A licensed plumber will lay the service pipe
from the main to the structure being served. All hookups between the
main up to and including the structure will be made by a licensed
plumber. The property owner shall be responsible for maintenance of
the water service line from the main up to the structure being served.
A.
Service pipe from the City's main to the meter shall
be laid at least four feet below the surface of the ground at all
points and shall be backfilled with suitable materials as determined
by the Water Superintendent and/or Highway Superintendent. The service
pipe shall conform to such standards and shall be of such make and
type as the Water Superintendent shall direct and shall be of such
size as the City shall deem proper. The minimum size for any service
hereafter installed shall, however, be 3/4 inch.
B.
Service pipes from the curb box to the meter, less
than two inches in diameter, shall be of pure, seamless, soft-tempered
copper tubing with flared or compression red brass or bronzed fittings.
C.
Tubing shall be of the following thickness:
Normal Pipe Size
(inches)
|
Outside Diameter of Tubing
(inches)
|
Type
| |
---|---|---|---|
3/4
|
7/8
|
K
| |
1
|
1 1/8
|
K
| |
1 1/4
|
1 3/8
|
K
| |
1 1/2
|
1 5/8
|
K
|
D.
No soldered joints shall be permitted in copper tubing
underground.
No tee or other fitting through which water
can be taken will be permitted on the service pipe between the main
and the meter.
Outdoor meter pits may be installed in special
cases on written approval of the City. Such meter pits must be installed
in accordance with City specifications and at the expense of the property
owner.
[Amended 12-5-2016 by L.L. No. 17-2016]
No branch will be allowed to be inserted in any service pipe
without a written permit from the City. Where branches already exist
and are not provided with curb boxes, in case of default in payment
of water rent by any one property owner or consumer, the main service
may be cut off until the back charges are paid. The City shall not
be liable for damages to any other property owner or consumer who
may thus be deprived of water. Backflow preventers (check valves)
must be installed on all installations. The City reserves the right
to set a time limit for the removal of any branch lines so that, upon
reasonable notice of the imposition of said time limit, each dwelling
so affected shall install a separate service line at the property
owner's or consumer's expense.
[Amended 9-18-2017 by L.L. No. 10-2017]
A.
The intent of this article is to:
(1)
Protect the public water supply served by the City of Beacon Water
and Sewer Department from the possibility of contamination or pollution
which could backflow or back-siphon into the public water system.
(2)
Promote the elimination or control of existing cross-connections,
actual or potential, between its customer's potable water system and
nonpotable systems.
(3)
Provide for the maintenance of a continuing program of cross-connection
control which will effectively prevent the contamination or pollution
of all potable water systems by cross-connection.
B.
Authority. Pursuant to the Federal Safe Drinking Water Act of 1974[1] and statutes promulgated in Article 2 of the Public Health Law and in Part 5, Section 5-1.31, of the State Sanitary Code (10 NYCRR Part 5), the New York State Department of Health (NYSDOH) has undertaken a program for preventing water from unapproved sources from entering the public potable water system. Subpart 5-1 of the State Sanitary Code, Section 5-1.32, requires that the supplier of all public water shall protect the public water system by containing potential contamination within the premises of each individual water user.
[1]
Editor's Note: See 42 U.S.C. § 300f et seq.
C.
AIR GAP
APPROVED
ATMOSPHERIC VACUUM BREAKER
AUXILIARY WATER SUPPLY
BACK PRESSURE
BACK-SIPHON
BACKFLOW
BACKFLOW PREVENTION DEVICE
BAROMETRIC LOOP
CONTAINMENT
CONTAMINANT
CROSS-CONNECTION
DEPARTMENT
DEPARTMENT OF HEALTH
DOUBLE CHECK VALVE ASSEMBLY (DCV)
DOUBLE CHECK VALVE WITH INTERMEDIATE ATMOSPHERIC VENT
DWELLING UNIT
DWELLING, ONE-FAMILY
DWELLING, TWO-FAMILY
FIXTURE ISOLATION
HOSE BIBB VACUUM BREAKER
OWNER
PERSON
POLLUTANT
PRESSURE VACUUM BREAKER
REDUCED-PRESSURE-PRINCIPLE BACKFLOW PREVENTER (RPZ)
WATER SERVICE ENTRANCE
WATER, NONPOTABLE
WATER, POTABLE
Definitions. As used in this section, the following terms shall have
the meanings indicated:
A physical separation sufficient to prevent backflow between
the free-flowing discharge end of the potable water system and any
other system; physically defined as a distance equal to twice the
diameter of the supply side pipe diameter but never less than one
inch.
