[Ord. No. 2021-2324, 3/9/2021]
1. The purpose of this Part is:
A. To protect the public water system from contamination or pollution
by isolating within the consumer's water system contaminants
or pollutants which could backflow through the service connections
into the water system.
B. To promote the elimination or control of existing cross-connections,
actual or potential, between the public's or consumer's
potable water system and nonpotable water systems, plumbing fixtures
and sources or systems containing process fluids.
C. To provide for the maintenance of a continuing program of cross-connection
control which will systematically and effectively prevent the contamination
or pollution of the public and consumer's potable water system.
D. To ensure conformance with standards established by the American
Water Works Association (AWWA).
[Ord. No. 2021-2324, 3/9/2021]
This Part shall apply to all premises served by the public water
system of the Borough of Phoenixville.
[Ord. No. 2021-2324, 3/9/2021]
The Borough and the consumer have the joint responsibility for
protection of the public water system from contamination due to backflow
of contaminants through the water service connection. If, in the judgment
of the Borough or its authorized representative, an approved backflow
prevention device is required, the Borough shall give notice to the
consumer to install such approved backflow prevention device at each
service connection to his premises. The consumer shall immediately
install such approved device or devices at his own expense, and failure,
refusal or inability on the part of the consumer to install such device
or devices shall constitute grounds for discontinuing water service
to the premises until such device or devices have been installed.
[Ord. No. 2021-2324, 3/9/2021]
1. The water system shall be considered as made up of two parts:
A. The public water system; and
B. The consumer's water system.
2. The public water system shall consist of the source facilities and
the distribution system and shall include all those facilities of
the public water supply system under the control of the Borough up
to a point where the consumer's water system begins.
3. The source shall include all components of the facilities utilized
in the production, treatment, storage and delivery of water to the
public distribution system.
4. The public distribution system shall include the network of conduits
used for delivery or water from the source to the consumer's
water system.
5. The consumer's water system shall include all facilities beyond
the service connection which are utilized in conveying water from
the public distribution system to points of use.
[Ord. No. 2021-2324, 3/9/2021]
1. No water service connection shall be installed or maintained to any
premises where actual or potential cross-connections to the public
water system or consumer's water system may exist unless such
actual or potential cross-connections are abated or controlled to
the satisfaction of the Borough.
2. No connection shall be installed or maintained whereby water from
an auxiliary water supply may enter the public or a consumer's
water system unless such auxiliary water supply and the method of
connection and use of such supply shall have been approved by the
Borough.
[Ord. No. 2021-2324, 3/9/2021]
1. The consumer's premises shall be open at all reasonable times
to the Borough or its authorized representative, for purposes of conducting
surveys and investigations of water use practices within the consumer's
premises to determine whether there are actual or potential cross-connections
to the consumer's water system through which contaminants or
pollutants could backflow into the public potable water system.
2. On request by the Borough, the consumer shall furnish information
on water use practices within his premises.
3. It shall be the responsibility of the water consumer to conduct periodic
surveys of water use practices on his premises to determine whether
there are actual or potential cross- connections to his water system
through which contaminants or pollutants could backflow into the public
water system.
[Ord. No. 2021-2324, 3/9/2021]
1. An approved backflow prevention device shall be installed prior to
the first branch line leading off each service line to a consumer's
water system where, in the judgment of the Borough, an actual or potential
hazard to the public water system exists.
2. An approved backflow prevention device shall be installed on each
service line to a consumer's water system where the following
conditions exist:
A. Systems having an auxiliary water supply, unless such auxiliary supply
is accepted as an additional source by the Borough and approved by
the Department of Environmental Protection.
B. Systems where any substance is handled in such a fashion as to create
an actual or potential hazard to the public water system. This shall
include systems having sources or auxiliary systems containing process
fluids or waters originating from the public water system which are
no longer under the sanitary control of the Borough.
C. Systems having internal cross-connections that, in the judgment of
the Borough, are not correctable or intricate plumbing arrangements
which make it impractical to determine whether or not cross-connections
exist.
D. Systems where, because of security requirements or other prohibitions
or restrictions, it is impossible or impractical to make a complete
cross-connection survey.
E. Systems having a repeated history of cross-connections being established
or reestablished.
F. Others which may be specified by the Borough from time to time.
3. An approved backflow prevention device shall be installed on each
service line to a consumer's water system serving, but not necessarily
limited to, the following types of facilities unless the public water
supplier determines that no actual or potential hazard to the public
water supply system exists:
A. Hospitals, mortuaries, clinics, nursing homes.
C. Sewage treatment plants, sewage pumping station or stormwater pumping
station.
D. Food or beverage processing plants.
F. Metal plating industries.
G. Petroleum processing or storage plants.
H. Radioactive material processing plants.
J. Others specified by the Borough.
[Ord. No. 2021-2324, 3/9/2021]
1. The type of protection required under § 26-209, Subsection
1, 2 and 3 of these regulations shall depend on the degree of hazard which exists, as follows:
A. An approved air gap separation shall be installed where the public
water system may be contaminated with substances that are dangerous
to the public health and could cause a severe health hazard.
B. An approved air gap separation or an approved reduced pressure zone
backflow prevention device shall be installed where the public water
system may be contaminated with a substance that could cause a system
or health hazard.
C. An approved air gap separation or an approved pressure zone backflow
prevention device or an approved double check valve assembly shall
be installed where the public water system may be polluted with substances
that would be objectionable but not dangerous to health.
