This article establishes minimum criteria for the installation, use and maintenance of outdoor lighting.
(Ordinance O-04-17 adopted 5/2/17)
The purpose of the lighting standards is to:
(1) 
Preserve and enhance the lawful nighttime use and enjoyment of property;
(2) 
Protect drivers and pedestrians on nearby travel ways from disabling glare from nonvehicular light sources that shine directly into their eyes, thereby, impairing safe travel;
(3) 
Shield neighboring properties from nuisance glare and trespass resulting from improperly directed or unshielded light sources;
(4) 
Prevent and/or lessen light pollution;
(5) 
Promote efficient design and operation with regard to energy conservation; and
(6) 
Curtail the degradation of the nighttime visual environment.
(Ordinance O-04-17 adopted 5/2/17)
The following words, terms and phrases, when used in this article, shall have the meanings ascribed to them in this section, except where the context clearly indicates a different meaning:
Building official.
The chief building official for the City of Glenn Heights, or his or her designee, having responsibility to enforce and administer this article.
Bulb or lamp.
The source of electric light. To be distinguished from the whole assembly, lamp is used to denote the bulb and its housing.
Candela.
The unit of luminous intensity in a given direction. It is commonly called one candlepower.
Cutoff fixture.
A fixture that provides a cutoff (shielding) of the light emitted.
Diffusing luminaire.
One that scatters light substantially in all directions as contrasted with a directional luminaire which confines its light principally in an angle of less than 180 degrees.
Fixture.
The assembly that holds the lamp in a lighting system. It includes the elements designed to give light output control, such as a reflector (mirror) or defractor (lens), the ballast, housing and the attachment parts.
Floodlight.
A luminaire designed to project its light in a well-defined area. It is directional in character.
Floodlight beam.
The angular spread of light between two orthogonal planes each of which equal ten percent of the maximum candlepower within the beam.
Footcandle.
The amount of illumination provided by one lumen uniformly distributed on one square foot of surface.
Footlambert.
The luminance of a surface uniformly emitting, transmitting, or reflecting one lumen per square foot of surface.
Full cutoff fixture.
A fixture that allows no emission above a horizontal plane through the fixture.
Fully shielded.
Light fixtures that are constructed so all light rays emitted by the fixture are projected below the horizontal plane passing through the lowest point on the fixture from which light is emitted, nearly 100 percent cut-off type, as evidenced by the manufacturer’s photometric data.
Glare.
Direct lighting emitted from a luminary that causes reduced vision or temporary blindness.
High pressure sodium (HPS).
A high intensity discharge lamp where radiation is produced from sodium vapor at relatively high partial pressures (100 tore). HPS is essentially point source light.
Horizontal plane.
A line horizontal to the lowest point on the fixture from which light is emitted.
Illumination.
The density of the luminous flux (lumens) incident on a surface. It is the quotient of the luminous flux divided by the area of the surface, expressed in footcandles.
Incandescent lamp.
Any lamp that produces light by heating a filament through use of an electric current.
Installed.
The attachment, or assembly fixed in place, whether or not connected to a power source, or any outdoor light fixture.
Kilowatt (kwh).
A unit of energy equal to the work done by one kilowatt (1,000 watts) of power acting for one hour.
Light source.
A device (such as a lamp) which produces visible energy as distinguished from devices or bodies which reflect or transmit light such as a luminaire.
Light trespass.
Light falling outside the boundary of property for which it was originally intended or needed. Also referred to as spillover light or obtrusive light.
Low pressure sodium (LPS).
A discharge lamp where the light is produced by radiation from sodium vapor at a relatively low partial pressure (about 0.001 tore). LPS is a “tube source” monochromatic light.
Lumen.
The quantity of luminous flux intercepted by a surface of one square foot, all points of which are one foot from a uniform source of one candela. A one-candela source provides 12.57 lumens.
Luminaire.
The device or fixture containing a light source and means for directing and controlling the distribution of light from the source.
Luminance.
The luminous intensity per unit projected area of a given surface viewed from a given direction; for purposes of this article expressed in candelas divided by distance squared.
Mercury lamp.
A high intensity discharge lamp where light is produced by radiation from mercury vapor.
Metal halide lamp.
A high intensity discharge lamp where light is produced by radiation from metal halide vapor.
Outdoor lighting fixture.
An outdoor artificial illumination device, whether permanent or portable, used for illumination outdoors and shall include but not be limited to devices used for search, spot, flood and area lighting for buildings and structures, recreational facilities, parking areas, landscape lighting, outdoor advertising displays, billboards, signs, public and private street lighting and walkway lighting.
