"507.5.7. Fire hydrants; Specifications. Fire hydrants
shall have national standard threads and be approved by the Fire Official.
The following criteria shall be required regarding installation:
| |
1.
|
The hard-suction connection shall face the street, access driveway
or fire walkway with the side outlets parallel to the cartway or walkway
edge.
|
2.
|
A minimum clearance of 20 inches, measured from the bottom of
the lowest outlet to final grade of ground or pavement, shall be provided.
In no case shall said clearance be more than 26 inches.
|
3.
|
Fire hydrants shall be appropriately spaced so as not to exceed
500 feet between hydrants.
|
4.
|
Fire hydrants required to be located outside a street right-of-way
shall not be accepted as public fire hydrants by the Township.
|
5.
|
. Fire hydrants shall be located within five feet of paved streets,
access driveways or fire walkways."
|
"603.4. Portable heaters. Portable heaters, vented
or unvented, in any structure, other than a single-family dwelling,
which is used wholly or in part for human habitation, shall be prohibited.
Portable heaters shall include, but not be limited to, heaters having
a barometrically fed fuel control, with a fuel supply tank located
less than 42 inches from the center control, with a fuel supply tank
located less than 42 inches from the center of the burner, using gas,
kerosene, range oil or No. 1 fuel oil for fuel.
|
603.4.1. Prohibited locations. Unvented
fuel-fired heating equipment shall not be located in or obtain combustion
air from any of the following rooms or spaces: sleeping rooms, bathrooms,
toilet rooms or storage rooms.
|
603.4.1.1. Certain sales prohibited. No person shall sell or offer for sale or install a secondhand,
previously owned, space heater or portable stove which uses gas, kerosene,
range oil or No. 1 fuel oil for fuel.
|
603.4.1.2. Limited permissible uses of unvented
kerosene heaters. Unvented kerosene heaters may be used in
an agricultural building or a building under construction. Such heaters
shall meet UL Subject 647 and bear the Underwriters' Laboratories,
Inc., label, so certifying compliance."
|