[Ord. No. 2021-2324, 3/9/2021]
1. Any backflow prevention device required by this Part shall be of
a model or construction approved by the Borough and shall comply with
the following:
A. Air gap separation to be approved shall be at least twice the diameter
of the supply pipe, measured vertically above the rim of the vessel,
but in no case less than one inch.
B. A double check valve assembly or a reduced pressure zone backflow
prevention device shall be approved by the public water supplier and
shall mean a device that has been manufactured in full conformance
with standards established by the American Water Works Association
(AWWA) entitled AWWA C506 Standards for Reduced Pressure Principle
and Double Check Valve Backflow Prevention Devices." Said AWWA standards
are herein adopted by the Borough. Final approval, however, of the
double check valve assembly shall be evidenced by a Certificate of
Full Approval issued by an approved testing laboratory, certifying
full compliance with said AWWA standards.
C. An interchangeable connection to be approved shall be either a swing-type
connector or a four-way valve of the lubricated plug type that operates
through a mechanism which unseats the plug, turns it 90° and reseats
the plug. Four-way valves shall not be used as stop valves but must
have separate stop valves on each pipe connected to the valve. The
telltale port on the four-way valve shall have no piping connected,
and the threads or flange on this port shall be destroyed so that
a connection cannot be made.
2. Existing backflow prevention devices approved by the Borough at the time of installation and properly maintained shall, except for inspection and maintenance requirements, be excluded from the requirement of Subsection
1 above, of this regulation, provided that the Borough is assured that they will satisfactorily protect the public potable water system. Whenever the existing device is moved from the present location or requires more than minimum maintenance or when the Borough finds that the maintenance of the device constitutes a hazard to health, the device shall be replaced by a backflow prevention device meeting time requirements of these regulations.
[Ord. No. 2021-2324, 3/9/2021]
1. Backflow prevention devices required by this Part shall be installed
at a location and in a manner approved by the Borough and shall be
installed by a person properly qualified and at the expense of the
consumer, if approved as such by the Borough.
2. Backflow prevention devices installed on the service line to a consumer's
water system shall be located on the consumer's side of the water
meter, as close to the meter as is reasonably practical and prior
to any other connection.
3. Pits and vaults shall be of watertight construction, be so located
and constructed as to prevent flooding and shall be maintained free
from standing water by means of either a sump pump or a suitable drain.
Such sump pump or drain shall not connect to a sanitary sewer nor
permit flooding of the pit or vault by reverse flow from its point
of discharge. An access ladder and adequate natural or artificial
lighting shall be provided to permit maintenance, inspection and testing
of the backflow prevention device.
[Ord. No. 2021-2324, 3/9/2021]
1. It shall be the duty of the consumer at any premises on which backflow
prevention devices required by this Part are installed to have inspections,
tests and overhaul made in accordance with the following schedule
or more often where inspections indicate a need.
A. Air separation shall be inspected at time of installation and at
least every 12 months thereafter.
B. Double check valve assemblies shall be inspected and tested for tightness
at the time of installation and at least every 12 months thereafter.
(1)
They shall be dismantled, inspected internally, cleaned and
repaired whenever needed at least every 30 months.
C. Reduced pressure zone backflow prevention devices shall be inspected
and tested for tightness at the time of installation and at least
12 months thereafter.
(1)
They shall be dismantled, inspected internally, cleaned and
repaired whenever needed at least every five years.
D. Interchangeable connections shall be inspected at the time of installation
and at least every 12 months thereafter.
2. Inspections, tests and overhaul of backflow prevention devices shall
be made at the expense of the water consumer and shall be performed
by the Borough or a person certified to inspect, test and overhaul
backflow prevention devices and approved as such by the Borough.
3. Whenever backflow prevention devices required by these regulations
are found to be defective, they shall be repaired or replaced at the
expense of the consumer without delay.
4. The water consumer must maintain a complete record of each backflow
prevention device from purchase to retirement. This shall include
a comprehensive listing that includes a record of all tests, inspections
and repairs. Records of inspections, tests, repairs and overhaul shall
be submitted to the Borough.
5. Backflow prevention devices shall not be bypassed, made inoperative,
removed or otherwise made ineffective without specific written authorization
by the Borough.
[Ord. No. 2021-2324, 3/9/2021]
1. Where a booster pump has been installed on the service line to or
within any premises, such pump shall be equipped with an approved
one-way check valve.
2. It shall be the duty of the water consumer to maintain the one-way
check valve in proper working order and to certify to the Borough,
at least once a year, that the device is operating properly.
[Ord. No. 2021-2324, 3/9/2021]
1. The Borough shall deny or discontinue, after reasonable notice to
the occupants thereof the water service to any premises wherein any
backflow prevention device required by this Part is not installed,
tested and maintained in a manner acceptable to the public water supplier
or if it is found that the backflow prevention device has been removed
or bypassed or if any unprotected cross-connection exists on the premises
or if a low pressure cutoff device required by these regulations is
not installed and maintained in working order.
2. Water service to such premises shall not be restored until the consumer
has corrected or eliminated such conditions or defects in conformance
with these regulations and to the satisfaction of the Borough.
3. In addition to or in lieu of the provisions of Subsection
1 above, any person violating any of the provisions or this Part shall be subject for each violation to a penalty of not less than $50 nor more than $1,000 to be imposed and collected in the manner provided by the Borough Code in the case of violations of Borough ordinances.