[Amended 4-7-1976 by L.L. No. 2-1976; 6-22-1982 by L.L. No.
9-1982; 12-31-1996 by L.L. No. 18-1996]
A. The Chief Fire Safety Inspector, Fire Safety Inspector or Assistant Fire Safety Inspectors shall survey each commercial, industrial, business, mercantile, storage, institutional or educational establishment, multiple dwelling or any other structure and shall specify suitable fire-detecting devices and extinguishing appliances and other fire safety devices which shall be provided. Such devices or appliances may consist of automatic fire alarm systems, automatic sprinklers or water-spray systems, standpipes and hoses, fixed or portable fire extinguishers of a type suitable for the likely probable class of fire, exit lights, emergency lighting units or panic hardware. For special storage or hazardous processes, appliances of more than one type or special systems may be required. Automatic fire alarm and sprinkler systems shall be as defined in §
143-13. The fire prevention chart is located at the end of this chapter.
[Amended 3-16-2010 by L.L. No. 1-2010]
A.1.
|
Strobe lights.
|
|
(1)
|
In order to notify responding firefighters of
conditions within a building or structure equipped with sprinkler
system, fire alarm system or containing hazardous materials or other
hazards to firefighters, identification strobe lights shall be installed
on the exterior of the building as follows:
|
|
|
(a)
|
Red strobe light: located above the fire department
siamese connection of a sprinkled building to indicate activation
of the water flow alarm.
|
|
|
(b)
|
Yellow strobe light: installed to indicate activation
of a pull station, smoke detector, heat detector or other alarm device.
|
|
|
(c)
|
Blue strobe light: installed to indicate the
presence of hazardous materials, conditions or other danger to firefighters.
|
|
(2)
|
The exact location of these lights shall be
determined by the Chief Fire Safety Inspector. Said strobes shall
be labeled with signs hung directly below the strobe identifying the
strobe, i.e., for red strobe, signed to read "Water Flow Alarm"; for
yellow strobe, signed to read "Fire Alarm"; and for blue strobe, signed
to read "Hazards."
|
B. Every application for a building permit for the construction,
reconstruction, addition, alteration or change in use of any building
or structure shall meet the fire and safety requirements of the chart
shown below, as well as any additional requirements deemed necessary
for the safety of persons and property by the Chief Fire Safety Inspector,
Fire Safety Inspector or Assistant Fire Safety Inspectors, and said
requirements shall be made a condition of the permit.
[Amended 6-22-1982 by L.L. No. 9-1982]
A. Sprinkler systems, standpipe systems, fire-detection
systems and other fire-protective or extinguishing systems and other
fire safety devices which have been installed as a requirement of
a building permit, order or because of any law or ordinance shall
be maintained in operative conditions at all times. It shall be unlawful
for any owner or occupant to reduce the effectiveness of the protection
so required, except that this shall not prohibit the owner or occupant
from temporarily reducing or discontinuing the protection, where necessary,
to make tests, repairs, alterations or additions. The Chief Fire Safety
Inspector shall be notified before such tests, repairs, alterations
or additions are commenced if the work is not to be completed within
a twenty-four-hour period.
[Amended 12-31-1996 by L.L. No. 18-1996; 3-16-2010 by L.L. No. 1-2010]
B. In order to ensure fire protection devices will operate
properly when and if required, routine inspections, tests and maintenance
is required. These inspections, tests and maintenance shall be performed
by a qualified individual and in accordance with NFPA or other applicable
standards and codes or as and when required by the Chief Fire Safety
Inspector. Whenever inspection, tests and maintenance is done, a written
report on a form approved by the Chief Fire Safety Inspector shall
be submitted to the Chief Fire Safety Inspector's office within five
days.
[Amended 9-25-1990 by L.L. No. 4-1990; 12-31-1996 by L.L. No.
18-1996; 3-16-2010 by L.L. No. 1-2010]
(1) Sprinkler systems.
(a)
Sprinkler systems shall be maintained in operative
condition, free from mechanical injury, structure failure, water failure
or obstructions. Sprinklers shall be maintained clean and free from
corrosion, paint, whitewash and other coatings which impair their
operation. Sprinkler systems shall be inspected and tested in accordance
with the National Fire Protection Association Standard for the inspection,
testing and maintenance of Water Based Fire Protection Systems (NFPA
25), but not less than on a semiannual basis.
(b)
Valves controlling water supply to sprinklers
shall be readily accessible at all times and shall be free of any
obstructions.
(c)
Supports for piping and equipment shall be structurally
sound.
(d)
Portions of the system subject to freezing shall
be appropriately protected.
(e)
Storage of materials shall not interfere with
the effective discharge of water from the sprinklers.
(f)
Riser flow tests shall be made quarterly from
water supply test pipes.
(g)
Control valves.
[1]
Each valve shall be numbered and shall have
a sign indicating the portion of the system it controls.
[2]
Each control valve shall be secured in its open
position using a lock or tamper switch.
[3]
Valves locked in the open position and valves
with tamper switches shall be inspected monthly.
[4]
Valve stems shall be lubricated at least once
a year using manufacturer's approved lubricant.
