[R.O. 2009 §6-153; Ord. No. 3971 §7, 3-21-2005; Ord. No. 4553 §9, 6-16-2014; Ord. No. 4899, 10-21-2019; Ord.
No. 4994, 12-6-2021]
A. The International Energy Conservation Code, 2018 Edition, as published by the International Code Council, be and is hereby adopted as the Energy Conservation Code of the City of Brentwood, Missouri, for regulating and governing energy efficient building envelopes and installation of energy efficient mechanical, lighting and power systems as herein provided; providing for the issuance of permits and collection of fees therefore; and each and all of the regulations, provisions, penalties, conditions and terms of said Energy Conservation Code on file in the office of the City Clerk are hereby referred to, adopted, and made a part hereof, as if fully set out in this Section
500.820, with the additions, insertions, deletions and changes prescribed below.
B. The
following Sections are hereby revised to read as follows:
1. Section C101.1. Title. This code shall be known as the Commercial
International Energy Conservation Code of the City of Brentwood and
shall be cited as such.
2. Section C108.4 Failure to comply. Any person who shall continue any work after having been served with a stop work order, except such work as that person is directed to perform to remove a violation or unsafe condition, shall be punishable in accordance with the provisions of Section
100.080 of the Brentwood City Code.
3. Section C108.5. Violation penalties. Any person who violates a provision of this code or fails to comply with any of the requirements thereof or who erects, constructs, alters or repairs a building or structure in violation of the approved construction documents or directive of the Building Official, or of a permit or certificate issued under the provisions of this code, shall be punishable in accordance with the provisions of Section
100.080 of the Brentwood City Code.
4. Section R101.1. Title. This code shall be known as the Residential
International Energy Conservation Code of the City of Brentwood and
shall be cited as such.
5. Section R108.4. Failure to comply. Any person who shall continue any work after having been served with a stop work order, except such work as that person is directed to perform to remove a violation or unsafe condition, shall be punishable in accordance with the provisions of Section
100.080 of the Brentwood City Code.
6. Section R108.5. Violation penalties. Any person who violates a provision of this code or fails to comply with any of the requirements thereof or who erects, constructs, alters or repairs a building or structure in violation of the approved construction documents or directive of the Building Official, or of a permit or certificate issued under the provisions of this code, shall be punishable in accordance with the provisions of Section
100.080 of the Brentwood City Code.
7. Section R202 (pages R-7 thru R-9): Insert the following definitions:
ELECTRIC VEHICLE SUPPLY EQUIPMENT (EVSE)
The conductors, including the ungrounded, grounded and equipment
grounding conductors, and the Electric Vehicle connectors, attachment
plugs, and all other fittings, devices, power outlets, or apparatus
installed specifically for the purpose of transferring energy between
the premises wiring and the Electric Vehicle.
EV CAPABLE SPACE
Electrical panel capacity and space to support a minimum
50-ampere, 208/240-volt dedicated branch circuit for each EV parking
space, and the installation of raceways, both underground and surface
mounted, to support the EVSE.
EV READY SPACE
A designated parking space which is provided with one (1)
50-ampere, 208/240-volt dedicated branch circuit for EVSE servicing
Electric Vehicles. The circuit shall terminate in a suitable termination
point such as a receptacle, junction box, or an EVSE, and be located
in close proximity to the proposed location of the EV parking space.
8. Subsection R404.2 (page R-37) Electric Vehicle (EV) charging for
new construction of single-family and multi-family developments as
defined under Section 604 of the IEBC, except where parking is more
than fifty (50) feet from the main structure is added to read as follows:
SECTION R404.2 Electric Vehicle (EV) charging for new construction.
New construction, as regulated by the International Residential Code,
shall facilitate future installation and use of Electric Vehicle Supply
Equipment (EVSE) in accordance with the National Electrical Code (NEPA
70).
|
SECTION R404.2.1 New one- and two- family dwellings and townhouses.
Each dwelling unit with a dedicated attached or detached parking garage
or on-site parking spaces, shall be provided with at least one (1)
electric vehicle ready space. The branch circuit shall be identified
as "EV Ready" in the service panel or subpanel directory and the termination
location shall be marked as "EV Ready."
|
SECTION R404.2.2 Identification. Construction documents shall
indicate the raceway termination point and proposed location of future
EV spaces and EV chargers. Construction documents shall also provide
information on amperage of future EVSE, raceway methods, wiring schematics
and electrical load calculations to verify that the electrical panel
service capacity and electrical system, including any on-site distribution
transformers, have sufficient capacity to simultaneously charge all
EVs at all required EV spaces at the full rated amperage of the EVSE.
|
SECTION R404.2.3 Multi-family dwellings (three (3) or more dwelling
units). EV Ready Spaces shall be provided in accordance with Table
R404.2.3. Where the calculation of percent served results in a fractional
parking space, it shall be rounded up to the next whole number. The
service panel or subpanel directory shall identify the spaces reserved
to support EV charging as "EV Ready."
|
Table R404.2.3
EV SPACES IN MULTI-FAMILY OCCUPANCIES
|
---|
Total number of parking spaces
|
Minimum number of EV Ready Spaces
|
Minimum number of EVSE Installed Spaces
|
---|
5-20
|
1
|
0
|
21-49
|
2
|
1
|
50+
|
10%*
|
2%*
|
* Percentages shall be rounded up to the next whole number
|