetlighting.
(1) 
The electric company's streetlighting service is only available to the municipality. The developer shall coordinate streetlighting requests with the Borough and all streetlighting shall conform to the municipality's and electric company's streetlighting specifications.
(2) 
The customer/developer shall provide the electric company with a preliminary plan showing proposed locations of streetlight standards. The electric company does not design or approve the design of streetlighting systems.
(3) 
The electric company returns plan showing the available source(s) for the streetlight feed(s) and, if not previously provided, this document which lists material requirements.
(4) 
The customer/developer shall provide streetlight luminaire(s) which is equipped to operate with the material, as specified herein and as approved by the electric company.
(5) 
Requirements.
(a) 
Streetlights shall be spaced at regular intervals as necessary to conform to the performance criteria. Minor adjustments to spacing may be made to accommodate lot lines, driveways, etc.
(b) 
The customer/developer shall provide the electric company with a final plan showing the location of the facilities (streetlights, service equipment, conduit and cable routing, etc.) and size and type of cables and fusing.
(c) 
Prior to excavating, the contractor shall call the PA one-call system.
(d) 
The customer/developer shall install facilities in accordance with requirements of the electric company, the municipality, the manufacturer, the National Electric Code, and the final plan. The customer/developer is required to provide and/or install:
[1] 
All trenching and backfilling, including service cable from source to junction box.
[2] 
All cable, conduit, foundations, standards, luminaires, lamps, and photoelectric controls as per developer agreement with the municipality.
[3] 
Service equipment at each source location designated by the electric company to facilitate streetlighting cable connections.
(e) 
The customer/developer shall secure an electrical inspection from the electric-company-accepted electrical inspection agency before the electric company will energize.
(f) 
Upon receipt of a streetlighting agreement from the municipality and the electrical inspection certificate, the electric company will:
[1] 
Install service to the line side of the service equipment.
[2] 
Install on each streetlight standard and identification tag to show grid location and an additional tag to show the maintenance agreement, lamp type and size.
(g) 
Note that a contract for energy and maintenance of fixtures with the municipality and the electric company is required prior to the electric company energizing the streetlighting system.
F. 
Calculations.
(1) 
Voltage drop shall be calculated to ensure voltage drop will not exceed the requirements of the National Electrical Code.
(2) 
Point-by-point footcandle calculations shall be performed to verify that the lighting system photometric performance conforms to the IESNA recommendations, as adopted by the municipality.
A. 
Lamps: high-pressure sodium meeting the following requirements:
Lamp Watts:
100W
150W
250W
Ballast Code:
S54
S55
S50
Lamp Volts:
55V
55V
100V
Light Center Length:
5 inches
5 inches
5 inches
Burning Position:
Any
Any
Any
Base Type:
Mogul
Mogul
Mogul
B. 
Ballasts.
(1) 
HID fixture ballasts. HID fixture ballasts shall conform to the following:
(a) 
High power factor.
(b) 
No inrush current condition.
(c) 
Current during warmup shall be less than normal operating current.
(d) 
Lamp starting to -20° F. for outdoor ballasts.
(e) 
Input line voltage range plus or minus 10%, minimum.
(f) 
Fuse located in hand hole at bottom of pole.
(2) 
Manufacturer: Advance.
(3) 
Substitutions: General Electric, Universal, or same manufacturer as lighting fixture manufacturer.
C. 
Poles.
(1) 
Streetlight pole.
(a) 
All poles shall have a hand hole near base of pole.
(b) 
All anchor bolt nuts shall be covered, either by metal pole base cover furnished with pole or by nut covers furnished by pole manufacturer.
(c) 
Lighting standards shall have each luminaire separately ballasted. Each ballast shall be separately fused with all fuses located near the hand hole of the pole base, where easily accessible.
(d) 
Weep holes shall be provided in the base of the pole shaft to prevent any accumulations of water.
(e) 
The pole shall contain a hand hole sufficiently large to allow inspection of splices, ground connection, and fuses, and ability to repull circuitry between poles. A ground pad shall be welded inside, ground smooth and tapped to receive a 1/4-20 thread, for lugged connection to ground rod.
(f) 
Pole finish shall be polyester powder coat paint and the color shall be as approved by the municipality and/or the electric company.
(g) 
Pole shall be 12 feet high above finish grade, including base.
(h) 
Manufacturer: as approved.
D. 
Fuse and fuse holder. Fuse and fuse holder for the fuse disconnect in the customer's junction box shall be per the electric company's requirements, fuse size as required.
E. 
Lighting fixtures.
(1) 
Streetlight fixture.
(a) 
Volts: 120V.
(b) 
Mounting: post-top.
(c) 
Type: high-pressure sodium.