[5]
Post indicator valves shall be operated quarterly
to assure proper operation and shall be left in a locked open position.
(h)
Fire Department connections shall be inspected
monthly.
(i)
Gauges shall be checked monthly to assure normal
pressure is being maintained. Gauges shall be checked with an inspector's
gauge every five years.
(j)
Water flow alarm devices shall be tested quarterly.
(k)
Sprinkler systems shall be flushed every five
years to assure that sprinklers receive an unobstructed flow of water.
Flushing shall include mains, risers, feed mains, cross mains and
branch lines and shall be done as per National Fire Protection Association
requirements.
(l)
Security personnel shall be notified, in writing,
of:
[1]
The location and use of control valves, drain
valves and alarm devices.
[2]
The requirement to promptly transmit a fire
alarm to the Fire Department.
[3]
The requirement for daily visual inspection
of sprinkler control valves to ascertain that they are open. Proper
notification shall be made of any valve found closed.
(m)
Valve inspection reports shall show that the
valves are:
[1]
In normally open or closed position.
[2]
Properly sealed, locked or equipped with a tamper
switch.
[3]
In good operating condition.
[4]
Provided with a wrench, where required.
(n)
The Chief Fire Safety Inspector shall be notified:
[1]
Of the installation or modification to a system.
[2]
Of the extent of protection provided and the
location and arrangement of control valves and connections for Fire
Department use.
[3]
When any portion of the system is taken out
of service.
(o)
Records shall be kept of all inspections, tests
and maintenance functions relating to sprinkler systems. Copies of
all service, repair, inspection and testing reports shall be forwarded
to the Chief Fire Safety Inspector's office on an approved form within
10 days of such service, repair, inspection or testing. See other
requirement of § 143-38C.
(2) Standpipe systems.
(a)
Valves shall be maintained tight against leaks.
(b)
Hoses shall be properly stored, ready for operation,
dry and free of deterioration.
(c)
Hose stations shall be conspicuously identified,
located for easy accessibility and installed to provide for the quick
and easy use of equipment.
(d)
Valves in the water supply pipe for the standpipe
system, other than hose station valves, shall be open and readily
accessible at all times and shall be free of any obstructions.
(3) Fire pumps.
(a)
Suction pipes, intakes and screens shall be
examined semiannually to assure that they are free from any obstruction.
(b)
The pump room shall be maintained at a temperature
above 40° F.
(c)
Oil in internal-combustion-engine-driven pumps
shall be changed not less than once a year.
(d)
Storage batteries shall be checked weekly to
determine battery condition and the amount of charge in the battery.
(e)
Fuel storage tanks shall be kept full at all
times.
(f)
Pumps shall be operated weekly at rated speed
to determine satisfactory condition of pumps and control equipment.
Electric-motor-driven pumps shall be tested monthly.
(g)
A flow test shall be performed at least semiannually
to assure that the pumps are operating properly and that there are
no obstructions in pumps or suction pipes.
(4) Yard hydrant systems.
(a)
Connection to hydrants on the distribution system
for other than fire-protection purposes shall be prohibited unless
authorized by the Chief Fire Safety Inspector.
(b)
Hydrants shall be readily accessible at all
times and shall be free of any obstructions, including but not limited
to fencing, vehicles, snow and ice, etc.
(c)
All hydrants shall be inspected and tested at
least annually to assure the proper operation thereof.
(d)
Yard hydrant systems employing outside fire
hoses shall have said hoses properly stored so as to be readily accessible
and protected from the weather.
(e)
Underground gate valves with roadway boxes shall
be operated quarterly to verify the open position.
(5) In order to ensure that firefighters utilize the proper
siamese connection, all siamese connections and/or the protective
covers installed on the siamese connection shall be color coded as
follows:
RED
Siamese supplying a standpipe (fire hose) system.
GREEN
Siamese supplying a sprinkler system.
YELLOW
Siamese supplying a combination standpipe and sprinkler system.
C. Fire alarm systems.
(1) Heat, smoke, flame detectors, water flow devices and
similar devices shall be maintained in a proper operating condition
at all times. Such systems shall be inspected and tested for proper
operation at least quarterly. Such inspections shall include all items
as specified by the Chief Fire Safety Inspector.
[Amended 12-31-1996 by L.L. No. 18-1996; 3-16-2010 by L.L. No. 1-2010]
(2) False alarms.
[Amended 6-19-2007 by L.L. No. 10-2007]
(a)
A "false alarm" is the dispatching of the Fire
Department to a condition that is unnecessary because there is no
fire or smoke and which is determined by the Fire Department officer
in charge to not be a good-intent call. The activation of an alarm
system through mechanical failure, malfunction, improper installation
or the negligence of the owner or alarm user shall also constitute
a false alarm.
(b)
The Chief Fire Safety Inspector or his designee(s)
shall investigate written reports of each alleged false alarm submitted
by the Fire Departments within the Town of Clarkstown. Notice of said
written report alleging violation shall be given to the alarm user
after the second false alarm.
(c)
A third or additional false alarms reported to the Chief Fire Safety Inspector's office within a calendar year are violations of this chapter and subject to penalties as provided in §
143-6 of this chapter.