Partially shielded.
Shielding so that the lower edge of the shield is at or below the centerline of the light source or lamp so as to minimize light transmission above the horizontal plane, or at least 90 percent of the emitted light projects below the horizontal plane as evidenced by the manufacturer’s photometric data.
Photometric.
Quantitative measurements of light levels and distribution.
Shielding.
A physical structure intended to restrict emitted light.
Substantial change.
Any change to the lamp or bulb that alters the lighting properties of the site, or any change in the type, style or orientation of a light fixture.
(Ordinance O-04-17 adopted 5/2/17)
The lighting standards for the city shall apply to all new construction except as follows:
(1) 
Outdoor lighting that lawfully exists as of the date of this article shall be deemed a lawful use. Any substantial change or addition to the existing lighting system, as determined by the building official, shall comply with the provisions of this article. If a site substantially changes more than 25 percent of the lighting on a site or adds new lighting that increases the number of light fixtures by more than 25 percent, the entire site shall comply with the provisions of this ordinance.
(2) 
Commercial sites approved as part of a site plan prior to the ordinance from which this article is derived shall conform to the provisions in place at that time. Any substantial change or addition to the existing lighting system shall, as determined by the building official, comply with the provisions of this section. If a site substantially changes more than 25 percent of the lighting on a site or adds new lighting that increases the number of light fixtures by more than 25 percent, the entire site shall comply with the provisions of this article.
(3) 
If a use with existing, nonconforming lighting shall cease operation for a period of more than 18 months, then such nonconforming lighting shall be deemed permanently abandoned. The lighting on such site shall be brought into conformance with the provisions of this article prior to the redevelopment or reuse of the site.
(4) 
The following uses shall be exempt from the requirements of this section:
(A) 
Lighting used for single-family homes and accessory buildings, provided no measurable light spills over to the adjacent property;
(B) 
Lighting specifically directed at a flag may be unshielded and unfiltered provided that the beam spread is limited to a narrow spot (approximately seven (7) degrees) and the fixture aperture is concealed by a matrix grid to limit glare;
(C) 
Lighting of baseball fields, softball fields, football fields, soccer fields, golf courses and golf driving ranges, and other similar sporting venues shall be exempt from the height and shielding requirements;
(D) 
Lighting of baseball fields, softball fields, football fields, soccer fields, golf courses and golf driving ranges, and other similar sporting venues, shall be allowed to exceed the maximum illumination level of forty (40) footcandles until 11:00 p.m. No outdoor recreational facility, public or private, shall be illuminated after 11:00 p.m. except to conclude any recreational or sporting event or other activity concluded at a ball park, outdoor amphitheatre, arena, or similar facility in progress prior to 11:00 p.m.;
(E) 
Automobile dealerships are allowed a maximum illumination level of fifty (50) footcandles at display areas until 11:00 p.m.;
(F) 
Lighting necessary for construction or emergencies is exempt from the provisions of this article, provided said lighting is temporary and is discontinued immediately upon completion of the construction work or abatement of the emergency necessitating said lighting;
(G) 
Searchlights require a temporary exemption approval as provided below;
(H) 
Navigation and airport lighting required by the Federal Aviation Administration for operation of airplanes;
(I) 
Lighting installed by a governmental agency for public benefit on public rights-of-way, parks, and public recreation areas;
(J) 
Temporary exemptions to the requirements of this article may be granted by the planning department upon finding that the exemption does not violate any provisions of land use or overlay districts, and it would not pose a hardship on any adjacent property or use. Such requests shall be submitted in writing to the development review committee and include the following:
(i) 
Specific exemption(s) requested;
(ii) 
Type and use of exterior light involved;
(iii) 
Duration of time for requested exemption;
(iv) 
Type of lamp and footcandles;
(v) 
Total wattage of lamp(s); and
(vi) 
Proposed location of exterior light.
(K) 
For street lighting within the public right-of-way, the development review committee may approve an alternate type of lighting not otherwise provided in this article if he or she finds that the proposed design, material or method:
(i) 
Provides approximate equivalence to the specific requirements of this article; or
(ii) 
Is otherwise satisfactory and complies with the intent of this article.
