Exciting enhancements are coming soon to eCode360! Learn more 🡪
City of Beacon, NY
Dutchess County
By using eCode360 you agree to be legally bound by the Terms of Use. If you do not agree to the Terms of Use, please do not use eCode360.
Table of Contents
Table of Contents
A licensed plumber will lay the service pipe from the main to the structure being served. All hookups between the main up to and including the structure will be made by a licensed plumber. The property owner shall be responsible for maintenance of the water service line from the main up to the structure being served.
A. 
Service pipe from the City's main to the meter shall be laid at least four feet below the surface of the ground at all points and shall be backfilled with suitable materials as determined by the Water Superintendent and/or Highway Superintendent. The service pipe shall conform to such standards and shall be of such make and type as the Water Superintendent shall direct and shall be of such size as the City shall deem proper. The minimum size for any service hereafter installed shall, however, be 3/4 inch.
B. 
Service pipes from the curb box to the meter, less than two inches in diameter, shall be of pure, seamless, soft-tempered copper tubing with flared or compression red brass or bronzed fittings.
C. 
Tubing shall be of the following thickness:
Normal Pipe Size
(inches)
Outside Diameter of Tubing
(inches)
Type
 3/4
7/8
K
1
1 1/8
K
1 1/4
1 3/8
K
1 1/2
1 5/8
K
D. 
No soldered joints shall be permitted in copper tubing underground.
No tee or other fitting through which water can be taken will be permitted on the service pipe between the main and the meter.
Outdoor meter pits may be installed in special cases on written approval of the City. Such meter pits must be installed in accordance with City specifications and at the expense of the property owner.
[Amended 12-5-2016 by L.L. No. 17-2016]
No branch will be allowed to be inserted in any service pipe without a written permit from the City. Where branches already exist and are not provided with curb boxes, in case of default in payment of water rent by any one property owner or consumer, the main service may be cut off until the back charges are paid. The City shall not be liable for damages to any other property owner or consumer who may thus be deprived of water. Backflow preventers (check valves) must be installed on all installations. The City reserves the right to set a time limit for the removal of any branch lines so that, upon reasonable notice of the imposition of said time limit, each dwelling so affected shall install a separate service line at the property owner's or consumer's expense.
[Amended 9-18-2017 by L.L. No. 10-2017]
A. 
The intent of this article is to:
(1) 
Protect the public water supply served by the City of Beacon Water and Sewer Department from the possibility of contamination or pollution which could backflow or back-siphon into the public water system.
(2) 
Promote the elimination or control of existing cross-connections, actual or potential, between its customer's potable water system and nonpotable systems.
(3) 
Provide for the maintenance of a continuing program of cross-connection control which will effectively prevent the contamination or pollution of all potable water systems by cross-connection.
B. 
Authority. Pursuant to the Federal Safe Drinking Water Act of 1974[1] and statutes promulgated in Article 2 of the Public Health Law and in Part 5, Section 5-1.31, of the State Sanitary Code (10 NYCRR Part 5), the New York State Department of Health (NYSDOH) has undertaken a program for preventing water from unapproved sources from entering the public potable water system. Subpart 5-1 of the State Sanitary Code, Section 5-1.32, requires that the supplier of all public water shall protect the public water system by containing potential contamination within the premises of each individual water user.
[1]
Editor's Note: See 42 U.S.C. § 300f et seq.
C. 
Definitions. As used in this section, the following terms shall have the meanings indicated:
AIR GAP
A physical separation sufficient to prevent backflow between the free-flowing discharge end of the potable water system and any other system; physically defined as a distance equal to twice the diameter of the supply side pipe diameter but never less than one inch.
APPROVED
Accepted by the New York State Department of Health, Dutchess County Department of Health and City of Beacon Water and Sewer Department meeting applicable specifications stated or cited in this regulation, or as suitable for the proposed use.
ATMOSPHERIC VACUUM BREAKER
A device which prevents backsiphonage by creating an atmospheric vent when there is either a negative pressure or subatmospheric pressure in a water system.
AUXILIARY WATER SUPPLY
Any water supply on or available to the premises other than the surveyor's approved public potable water supply.
BACK PRESSURE
A condition in which the owner's system pressure is greater than the supplier's system pressure.
BACK-SIPHON
The flow of water or other liquids, mixtures or substances into the distribution pipes of a potable water supply system from any source other than its intended source, caused by a sudden reduction of pressure in the potable water supply system.