[Amended 3-16-2010 by L.L. No. 1-2010]
(d) A false alarm caused by the failure of a person, firm or corporation to properly put a fire alarm system out of service while making repairs, tests, inspections or other maintenance is a violation of this chapter and subject to penalties as provided in §
143-6 of this chapter.
[Amended 3-16-2010 by L.L. No. 1-2010]
(3) Required equipment.
[Added 12-31-1996 by L.L. No. 18-1996]
(a)
Fire alarm or fire detection systems shall have
an annunciator or remote, located at or near the main entrance of
the building. Such annunciator shall show the location and type of
alarm. A floor plan of the protected premises shall also be provided
at this location. The location of any annunciator or panel not clearly
visible upon entry of the main entrance of a building shall be marked
with a sign.
(b)
Upon activation of a alarm the person in charge
of a premises shall cause the premises to be evacuated unless an evacuation
plan preapproved by the Chief Fire Safety Inspector and fire department
is in place. In such case the provisions of the plan shall be followed.
(c)
No fire system shall be reset from an alarm
condition unless approved by the Chief Fire Safety Inspector or fire
department officer-in-charge. A sign stating such shall be provided
on all fire alarm panels.
(d)
The owner or responsible party of any premises
containing a fire alarm or fire detection system shall ensure that
a qualified technician is available to respond with two hours of notification
to initiate needed repair or service of the system.
(e)
If the fire alarm system signal transmission
is not tested on a daily basis to 44-Control, all dedicated phone
lines used for the purpose of transmitting fire alarm signals shall
be equipped with a visual/audio signal to operate in the event of
a line failure or disablement. It shall be the sole responsibility
of the property owner to maintain all fire alarm system phone lines
active at all times.
(f)
A red name plate with one-inch white letters
shall be located below the visual/audio signal with the following
information:
[2]
Telephone number of alarm company.
D. Commercial cooking appliances.
[Added 12-31-1996 by L.L. No. 18-1996 ]
(1) All commercial cooking appliances producing grease-laden
smoke shall be required to have an approved exhaust removal system
with related duct work; all to be protected by an approved automatic
fire suppression system installed and maintained in compliance with
current applicable National Fire Protection Association standards.
(2) These systems shall be inspected by an approved service
firm on a semiannual basis. To ensure proper inspection, a uniform
inspection form, provided by the Chief Fire Safety Inspector, shall
be utilized with a copy of the completed form forwarded to the Chief
Fire Safety Inspector within 10 days of the inspection.
E. Elevators, escalators and dumbwaiters.
[Added 3-16-2010 by L.L. No. 1-2010]
(1) General. Elevators, escalators and dumbwaiters shall be maintained
to safely sustain all imposed loads, to operate properly and to be
free from physical and fire hazards. The most current certificate
of inspection shall be on display at all times within the elevator
or attached to the escalator or dumbwaiter or available for inspection
in the office of the building operator.
(a)
Elevators, dumbwaiters, escalators and platform lifts shall
be maintained and meet the schedule of inspections in accordance with
the Building Code of New York State, Section 3001, and Appendix N,
Table-1 of ASME A17.1 and ASME A18.1.
(2) Elevators. In buildings equipped with passenger elevators, at least
one elevator shall be maintained in operation at all times when the
building is occupied. Exception: Buildings equipped with only one
elevator shall be permitted to have the elevator temporarily out of
service for testing or servicing.
F. Emergency and standby power systems.
[Added 3-16-2010 by L.L. No. 1-2010]
(1) Maintenance. Emergency and standby power systems shall be maintained
such that the system is capable of supplying service within the time
specified for the type of duration required.
(2) Inspections. Inspection, testing and maintenance of emergency standby
power systems shall include the date of service, name of the servicing
technician, a summary of conditions noted and a detailed description
of any conditions requiring correction and what corrective action
was taken. Such records shall be kept on the premises served by the
emergency or standby power system and be available for inspection
by the Code Enforcement Official.
(3) Switch maintenance. Emergency and standby power system transfer switches
shall be included in the inspection, testing and maintenance. Transfer
switches shall be maintained free from accumulated dust and dirt.
Inspection shall include examination of the transfer switch contacts
for evidence of deterioration. When evidence of contact deterioration
is detected, the contacts shall be replaced in accordance with the
transfer switch manufacturer's instructions.
(4) Operational inspection and testing. Emergency power systems, including
all appurtenant components, shall be inspected and tested under load
at least annually.
(5) Transfer switch test. The test of the transfer switch shall consist
of electrically operating the transfer switch from the normal position
to the alternate position and then back to the normal position.
(6) Supervision of maintenance and testing. Routine maintenance, inspection
and operational testing shall be overseen by a properly instructed
individual.
G. Whenever such tests, repairs, alterations or maintenance inspections
are made, a written report in a form specified by the Chief Fire Safety
Inspector shall be forwarded to the Building Department by the person,
firm or corporation making said tests, repairs, alterations, inspections
or additions.
[Amended 12-31-1996 by L.L. No. 18-1996; 3-16-2010 by L.L. No. 1-2010]