Accepted by the New York State Department of Health, Dutchess
County Department of Health and City of Beacon Water and Sewer Department
meeting applicable specifications stated or cited in this regulation,
or as suitable for the proposed use.
A device which prevents backsiphonage by creating an atmospheric
vent when there is either a negative pressure or subatmospheric pressure
in a water system.
Any water supply on or available to the premises other than
the surveyor's approved public potable water supply.
A condition in which the owner's system pressure is greater
than the supplier's system pressure.
The flow of water or other liquids, mixtures or substances
into the distribution pipes of a potable water supply system from
any source other than its intended source, caused by a sudden reduction
of pressure in the potable water supply system.
The flow of water or other liquids, mixtures or substances
and/or positive or reduced pressure in the distribution pipes of a
potable water supply from any source other than its intended source.
A device or means designed to prevent backflow or backsiphonage.
Most commonly categorized as air gap, reduced pressure principle device,
double check valve assembly, pressure vacuum breaker, atmospheric
vacuum breaker, hose bibb vacuum breaker, residential dual check,
double check with intermediate atmospheric vent, and barometric loop.
A fabricated piping arrangement rising at least 35 feet at
its topmost point above the highest fixture it supplies. It is utilized
in water supply systems to protect against backsiphonage.
A method of backflow prevention which requires a backflow
prevention device at the water service entrance immediately after
the water meter or, in the event of no meter, immediately after the
point of entry.
Any physical, chemical, microbiological or radiological substance
or matter in water.
Any actual or potential connection between the public water
supply and a source of contamination or pollution.
The City of Beacon Water and Sewer Department.
The State of New York Health Department and its agent, the
Dutchess County Department of Health.
An assembly of two independently operating spring-loaded
check valves with tightly closing shutoff valves on each side of the
check valves, plus properly located test cocks for the testing of
each check valve.
A device having two spring-loaded check valves separated
by an atmospheric vent chamber.
One or more rooms with provision for living, cooking, sanitary
and sleeping facilities arranged for the use of one family.
A building containing not more than one dwelling unit occupied
exclusively for residential purposes by one family.
A building containing not more than two dwelling units occupied
exclusively for residential purposes by two families living independently
of each other.
A method of backflow prevention in which a backflow prevention
device is located to correct a cross-connection at an in-plant location
rather than at a water service entrance.
A device which is permanently attached to a hose bibb and
which acts as an atmospheric vacuum breaker.
Any person who has a legal title to, or license to operate
or habitat in, a property upon which a cross-connection is present.
Any individual, partnership, company, public or private corporation,
political subdivision or agency of the State Department, agency or
instrumentality of the United States or any other legal entity.
A foreign substance that, if permitted to get into the public
water system, will degrade its quality so as to constitute a moderate
hazard or impair the usefulness or quality of the water to a degree
which does not create an actual hazard to the public health but which
does adversely and unreasonably affect such water for domestic use.
A device containing one or two independently operated spring-loaded
check valves and an independently operated spring-loaded air inlet
valve located on the discharge side of the check or checks. Such device
includes tightly closing shutoff valves on each side of the check
valves and properly located test cocks for the testing of the check
valves.
An assembly consisting of two independently operating approved
check valves with an automatically operating differential relief valve
located between two check valves, tightly closing shutoff valves on
each side of the check valves, plus properly located test cocks for
the testing of the check valves and the relief valve.
The point in the owner's water system beyond the sanitary
control of the City; generally considered on the outlet end of the
water meter and always before any unprotected branch.
Water that is not safe for human consumption or that is of
questionable potability.
Water free from impurities in amounts sufficient to cause
disease or harmful physiological effects.
D.
Enforcement. The Water Superintendent and/or City Engineer or his
or her designee shall enforce this article and the cross-connection
and backflow protection requirements, specifications, guidelines and
facilities classifications of the NYSDOH and the Dutchess County Department
of Health (DCDOH). Specifications, guidelines, facilities, classifications
and other administrative requirements and information which shall
be used to implement the requirements shall be on file in the Department
and available for review.
E.
Administration.
(1)
The Department will operate a cross-connection control program to
include the keeping of necessary records, which fulfills the requirements
of the NYSDOH's cross-connection regulations and testing of backflow
prevention equipment.