(d) 
Description: die-cast aluminum housing, fully enclosed and gasketed. UL listed suitable for wet locations. Impact- and heat-resistant glass lens. NEMA Type III distribution.
(e) 
On projects that GPU Energy will maintain lighting fixtures after installation, fixtures shall conform to GPU Energy's requirements.
(f) 
Manufacturer: as approved (same as pole manufacturer).
F. 
Structural requirements.
(1) 
All poles, concrete bases and fixtures shall be installed as an integral unit to withstand 100 mph winds and 120 mph gusts.
(2) 
All pole embedded depths and/or concrete bases shall be shown on the drawings, shall be designed by and the design drawings sealed by a professional engineer, licensed in Pennsylvania, taking into account soil conditions at the location of the pole.
(3) 
All dimensions of the pole, base plate, material type and thickness and welding information shall appear on the shop drawings along with wind loading for pole and lighting fixtures.
G. 
Photo electric control. Photo electric controls must be suitable for use with an EEI-NEMA standard twist lock receptacle, shall have a maximum load capability of 1,800 volt-amperes, shall be equipped with suitable type surge protection, and have the following characteristics:
(1) 
Operating voltage: 120V.
(2) 
Voltage range: 105 to 130V.
(3) 
Time delay: 10 seconds maximum.
H. 
Conduit.
(1) 
Polyvinyl chloride (PVC): Schedule 40.
(2) 
Extruded from virgin polyvinyl chloride compound.
(3) 
Resistant to water, oil, outdoor aging, exposure to sunlight, underground environments, and corrosive atmospheres.
(4) 
Flame retardant for use above ground, resistant to low temperatures, and resistant to distortion due to heat under conditions likely to be encountered in intended service.
(5) 
Sufficient strength to withstand abuse, such as impact and crushing during handling, installation, and service. Ten-foot lengths with one coupling furnished for each length.
(6) 
Minimum size: one inch.
(7) 
Each length shall be clearly and durably marked with the manufacturer's name. Markings shall be permanent for PVC used above ground.
(8) 
PVC conduit shall be UL listed.
(9) 
Comply with applicable ASTM testing procedures and specifications.
(10) 
Fittings.
(a) 
Conform to applicable PVC conduit specifications above.
(b) 
Manufacturer: same as PVC conduit manufactures.
I. 
Wire.
(1) 
All wire and cable shall conform to the following:
(a) 
Copper shall not be less than 98% conductivity.
(b) 
Single conductor, unless otherwise indicated.
(c) 
Color coded.
(d) 
Marked with classification type, conductor size, and voltage rating, every foot, where applicable.
(e) 
Minimum size: #12 AWG, unless otherwise specified.
(f) 
Sizes #8 AWG and larger shall be stranded.
(g) 
UL listed.
(2) 
Wire specification No. 1.
(a) 
Type THW insulation, UL listed.
(b) 
Six-hundred-volt insulation.
(c) 
Ampacity based upon maximum conductor temperature of 75° C. in wet or dry locations, continuous operation.
(d) 
Conform to ASTM B3 for solid conductors and ASTM B8 for stranded conductor.
(e) 
Annealed, uncoated copper conductor.
(f) 
Flame retardant, moisture- and heat-resistant thermoplastic (PVC) insulation.
(3) 
Wire specification No. 2.
(a) 
Type XHHW insulation, UL listed.
(b) 
Six-hundred-volt insulation.
(c) 
Ampacity based upon maximum conductor temperature of 90° C. dry locations and 75° C. wet locations, continuous operation.
(d) 
Moisture- and heat-resistant cross linked polyethylene (XLP) insulation.
(e) 
Conform to applicable NEMA and IPCEA requirements.
(f) 
Conform to ASTM B3 for solid conductors and ASTM B8 for stranded conductors.
(g) 
Soft copper conductor.
(4) 
Wire Specification No. 4.
(a) 
Type THHN/THWN insulation, UL listed.
(b) 
Six-hundred-volt insulation.
(c) 
Ampacity based upon maximum conductor temperature of 90° C. dry locations [THHNO and 75° C. dry and wet locations (THWN)], continuous operation.
(d) 
Flame-retardant, moisture- and heat-resistant thermoplastic (PVC) insulation with nylon jacket.
(e) 
Conform to applicable NEMA and IPCEA requirements.
(f) 
Conform to ASTM B3 for solid conductors and ASTM B8 for stranded conductors.
(g) 
Soft copper conductor.
J. 
Connectors.
(1) 
Connector specification No. 1: splice connectors.
(a) 
For insulated wire, 600 volt and under, #8 AWG and smaller.
(b) 
Compression solderless connector.