(Ordinance O-04-17 adopted 5/2/17)
(a) 
As part of any site plan application or prior to altering any existing lighting, the applicant shall submit evidence that the proposed work will comply with this article. The submission shall contain, but is not be limited to, the following:
(1) 
Plans indicating the location on the premises, and the type of illuminating devices, fixtures, lamps, supports, reflectors and other devices, and the mounting height of the light;
(2) 
Description of the illuminating devices, fixtures, lamps, supports, reflectors and other devices shall include, but is not limited to, catalog cuts by manufacturers and drawings; and
(3) 
Photometric plans showing illumination levels on the property, at the property line and just beyond the property line, as well as other data such as that furnished by manufacturers or similar data showing the angle of cutoff for light emissions.
(b) 
The required plans, description, and data provided shall be sufficient to enable the plans examiner to readily determine whether compliance with the requirements of this article will be secured.
(Ordinance O-04-17 adopted 5/2/17)
(a) 
Metering equipment.
Lighting levels shall be measured in footcandles with a direct reading, portable light meter. The meter shall read within an accuracy of plus or minus five percent. It shall have been tested and calibrated by an independent commercial photometric laboratory or the manufacturer within one year of the date of use as attested to by a certificate issued by such laboratory.
(b) 
Method of measurement.
The meter sensor shall be mounted or held not more than six inches above ground level in a horizontal position. Readings shall be taken only after the cell has been exposed to provide a constant reading. Measurements shall be made when the National Weather Service indicates visibility is six miles or greater such that measurements will not be adversely affected by atmospheric scatter. Measurements shall be made at least one hour after sunset or one hour prior to sunrise with the existing questioned light sources on, then with the same sources off. The difference between the two readings shall be compared to the limitations stated by this section. This procedure eliminates the effects of moonlight and other ambient light. However, if lighting levels comply with the light sources on then no further reading is needed with the light sources off to demonstrate compliance.
(c) 
Computation of illumination.
Illumination at a point may be computed in lieu of measurement. Computation methods shall consist of an Illumination Engineering Society of North America accepted method, using certified photometric data furnished by the fixture manufacturer, lamp manufacturer, photometric laboratory, or other reliable authority satisfactory to the city. Computations shall be based on new, properly seasoned lamps, new and clean fixtures, and at rated voltage and wattage, with ballasts, lenses, shields, diffusers, and other appurtenances in place, and with proper regard taken for mounting height, relative elevation, natural and man-made objects and industry standard maintenance factors.
(Ordinance O-04-17 adopted 5/2/17)
(a) 
Maximum illumination level for on-site lighting is twenty (20) footcandles as measured at grade, based on light loss factor of sixty-eight percent (0.68) for metal halide lighting and seventy-two percent (0.72) for high pressure sodium lighting.
(b) 
All minimum illumination guidelines listed in this article should be maintained from the ground level to a height of six (6) feet. The minimum to maximum uniformity ratio may range up to 6:1 in acceptable layouts.
(c) 
The lighting levels specified are the minimum levels that are typically acceptable. In some circumstances, customer convenience, closed-circuit television, and customer attraction may require a higher level of lighting. In addition, demographics, the crime index and other factors particular to a certain geographic area may require a higher level of lighting than listed below.
(1) 
High risk activity (4–5 footcandles):
(A) 
ATM.
(B) 
Pay phones.
(C) 
Bus/transit shelters.
(2) 
Medium high risk activity (3–4 footcandles):
(A) 
Convenience stores.
(B) 
Fast food.
(C) 
Pharmacies.
(D) 
Pool halls.
(E) 
Grocery stores (24-hour, immediate parking areas).
(F) 
Establishments licensed for the sale of liquor, beer or wine.
(3) 
Medium risk activities (2–3 footcandles):
(A) 
Gas stations (not convenience stores).
(B) 
Entertainment/amusement.
(C) 
Video stores.
(D) 
Laundries.
(E) 
Banks.
(F) 
Restaurants (no sale of alcohol).
(G) 
Hotels/motels.
(H) 
Video halls.
(I) 
Card/telemarketing.
(J) 
Malls.
(4) 
Medium low risk activity (1–2 footcandles):
(A) 
Multifamily housing.
(B) 
Health care.
(C) 
Industrial (night use).
(D) 
Preschools.
(E) 
Worship.
(F) 
Hospital.
(G) 
General retail.
(H) 
Dental.
(I) 
Warehouse (night use).
(J) 
Educational.
(K) 
Storage.
(L) 
General office (night use).
(M) 
Grocery stores (non24-hour).
(5) 
Low risk activity (.50–1 footcandle):
(A) 
Warehouse (day use).