(2)
The owners shall allow their property to be inspected for possible
cross-connections and shall follow the provisions the Department's
cross-connection control program as set forth by the City of Beacon.
(3)
If the Department requires that the public supply be protected by
containment, the owners shall be responsible for water quality beyond
the outlet end of the containment device and should utilize fixture
outlet protection for that purpose.
F.
Responsibilities.
(1)
Department.
(a)
The Department will not allow any cross-connection to remain
unless it is protected by an approved backflow prevention device,
which will be regularly tested to insure satisfactory operation. If,
in the judgment of the City, an approved backflow prevention device
is required for existing installations, the City shall give notice
in writing to said owner to install an approved backflow prevention
device at each service connection to said premises. Hazardous conditions
shall be addressed immediately. On new installations, the Department
will provide on-site evaluation and/or review of plans in order to
determine the type of backflow prevention device, if any, that will
be required. Plans shall be signed and sealed by a currently licensed
New York State professional engineer.
(b)
For premises existing prior to the start of this program, the
Department will perform evaluations and review of plans and/or inspection
of premises and inform the owner by letter of any corrective action
deemed necessary, the method of achieving the correction and the time
allowed for the correction to be made. Ordinarily, 90 days will be
allowed; however, this time period may be shortened by the Department
depending upon the degree of hazard involved and the history of the
device(s) in question.
(c)
The Department shall inform the owners, by letter, of any failure
to comply by the time of the first reinspection. The Department will
allow an additional 15 days for the correction. In the event that
the owners fail to comply with the necessary correction by the time
of the second reinspection, the Department will inform the owners,
by letter, that the water service to the owners' premises will be
terminated within a period not to exceed five days. In the event that
the owners inform the Department of extenuating circumstances as to
why the correction has not been made, a time extension may be granted
by the Department but in no case will exceed an additional 30 days.
(d)
If the Department determines at any time that a serious threat
to the public health exists, the water service will be terminated
immediately. If the Department determines that terminating water service
is not feasible, the owner will be subject to fines listed in another
section of this chapter.
(e)
The Department shall have on file a list of private contractors
who are certified backflow device testers. The owner is responsible
for all costs associated with the installation and testing of any
backflow prevention device.
(f)
The Department will begin initial premises inspections to determine
the nature of existing or potential hazards following the approval
of this program by the City Council of the City of Beacon. Initial
focus will be on high-hazard industries and commercial premises.
(2)
Owners.
(a)
The owners shall be responsible for the elimination or protection
of all cross-connections on their premises.
(b)
The owners, after having been informed by a letter from the
Department, shall at their expense install, maintain, and test, or
have tested, any and all backflow prevention devices on their premises.
The owners shall be responsible for all costs associated with the
installation and testing of backflow prevention devices.
(c)
After the Department determines the type of backflow prevention
device, if any, required and approves the backflow prevention device,
the owner shall submit an application to the NYSDOH to obtain a permit
to construct the approved backflow prevention device. The work shall
be completed within 90 days from receipt of the permit. Failure or
refusal or inability on the part of the owner to install said device
within 90 days shall constitute grounds for discontinuing water service
until such device has been properly installed.
(d)
After completion of installation of the backflow prevention
device, the owner shall apply for a completed works permit by submitting
to the NYSDOH a certification from an engineer which states that the
installation of the work is in compliance with the approved plans
and certification from an approved tester of backflow prevention devices,
that the installation was tested and is working as designed and approved
and in accordance with the intent of these regulations.
(e)
The owner shall submit to the City of Beacon Water and Sewer
Department and Building Department all certifications submitted to
the NYSDOH, including the certification that the installation of the
approved backflow prevention device is in compliance with the approved
plans and the certification that the installation was tested and is
working as designed.
(f)
The owners shall correct any malfunction of the backflow prevention
device which is revealed by periodic testing.
(g)
The owners shall inform the Department of any proposed or modified
cross-connections of which the owners are aware but have not been
found by the Department.
(h)
The owners shall not install a bypass around any backflow prevention
device unless there is a backflow prevention device of the same type
on the bypass. Owners who cannot shut down operation for testing of
the device(s) must supply additional devices necessary to allow testing
to take place.
(i)
The owners shall install only backflow prevention devices which
are shown on an NYSDOH list of approved backflow prevention devices.