(c) 
Insulated or noninsulated.
(d) 
UL listed.
(e) 
Manufacturer: Buchanan B-cap.
(f) 
Substitutions: Ideal Wing-nut, 3M Schotchlok.
(2) 
Connector specification No. 2: splice connectors.
(a) 
For insulated wire, 600 volts and under, #6 AWG and larger.
(b) 
Split bolt pressure connector.
(c) 
Bronze.
(d) 
UL listed.
(e) 
Manufacturer: Anderson.
(f) 
Substitutions: Thomas & Betts, Penn-Union, Dossert, Burndy, Reliable Electric, Ideal.
(3) 
Connector specification No. 3: splice connectors.
(a) 
For insulated wire, 600 volts and under, #6 AWG and larger.
(b) 
Compression or crimp connector, short sleeve.
(c) 
Copper.
(d) 
UL listed.
(e) 
Manufacturer: Anderson.
(f) 
Substitutions: Thomas & Betts, Dossert, Burndy, MAC, 3M, Ideal.
(4) 
Connector specification No. 4: lug connector.
(a) 
For insulated wire, 600 volt and under, #8 AWG and larger.
(b) 
Compression or crimp connector, short sleeve.
(c) 
Copper.
(d) 
UL listed.
(e) 
Manufacturer: Anderson.
(f) 
Substitutions: Thomas & Betts, Penn-Union, Dossert, Burndy, MAC, 3M, Ideal.
(5) 
Connector specification No. 5: lug connector.
(a) 
For insulated wire, 600 volt and under, #8 AWG and larger.
(b) 
Bolted-type pressure connection, hex head or hex socket pressure bolts.
(c) 
Copper.
(d) 
UL listed.
(e) 
Manufacturer: Penn-Union.
(f) 
Substitutions: Thomas & Bells, Anderson, Dossert, Burndy, Ideal.
(6) 
Connector specification No. 6: lug connector.
(a) 
For insulated wire, 600 volt and under, #10 AWG and smaller.
(b) 
Compression or crimp type.
(c) 
Standard barrel, insulated for 600 volts.
(d) 
Ring terminal or flanged or flared block spade terminal.
(e) 
Copper.
(f) 
UL listed.
(g) 
Manufacturer: Penn-Union Penn Crimp.
(h) 
Substitutions: Ideal Crimp Terminal, Thomas & Betts Sta-Kon, Burndy Insulug, MAC MiniDent, 3M Scotchlok Terminals.
(7) 
Connector application. Unless otherwise noted, connectors shall be used for insulated wire, 600 volts and under as follows:
Connector Schedule
Application
Connector Spec. No.
Splice Connectors:
#8 AWG and smaller
1
#6 AWG and larger
2 or 3
Lug connectors:
Stranded wire connection under head of binding screw or bolt
4 or 6
Connection to equipment bus, or screw or bolt terminals
4, 5, 6, or manufacturer supplied lugs
K. 
Tape.
(1) 
Tape specification No. 1: tape for insulation 600 volts or less.
(a) 
Vinyl plastic all-weather electrical tape.
(b) 
Manufacturer: 3M Scotch 33+.
(c) 
Substitutions: Tomic, Okonite.
(2) 
Tape specification No. 2: underground marker tape.
(a) 
Material: red, plastic, six inches wide.
(b) 
Marking: CAUTION - BURIED ELECTRIC LINE BELOW, or similar wording.
(c) 
Manufacturer: Griffolyn, Inc.
(d) 
Substitutions: Allen Company.
L. 
Wire markers.
(1) 
Wire marker specification No. 2: vinyl plastic or vinyl polyester.
(a) 
Temperature range: to 250° F.
(b) 
Self-sticking adhesive backing.
(c) 
Waterproof, solvent proof.
(d) 
Printing permanently protected.
(e) 
Manufacturer: Thomas & Betts E-Z-Code, Type WSL.
(f) 
Substitutions: W.H. Brady Co. Type CAB.
M. 
Ground rods.
(1) 
Type: high-strength steel core.
(2) 
Construction: copper exterior welded to the steel core.
(3) 
Chamfered top to prevent mushrooming. Pointed end.
(4) 
Minimum diameter.
(a) 
Ten-foot rod: three-fourths-inch diameter.
(b) 
Above 10 feet: one-inch diameter.
(5) 
For lengths over 10 feet, sectional rods with steel driving bolt may be furnished.
(6) 
Manufacturer: Copperweld.
(7) 
Substitutions: Penn-Union, Weaver.
N. 
Ground connectors.
(1) 
Ground connector specification No. 2.
(a) 
Type: ground grid clamps. Compression connection to cable or rod.
(b) 
High-conductivity cast-copper fittings.