(B) 
Office (day use only).
(C) 
Greenbelt.
(D) 
Car dealers (after hours).
(E) 
Parks.
(F) 
Industrial (day use).
(G) 
Mini-storage.
(H) 
Retention areas.
(I) 
Walkways in apartment complexes.
(d) 
Limitations on neighboring property.
The limit of illumination on neighboring property from one establishment shall be based on the zoning of the neighboring property. Maximum computed maintained and maximum measured footcandles at the neighboring property lines shall not exceed:
(1) 
Single-family and two-family residential districts: 0.25 footcandles.
(2) 
Multifamily residential districts: 0.5 footcandles.
(3) 
Nonresidential districts (excluding industrial): 3.0 footcandles.
(4) 
Rights-of-way and private streets: 3.0 footcandles.
(5) 
Retail and commercial districts: 4.0 footcandles.
Exception. Illumination at interior property lines on contiguous lots in a multitenant nonresidential development may exceed the above criteria when necessary to provide constant lighting levels of adjoining parking areas, fire lanes and interior access roadways as determined by the director of community development.
(e) 
Limitations on subject property.
The maximum outdoor maintained computed and measured illumination level on the subject property shall not exceed 20 footcandles at any point, with the following exceptions:
(1) 
Lighting under canopies (such as service stations) shall not exceed 30 footcandles. All other lighting on the site shall comply with the provisions of this section; and
(2) 
Lighting for car dealerships shall not exceed 30 footcandles within vehicle display areas.
(f) 
Hours of operation.
(1) 
Lighting used for the illumination of outdoor sales and eating areas, on-site advertising, assembly areas, repair areas, and businesses may be operated during the hours that the facilities are open to the public;
(2) 
Lighting used for the illumination of recreational and sporting areas shall be turned off by 11:00 p.m. on Sunday through Thursday and by 12:00 midnight on Friday and Saturday; and
(3) 
Lighting used for the illumination of walkways, roadways, equipment yards, parking areas and outdoor security may be operated any time.
(a) 
Building mounted light fixtures shall be attached only to walls and the top of the fixture shall not be higher than necessary to illuminate the area required.
(b) 
In any residential zoning district or within fifty (50) feet of any residential zoning district, freestanding light fixtures shall not exceed eighteen (18) feet in height. Within the next [fifty] (50) to one hundred and fifty (150) feet of any residential zoning district, freestanding light fixtures shall not exceed twenty-five (25) feet in height. In all other locations, freestanding light fixtures shall not exceed thirty (30) feet in height.
(c) 
To comply with 1 and 2 [subsections (a) and (b)] above, height shall be measured from the top of a light fixture to the adjacent grade at the base of the support for that light fixture.
(d) 
Light fixture design:
(1) 
All luminaries used for security shall be vandal resistant that resist tampering, incorporate vandal resistant refractors (lens) and shall be provided with a gasket or seal designed to resist rain, dust and insect contamination;
(2) 
Outdoor light fixtures, which are full cutoff to direct all light below a horizontal plane through the bottom of the fixture and have no lens which drops below the fixture may use any illumination source, up to a maximum of forty (40) footcandles;
(3) 
Outdoor light fixtures, which have a lens or diffuser which is visible above the horizontal plane and constructed of white/opal glass, are considered noncutoff and filtered and shall be limited to the light output equal to a one hundred (100) watt incandescent bulb, no greater than one thousand seven hundred (1,700) lumens;
(4) 
Outdoor light fixtures, which have a lens or diffuser which is visible above the horizontal plane and constructed of clear or prismatic glass, are considered noncutoff and nonfiltered and shall be limited to the light output equal to a fifty (50) watt incandescent bulb no greater than six hundred (600) lumens;
(5) 
All conduit must be concealed; and
(6) 
The footcandle level at the property line adjacent to a single-family district (from the proposed lighting) shall not exceed one-quarter (0.25) footcandle. Lighting next to a residential use shall not spill over onto that use.
(e) 
Other conditions related to lighting may be required through development plan review.
(Ordinance O-04-17 adopted 5/2/17)
The following areas on a building or development shall be illuminated to the minimum security lighting levels shown below:
(1) 
All loading areas and docks shall be illuminated from dusk to dawn, with four (4) footcandles of light at finish grade.
(2) 
Carport parking structures shall be illuminated from dusk to dawn, with three (3) footcandles, including the adjacent landscape area to finish grade.
