The provisions of this chapter shall specify where fire protection
systems are required and shall apply to the design, installation,
inspection, operation, testing and maintenance of all fire protection
systems. All new fire protection systems or modifications to existing
fire protection systems shall be approved by the Township.
The fire code official shall have the authority to require construction
documents and calculations for all fire protection systems and to
require permits be issued for the installation, rehabilitation or
modification of any fire protection system. Construction documents
for fire protection systems shall be submitted for review and approval
prior to system installation.
Before requesting final approval of the installation, where
required by the fire code official, the installing contractor shall
furnish a written statement to the fire code official that the subject
fire protection system has been installed in accordance with approved
plans and has been tested in accordance with the manufacturer's
specifications and the appropriate installation standard. Any deviations
from the design standards shall be noted and copies of the approvals
for such deviations shall be attached to the written statement.
All fire protection systems shall be installed consistent with
the terms of the Uniform Construction Code in effect in the Township
at the time a building permit application is made and shall be approved
by the fire code official. No new fire protection system shall be
installed, and no existing system shall be modified or replaced, without
a permit from the fire code official.
Fire protection systems shall be maintained in accordance with
the original installation standards for that system. Required systems
shall be extended, altered, or augmented as necessary to maintain
and continue protection whenever the building is altered, remodeled
or added to. Alterations to fire protection systems shall be done
in accordance with applicable standards.
A. Required fire protection systems. Fire protection systems required
by this code or the International Building Code shall be installed,
repaired, operated, tested and maintained in accordance with this
code.
B. Nonrequired fire protection systems. Any fire protection system or
portion thereof not required by this code or the International Building
Code shall be allowed to be furnished for partial or complete protection
provided such installed system meets the requirements of this code
and the International Building Code.
C. Additional fire protection systems. In occupancies of a hazardous
nature, where special hazards exist in addition to the normal hazards
of the occupancy, or where the fire code official determines that
access for fire apparatus is unduly difficult, the fire code official
shall have the authority to require additional safeguards. Such safeguards
include, but shall not be limited to, the following: automatic fire
detection systems, fire alarm systems, automatic fire-extinguishing
systems, standpipe systems, or portable or fixed extinguishers. Fire
protection equipment required under this section shall be installed
in accordance with this code and the applicable referenced standards.
D. Appearance of equipment. Any device that has the physical appearance
of life safety or fire protection equipment but that does not perform
that life safety or fire protection function, shall be prohibited.
Fire detection and alarm systems, fire-extinguishing systems,
fire hydrant systems, fire standpipe systems, fire pump systems, private
fire service mains and all other fire protection systems and appurtenances
thereto shall be subject to acceptance tests as contained in the installation
standards and as approved by the fire code official. The fire code
official shall be notified before any required acceptance testing.
It shall be unlawful to occupy any portion of a building or
structure until the required fire detection, alarm and suppression
systems have been tested and approved.
Fire detection, alarm and extinguishing systems shall be maintained
in an operative condition, at all times, and shall be replaced or
repaired where defective. Nonrequired fire protection systems and
equipment shall be inspected, tested and maintained or removed.
Fire protection systems shall be inspected, tested and maintained
in accordance with the referenced standards listed in the Table of
Fire Protection System Maintenance Standards set forth in Subsection
A below:
A. Table of Fire Protection System Maintenance Standards.
System
|
Standard
|
---|
Portable fire extinguishers
|
NFPA 10
|
Carbon dioxide fire-extinguishing system
|
NFPA 12
|
Halon 1301 fire-extinguishing systems
|
NFPA 12A
|
Dry-chemical extinguishing systems
|
NFPA 17
|
Wet-chemical extinguishing systems
|
NFPA 17A
|
Water-based fire protection systems
|
NFPA 25
|
Fire alarm systems
|
NFPA 72
|
Water-mist systems
|
NFPA 750
|
Clean-agent extinguishing systems
|
NFPA 2001
|
B. Records. Records of all system inspections, tests and maintenance
required by the referenced standards shall be maintained on the premises
for a minimum of three years and shall be copied to the fire code
official upon request.
C. Records information. Initial records shall include the name of the
installation contractor, type of components installed, manufacturer
of the components, location and number of components installed per
floor. Records shall also include the manufacturers' operation
and maintenance instruction manuals. Such records shall be maintained
on the premises.
Where a required fire protection system is out of service, the
fire department and the fire code official shall be notified immediately
and, where required by the fire code official, the building shall
either be evacuated or an approved fire watch shall be provided for
all occupants left unprotected by the shutdown until the fire protection
system has been returned to service. Where required and/or utilized,
fire watches shall be provided with at least one approved means for
notification of the fire department and their only duty shall be to
perform constant patrols of the protected premises and keep watch
for fires.