BACKFLOW
The flow of water or other liquids, mixtures or substances and/or positive or reduced pressure in the distribution pipes of a potable water supply from any source other than its intended source.
BACKFLOW PREVENTION DEVICE
A device or means designed to prevent backflow or backsiphonage. Most commonly categorized as air gap, reduced pressure principle device, double check valve assembly, pressure vacuum breaker, atmospheric vacuum breaker, hose bibb vacuum breaker, residential dual check, double check with intermediate atmospheric vent, and barometric loop.
BAROMETRIC LOOP
A fabricated piping arrangement rising at least 35 feet at its topmost point above the highest fixture it supplies. It is utilized in water supply systems to protect against backsiphonage.
CONTAINMENT
A method of backflow prevention which requires a backflow prevention device at the water service entrance immediately after the water meter or, in the event of no meter, immediately after the point of entry.
CONTAMINANT
Any physical, chemical, microbiological or radiological substance or matter in water.
CROSS-CONNECTION
Any actual or potential connection between the public water supply and a source of contamination or pollution.
DEPARTMENT
The City of Beacon Water and Sewer Department.
DEPARTMENT OF HEALTH
The State of New York Health Department and its agent, the Dutchess County Department of Health.
DOUBLE CHECK VALVE ASSEMBLY (DCV)
An assembly of two independently operating spring-loaded check valves with tightly closing shutoff valves on each side of the check valves, plus properly located test cocks for the testing of each check valve.
DOUBLE CHECK VALVE WITH INTERMEDIATE ATMOSPHERIC VENT
A device having two spring-loaded check valves separated by an atmospheric vent chamber.
DWELLING UNIT
One or more rooms with provision for living, cooking, sanitary and sleeping facilities arranged for the use of one family.
DWELLING, ONE-FAMILY
A building containing not more than one dwelling unit occupied exclusively for residential purposes by one family.
DWELLING, TWO-FAMILY
A building containing not more than two dwelling units occupied exclusively for residential purposes by two families living independently of each other.
FIXTURE ISOLATION
A method of backflow prevention in which a backflow prevention device is located to correct a cross-connection at an in-plant location rather than at a water service entrance.
HOSE BIBB VACUUM BREAKER
A device which is permanently attached to a hose bibb and which acts as an atmospheric vacuum breaker.
OWNER
Any person who has a legal title to, or license to operate or habitat in, a property upon which a cross-connection is present.
PERSON
Any individual, partnership, company, public or private corporation, political subdivision or agency of the State Department, agency or instrumentality of the United States or any other legal entity.
POLLUTANT
A foreign substance that, if permitted to get into the public water system, will degrade its quality so as to constitute a moderate hazard or impair the usefulness or quality of the water to a degree which does not create an actual hazard to the public health but which does adversely and unreasonably affect such water for domestic use.
PRESSURE VACUUM BREAKER
A device containing one or two independently operated spring-loaded check valves and an independently operated spring-loaded air inlet valve located on the discharge side of the check or checks. Such device includes tightly closing shutoff valves on each side of the check valves and properly located test cocks for the testing of the check valves.
REDUCED-PRESSURE-PRINCIPLE BACKFLOW PREVENTER (RPZ)
An assembly consisting of two independently operating approved check valves with an automatically operating differential relief valve located between two check valves, tightly closing shutoff valves on each side of the check valves, plus properly located test cocks for the testing of the check valves and the relief valve.
WATER SERVICE ENTRANCE
The point in the owner's water system beyond the sanitary control of the City; generally considered on the outlet end of the water meter and always before any unprotected branch.
WATER, NONPOTABLE
Water that is not safe for human consumption or that is of questionable potability.
WATER, POTABLE
Water free from impurities in amounts sufficient to cause disease or harmful physiological effects.
D. 
Enforcement. The Water Superintendent and/or City Engineer or his or her designee shall enforce this article and the cross-connection and backflow protection requirements, specifications, guidelines and facilities classifications of the NYSDOH and the Dutchess County Department of Health (DCDOH). Specifications, guidelines, facilities, classifications and other administrative requirements and information which shall be used to implement the requirements shall be on file in the Department and available for review.
E. 
Administration.
(1) 
The Department will operate a cross-connection control program to include the keeping of necessary records, which fulfills the requirements of the NYSDOH's cross-connection regulations and testing of backflow prevention equipment.