(3) 
Parking structures and parking garages shall be illuminated from dawn to dusk with ten (10) footcandles, and from dusk to dawn with four (4) footcandles. Sublevel parking shall be continuously illuminated twenty-four (24) hours a day with four (4) footcandles at finish grade. Transitional lighting will be required at all entry areas.
(4) 
All stairwells, landings and areas under the lower landing shall be continuously illuminated with five (5) footcandles.
(5) 
Breezeway lighting shall be illuminated from dusk to dawn, with four (4) footcandles. Transitional lighting will be required at all entry areas to the breezeway corridor.
(6) 
Exterior pedestrian pathways and adjacent landscape areas within twenty (20) feet of the pathway shall be illuminated from dusk to dawn, with one-half (0.5) footcandle of light at finish grade. Pedestrian gates shall be illuminated from dusk to dawn, with five (5) footcandles and two (2) footcandles within a fifteen (15) foot radius.
(7) 
Retention areas shall be illuminated from dusk to dawn, with five (5) footcandles of light at finish grade.
(8) 
Cluster or neighborhood mailboxes shall be illuminated from dusk to dawn, with five (5) footcandles of light for a fifteen (15) foot radius of the mailboxes.
(9) 
Parking lots, aisles and refuse areas shall be illuminated from dusk to dawn as follows:
(A) 
Parking spaces for motor vehicles and bicycles shall be illuminated with two (2) footcandles;
(B) 
Parking lot drive aisles shall be illuminated with one (1) footcandle; and
(C) 
Refuse areas shall be illuminated to two (2) footcandles, with gates five (5) footcandles.
(10) 
All building entrances and vehicular gates at operator or locking mechanism shall be illumined with five (5) footcandles at the entrance and two (2) footcandles within a fifteen (15) foot radius from the center point of the entrance.
(11) 
Secondary lighting may be required to supplement the primary security lighting due to design elements and landscaping conflicts, in order to meet the minimum lighting criteria.
(Ordinance O-04-17 adopted 5/2/17)
The purpose of the effective outdoor lighting section is to minimize glare, sky glow, light trespass and excessive energy consumption through the use of appropriate lighting fixtures, practices and systems, while maintaining safety, security and productivity and curtailing degradation of the nighttime visual environment. The following are requirements for effective outdoor lighting:
(1) 
Fully shielded luminaries shall be required in all outdoor lighting installations, with the following exceptions:
(A) 
Outdoor light fixtures used to illuminate flags, statues, or any other objects mounted on a pole, pedestal or platform shall use a very narrow cone of light or shielded lights for the purpose of confining the light to the object of interest and minimize light spillover and glare. Compliance with this provision shall be subject to approval by the building official; and
(B) 
Building facades and architectural features of buildings may be floodlighted when the floodlight fixtures are equipped with shields and are located so as to limit the fixture’s direct light distribution to the facade or feature being illuminated. The configuration of the floodlight installation shall block all view to the floodlight fixture’s lamps from adjacent properties. Compliance with this provision shall be subject to approval by the building official.
(2) 
The following lamp types shall be prohibited for outdoor lighting:
(A) 
Mercury vapor;
(B) 
Bare bulbs above seventy-five (75) watts; and
(C) 
Strings of lamps, except for temporary lighting as provided in section 15.03.004.
(3) 
The quality of the light source shall be a minimum of 65 CRI (color rendering index) as indicated by the lamp manufacturer’s data.
(4) 
Outdoor lighting shall be constructed and installed in a manner consistent with this section and shall be located so as [to] not produce glare or direct illumination across the property line or onto rights-of-way.
(Ordinance O-04-17 adopted 5/2/17)
In both residential, nonresidential districts and all provisional districts (SF-4, MF and MH) lighting is required to be approved with the site plan and designed and constructed to the following standards:
(1) 
Metal standards (poles). The use of fiberglass poles is prohibited.
(2) 
High pressure sodium bulbs (100 watt in residential areas and 250 watt at major intersections).
(3) 
Poles shall be erected a maximum of two hundred feet (200') apart.
(4) 
Streetlights shall be at each intersection and at the intersections (i.e., street intersection and street and alley intersections).
(5) 
A photometric plan must be approved by the city for streetlights and for any other lighting in the project (e.g. park lighting, parking lot lighting), this shall include the streetlight locations, type of pole, the type of head and the size of the bulb (this plan can and should be produced by the utility company).
(6) 
All electrical wiring for street lighting facilities shall also be installed with underground.
(Ordinance O-04-17 adopted 5/2/17)