(j)
Any owners having a private well or other private water source
must obtain approval from the Department if the well or source is
cross-connected to the Department's system. Permission to cross-connect
may be denied by the Department. The owner may be required to install
a backflow prevention device at the service entrance if a private
water source is maintained, even if it is not cross-connected to the
Department's system.
(k)
In the event that the owners install plumbing to provide potable
water for domestic purposes which is on the Department's side of the
backflow prevention device, such plumbing must have its own backflow
prevention device installed.
(l)
The owners shall be responsible for the payment of all permit
fees, penalties, annual or semiannual device testing, retesting in
the case that the device fails to operate correctly, and second reinspections
for noncompliance with Department and/or Department of Health requirements.
G.
Determination of type of backflow protection device.
(1)
Categories; rating system; regulation.
(a)
An acceptable backflow prevention device must be installed in
every service connection to a facility. Three categories shall be
considered when determining the degree of hazard posed by a facility
and making the subsequent determination of the type of protection
device required. The City of Beacon recognizes the threat to the public
water system arising from cross-connections. All threats will be classified
by degree of hazard and will require the installation of approved
reduced pressure principle backflow prevention devices, reduced pressure
zone assembly, (RPZA) or double check valve assembly (DCVA). The considerations
are:
(b)
Based on these considerations the water supply operator and/or
the City Engineer shall rate a facility as hazardous, aesthetically
objectionable or nonhazardous.
[1]
A hazardous facility must be contained through the use of an
RPZA or properly designed air gap.
[2]
An aesthetically objectionable facility must be contained through
the use of a DCV, RPZA, or air gap.
[3]
Nonhazardous facilities should be protected through an internal
plumbing control program to ensure that plumbing cross-connections
are adequately protected or eliminated; or through the use of a DCVA,
RPZA or air gap.
(2)
The Water Superintendent and/or the City Engineer as designated by
the City Council shall determine the type of device required for each
property and facility. In making this determination, the water supply
operator may utilize the Sample List of Facilities Requiring Backflow
Prevention, prepared by the NYSDOH and, if necessary, shall consult
with the DCDOH.
(3)
Cross-connection control by facility type.
(a)
Hazardous types of facilities which shall require installation
of an approved reduced pressure zone assembly (RPZA) or air gap in
the service connection to the public water distribution system include
but are not limited to:
[1]
Sewage and industrial wastewater treatment plants and pumping
stations and sewer flushers.
[2]
Paper manufacturing or processing, dye plants, petroleum processing,
printing plants, chemical manufacturing or processing, industrial
fluid systems, steam generation, rubber processing and tanneries.
[3]
Canneries, breweries, food processing, milk processing, ice
manufacturing, meat packers, poultry processing and rendering companies.
[4]
Hospitals, clinics, laboratories, veterinary hospitals, mortuaries
and embalmers.
[5]
Metal plating, photo processing, laundries, commercial car washes,
commercial refrigeration systems and dry-cleaning establishments.
[6]
Commercial greenhouses, spraying and irrigation systems using
weedicides, herbicides and exterminators.
[7]
Boiler systems, cooling towers or internal firefighter systems
using conditioners, inhibitors and corrosion control chemicals.
[8]
Residential units with lawn and irrigation systems with chemical
injection.
[9]
Residential units or facilities with service provided by both
the village water distribution system and private well or water supply.
(b)
Aesthetically objectionable types of facilities which shall
require installation of an approved double check valve, RPZA or air
gap in the service connection of the public water distribution system
are those which include but are not limited to:
[1]
Customer fire-protection loops and fire-storage tanks with no
chemical additives.
[2]
High-temperature potable water.
[3]
Utilization for food-grade dyes.
[4]
Complex plumbing systems in commercial buildings, such as but
not limited to beauty salons, churches, apartment buildings, gas stations,
supermarkets, nursing homes, construction sites and carnivals.
[5]
Residential units with lawn and irrigation systems.
(c)
It is not possible to list every circumstance and facility type
that may be encountered by the Department while evaluating all users.
The Department, while evaluating a facility, will rely on experience,
assistance from local Health Department officials and the Cross-Connection
Control Program Manual.
H.