(c) 
Cable, rod, plate or combination connector, as required.
(d) 
Suitable for direct burial or imbedded in concrete.
(e) 
Manufacturer: Thomas & Betts.
(f) 
Substitutions: Burndy.
(2) 
Ground connector application. Unless noted otherwise, ground connectors shall be installed as follows: connection of ground wire or ground grid cable to ground rod, building steel or another ground grid cable.
A. 
Raceway installation. PVC conduit shall be installed as follows:
(1) 
Expansion joints shall be installed where expansion and contraction of PVC occurs due to changing temperature conditions.
(2) 
Joints in PVC conduit runs shall be in accordance with manufacturer's recommendations.
(3) 
PVC conduit shall not be used where subject to ambient temperature exceeding those in which conduit has been approved.
(4) 
Fittings as specified under raceway specification No. 4 shall be used when installing PVC conduit.
(5) 
Install ground wire, sized per NEC in all PVC conduit runs.
(6) 
Underground raceways or duct banks shall have a marker or warning tape installed above raceway, 12 inches below finished grade. Use tape specification No. 2. Duct banks with widths over 12 inches shall have six-inch wide tape runs installed side-by-side on twelve-inch (maximum) centers.
B. 
Wiring methods.
(1) 
Wiring shall be installed in raceways unless otherwise noted.
(2) 
Use color-coded wire throughout as required by the National Electric Code for convenience in testing and maintenance. Neutral conductors shall be color-coded neutral gray or white; grounding conductors shall be green.
(3) 
Pull wire into conduit so that insulation will not be damaged. Approved pulling compound shall be used to assist in pulling of six-hundred-volt wire into conduit. Oil or grease will not be permitted. Pulling compound shall be compatible with wire insulation and conduit.
(4) 
Conductors shall be installed continuous from outlet to outlet, without splicing except within outlet or junction boxes.
(5) 
Noninsulated splices in insulated wire, 600 volts and under shall be factory insulated as follows:
(a) 
Rubber and friction tape coated with Scotchkote or similar coating.
(b) 
Scotchfil or equivalent electrical putty with tape specification No. 1.
(c) 
Insulation of splices shall provide same insulation qualities as insulation of wire being spliced.
(6) 
Stranded wire shall not be placed under the head of a binding screw or bolt. Refer to § 97-94, this article, for connectors to be used in stranded wire connections under head of binding screw or bolt.
(7) 
Wire shall be identified by use of wire markers at termination points, including outlet boxes, pull boxes, junction boxes, wireways and at locations where wire changes direction within an enclosure. Unless otherwise specified, wire markers shall be as specified under wire marker specification No. 2.
C. 
Ground rod installation.
(1) 
Ground rods shall be installed as required by the National Electric Code near the customer's junction box for the electrical service ground.
(2) 
Ground rods shall be driven to a depth so that the top of the rod is two feet below grade.
D. 
Grounding.
(1) 
Equipment grounding.
(a) 
Unless otherwise specified, conductive noncurrent carrying electrical materials and equipment shall be grounded. Nonelectrical items of equipment shall be grounded as indicated on drawings. Grounding shall be in accordance with National Electrical Code requirements.
(b) 
Grounding shall be separate insulated grounding conductors pulled with phase conductors. The grounding system shall be electrically and mechanically continuous from all outlet devices, power utilization equipment, and distribution equipment to system main ground point.
(c) 
Bonds and jumpers shall be furnished and installed where required during construction and where necessary to ensure both operation and safety.
(d) 
Service ground point shall be ground rods near the customer's junction box.
(e) 
Neutral conductors shall be continuous throughout the system and shall be grounded only at switchboard neutral.
(f) 
Ground wire shall be installed in all PVC raceway runs. Ground wires shall be insulated.
(2) 
Grounding tests.
(a) 
Ground resistance of main system grounding point shall be inspected and shall not exceed values required by the National Electrical Code. Inspection shall be made using two auxiliary ground rod (three point) method or other approved method. If resistance is found to be higher than that allowed by the National Electric Code, additional ground rods shall be driven until a resistance below allowed value is obtained.
(b) 
Outside inspections shall not be performed during unusually wet conditions. Cheek shall be made during dry weather conditions.
(c) 
Complete inspection record shall be submitted to the municipality showing resistance values and calculations and shall indicate method of test.
E. 
Excavation. Excavate trenches and for pole bases as specified in Article VII. Provide thirty-inch minimum cover from the top of the conduit to the finished grade elevation.
F. 
Paving and restoration. Paving and restoration shall be as specified in Article XIII.
G. 
Concrete. Concrete shall be placed as specified in Articles XXVII and XXVIII.