A. Impairment coordinator. The building owner shall assign an impairment
coordinator to comply with the requirements of this section. In the
absence of a specific designee, the owner shall be considered the
impairment coordinator.
B. Tag required. A tag shall be used to indicate that a system, or portion
thereof, has been removed from service.
C. Placement of tag. The tag shall be posted at each fire department
connection, system control valve, fire alarm control unit, fire alarm
annunciator and fire command center, indicating which system, or part
thereof, has been removed from service. The fire code official shall
specify where the tag is to be placed.
D. Preplanned impairment programs. Preplanned impairments shall be authorized
by the impairment coordinator. Before authorization is given, a designated
individual shall be responsible for verifying that all of the following
procedures have been implemented:
(1) The extent and expected duration of the impairment have been determined.
(2) The areas or buildings involved have been inspected and the increased
risks determined.
(3) Recommendations have been submitted to management or building owner/manager.
(4) The fire department has been notified.
(5) The insurance carrier, the alarm company, building owner/manager,
and other authorities have jurisdiction have been notified.
(6) The supervisors in the area to be affected have been notified.
(7) A tag impairment system has been implemented.
(8) Necessary tools and materials have been assembled on the impairment
site.
E. Emergency impairments. When unplanned impairments occur, appropriate emergency action shall be taken to minimize potential injury and damage. The impairment coordinator shall implement the steps outlined in §
53-56D.
F. Restoring systems to service. When impaired equipment is restored
to normal working order, the impairment coordinator shall verify that
all of the following procedures have been implemented:
(1) Necessary inspections and tests have been conducted to verify that
affected systems are operational.
(2) Supervisors have been advised that protection is restored.
(3) The fire department has been advised that protection is restored.
(4) The building owner/manager, insurance carrier, alarm company and
other involved parties have been advised that protection is restored.
(5) The impairment tag has been removed.
It shall be unlawful for any person to remove, tamper with or
otherwise disturb any fire hydrant, fire detection and alarm system,
fire suppression system, or other fire appliance required by this
code except for the purpose of extinguishing fire, training purposes,
recharging or making necessary repairs, or when approved by the fire
code official.
A. Removal of or tampering with appurtenances. Locks, gates, doors,
barricades, chains, enclosures, signs, tags or seals which have been
installed by or at the direction of the fire code official shall not
be removed, unlocked, destroyed, tampered with or otherwise vandalized
in any manner.
Any fire protection system component regulated by this code
that is the subject of a voluntary or mandatory recall under federal
law shall be replaced with approved, listed components in compliance
with the referenced standards of this code. The fire code official
shall be notified, in writing, by the building owner when the recalled
component parts have been replaced.
Fire hose threads and fittings used in connection with automatic
sprinkler systems shall be as prescribed by the fire code official.
The location of fire department connections shall be approved
by the fire code official.
Class I standpipe hose connections shall be provided in all
of the following locations:
A. In every required stairway, a hose connection shall be provided for
each floor level above or below grade. Hose connections shall be located
at an intermediate floor level landing between floors, unless otherwise
approved by the fire code official.
B. On each side of the wall adjacent to the exit opening of a horizontal
exit; provided, however, that where floor areas adjacent to a horizontal
exit are reachable from exit stairway hose connections by a thirty-foot
(9,144 mm) hose steam from a nozzle attached to 100 feet (30,480 mm)
of hose, a hose connection shall not be required at the horizontal
exit.
C. In every exit passageway, at the entrance from the exit passageway
to other areas of a building.
D. In covered mall buildings, adjacent to each exterior public entrance
to the mall and adjacent to each entrance from an exit passageway
or exit corridor to the mall.
E. Where the roof has a slope less than four units vertical in 12 units
horizontal (33.3% slope), each standpipe shall be provided with a
hose connection located either on the roof or at the highest landing
of a stairway with stair access to the roof. An additional hose connection
shall be provided at the top of the most hydraulically remote standpipe
for testing purposes.
F. Where the most remote portion of a nonsprinklered floor or story
is more than 150 feet (45,720 mm) from a hose connection or the most
remote portion of a sprinklered floor or story is more than 200 feet
(60,960 mm) from a hose connection, the fire code official is authorized
to require that additional hose connections be provided in approved
locations.
Risers and laterals of Class I standpipe systems not located
within an enclosed stairway or pressurized enclosure shall be protected
by a degree of fire resistance equal to that required for vertical
enclosures in the building in which they are located; provided, however,
that in buildings equipped throughout with an approved automatic sprinkler
system, laterals that are not located within an enclosed stairway
or pressurized enclosure are not required to be enclosed within fire-resistance-rated
construction.
In buildings where more than one standpipe is provided, the
standpipes shall be interconnected in accordance with NFPA 14.