Existing in-use backflow prevention devices. Any existing backflow
prevention device shall be allowed by the Department to continue in
service unless the degree of hazard is such as to supersede the effectiveness
of the present backflow prevention device, or result in an unreasonable
risk to the public health. Where the degree of hazard has increased,
as in the case of a residential installation converting to a business
establishment, any existing backflow prevention device must be upgraded
to a reduced-pressure-principle device, or a reduced-pressure-principle
device must be installed in the event that no backflow prevention
device was present.
I.
Periodic testing.
(1)
All testers of backflow prevention devices shall be approved by the
NYSDOH pursuant to Section 1.13 of Part 5 of the New York State Sanitary
Code, 10 NYCRR Section 5-1.31.
(2)
The testing of backflow prevention devices shall be performed on
an annual basis by the owner of any system requiring the same, and
the cost of such testing shall be borne by the owner of the system.
The testing procedures shall conform to the requirements of the NYSDOH
and the DCDOH. Test results shall be submitted to the Department within
30 days of the completion of such testing. Late submissions of annual
test results shall be subject to an administrative processing fee
in the amount of $25.
(3)
Any backflow prevention device which fails during a periodic test
will be repaired or replaced. When repairs are necessary, upon completion
of the repair the device will be retested at the owner's expense to
ensure correct operation. High-hazard situations will not be allowed
to continue unprotected if the backflow prevention device fails the
test and cannot be repaired immediately. In other situations, a compliance
date of not more than 30 days after the test date will be established.
The owner is responsible for spare parts, repair tools or a replacement
device. Parallel installation of two devices is an effective means
of the owner ensuring uninterrupted water service during testing or
repair of devices and is strongly recommended when the owner desires
such continuity.
(4)
Backflow prevention devices will be tested more frequently than specified
above in cases where there is a history of test failures and the water
supply operator feels that, due to the degree of hazard involved,
additional testing is warranted. Cost of the additional testing will
be borne by the owner.
(5)
Testing is not required when fixture isolation is achieved with the
utilization of a nontestable backflow prevention device.
J.
Residential dual check assembly.
(1)
Effective the date of the acceptance of this cross-connection control
program for the City of Beacon, all new residential buildings, which
includes one-family and two-family dwellings, will be required to
install a residential dual check assembly immediately downstream of
the water meter. Installation of this residential dual check assembly
on the retrofit basis on existing service lines will be instituted
at a time and at a potential cost to the homeowner as deemed necessary
by the Department.
(2)
The owners must be aware that installation of a residential dual
check assembly results in a potential closed plumbing system within
the residence. As such, provisions may have to be made by the owners
to provide for thermal expansion within the closed loop system, i.e.,
the installation of thermal expansion devices and/or pressure relief
valves.
K.
Strainers. The Department strongly recommends that all new retrofit
installations of reduced-pressure-principle devices and double check
valve backflow prevention devices include the installation of strainers
located immediately upstream of the backflow prevention device. The
installation of strainers will preclude the fouling of the backflow
prevention devices due to both foreseen and unforeseen circumstances
occurring to the water supply system, such as water main repairs,
water main breaks, fires, periodic cleaning and flushing of mains,
etc. These occurrences may stir up debris within the water main that
will cause fouling of backflow prevention devices installed without
the benefit of strainers.
L.
Penalties for offenses; corrective action.
(1)
Any person violating any provision of this chapter shall be subject to a penalty as prescribed in § 1-3.
(2)
Notwithstanding the penalties hereinabove provided, the City of Beacon
may maintain an action or proceeding in a court of competent jurisdiction
to compel compliance with or to restrain by injunction the violation
of any provision of this chapter.
[Amended 12-5-2016 by L.L. No. 17-2016]
In the event that a change in ground elevation leaves a service pipe insufficiently buried, the property owner shall promptly lower or raise his service pipe to conform to the new ground elevation. In case the property owner fails or neglects to make such alterations promptly, the supply of water will be shut off until the alterations are completed, and a new charge, as set forth in the schedule of rates established pursuant to § 219-29, will be made to cover the labor and expense by the City resulting from the property owner's failure so to do.
[Amended 12-5-2016 by L.L. No. 17-2016]
In all places where steam boilers, hot-water tanks, refrigerating
or air-conditioning units are supplied with water from the water system,
the property owner or consumer must see that the plumber places a
suitable safety valve, vacuum valve or other proper device to prevent
damage from collapse or explosion when water is shut off. The City
shall not be liable for any damage resulting from sudden shutting
off of the supply of water from any steam boiler or other fixture
deriving its supply from the water supply.