Section 1203 - Emergency and Standby Power Systems.
1203.1.3 Installation. Emergency power systems
and standby power systems shall be installed in accordance with the
International Building Code, NFPA 70, NFPA 110 and NFPA 111.
l. A permit must be obtained from the City of Frontenac prior
to installation.
2. An electrical permit must be obtained from St. Louis County
prior to the installation.
3. Proposed location on the lot must be provided.
4. A copy of the survey of the property is needed so that it
can be determined that the proposed location complies with the following:
a) The local Zoning Ordinance.
b) The local Building and Fire Code; and
c) The manufacturers installation instructions.
5. A copy of the manufacturers installation instructions must
be submitted with the permit application.
6. The generator location is very important to minimize fire
and exhaust gas hazards:
a) All generators shall be at least five (5) feet from combustibles
to all sides including overhead.
b) The generator must be located so that exhaust gases will
not collect adjacent to, enter into or be drawn into an occupied building.
Minimum clearance of ten (10) feet is required from the generator's
exhaust point to any of the home's windows or doors.
c) The unit must be installed level and not where any water
may . accumulate.
d) The unit must not be located where water could flood or spray
the unit. Sump pump discharge area, downspout discharge or similar
issues must be considered.
e) The unit must not be located over buried utility services.
f) The unit must not block access to other utility equipment
such as electric service, telephone equipment, gas meters, etc.