(2) 
The owners shall allow their property to be inspected for possible cross-connections and shall follow the provisions the Department's cross-connection control program as set forth by the City of Beacon.
(3) 
If the Department requires that the public supply be protected by containment, the owners shall be responsible for water quality beyond the outlet end of the containment device and should utilize fixture outlet protection for that purpose.
F. 
Responsibilities.
(1) 
Department.
(a) 
The Department will not allow any cross-connection to remain unless it is protected by an approved backflow prevention device, which will be regularly tested to insure satisfactory operation. If, in the judgment of the City, an approved backflow prevention device is required for existing installations, the City shall give notice in writing to said owner to install an approved backflow prevention device at each service connection to said premises. Hazardous conditions shall be addressed immediately. On new installations, the Department will provide on-site evaluation and/or review of plans in order to determine the type of backflow prevention device, if any, that will be required. Plans shall be signed and sealed by a currently licensed New York State professional engineer.
(b) 
For premises existing prior to the start of this program, the Department will perform evaluations and review of plans and/or inspection of premises and inform the owner by letter of any corrective action deemed necessary, the method of achieving the correction and the time allowed for the correction to be made. Ordinarily, 90 days will be allowed; however, this time period may be shortened by the Department depending upon the degree of hazard involved and the history of the device(s) in question.
(c) 
The Department shall inform the owners, by letter, of any failure to comply by the time of the first reinspection. The Department will allow an additional 15 days for the correction. In the event that the owners fail to comply with the necessary correction by the time of the second reinspection, the Department will inform the owners, by letter, that the water service to the owners' premises will be terminated within a period not to exceed five days. In the event that the owners inform the Department of extenuating circumstances as to why the correction has not been made, a time extension may be granted by the Department but in no case will exceed an additional 30 days.
(d) 
If the Department determines at any time that a serious threat to the public health exists, the water service will be terminated immediately. If the Department determines that terminating water service is not feasible, the owner will be subject to fines listed in another section of this chapter.
(e) 
The Department shall have on file a list of private contractors who are certified backflow device testers. The owner is responsible for all costs associated with the installation and testing of any backflow prevention device.
(f) 
The Department will begin initial premises inspections to determine the nature of existing or potential hazards following the approval of this program by the City Council of the City of Beacon. Initial focus will be on high-hazard industries and commercial premises.
(2) 
Owners.
(a) 
The owners shall be responsible for the elimination or protection of all cross-connections on their premises.
(b) 
The owners, after having been informed by a letter from the Department, shall at their expense install, maintain, and test, or have tested, any and all backflow prevention devices on their premises. The owners shall be responsible for all costs associated with the installation and testing of backflow prevention devices.
(c) 
After the Department determines the type of backflow prevention device, if any, required and approves the backflow prevention device, the owner shall submit an application to the NYSDOH to obtain a permit to construct the approved backflow prevention device. The work shall be completed within 90 days from receipt of the permit. Failure or refusal or inability on the part of the owner to install said device within 90 days shall constitute grounds for discontinuing water service until such device has been properly installed.
(d) 
After completion of installation of the backflow prevention device, the owner shall apply for a completed works permit by submitting to the NYSDOH a certification from an engineer which states that the installation of the work is in compliance with the approved plans and certification from an approved tester of backflow prevention devices, that the installation was tested and is working as designed and approved and in accordance with the intent of these regulations.
(e) 
The owner shall submit to the City of Beacon Water and Sewer Department and Building Department all certifications submitted to the NYSDOH, including the certification that the installation of the approved backflow prevention device is in compliance with the approved plans and the certification that the installation was tested and is working as designed.
(f) 
The owners shall correct any malfunction of the backflow prevention device which is revealed by periodic testing.
(g) 
The owners shall inform the Department of any proposed or modified cross-connections of which the owners are aware but have not been found by the Department.
(h) 
The owners shall not install a bypass around any backflow prevention device unless there is a backflow prevention device of the same type on the bypass. Owners who cannot shut down operation for testing of the device(s) must supply additional devices necessary to allow testing to take place.
(i) 
The owners shall install only backflow prevention devices which are shown on an NYSDOH list of approved backflow prevention devices.
(j) 
Any owners having a private well or other private water source must obtain approval from the Department if the well or source is cross-connected to the Department's system. Permission to cross-connect may be denied by the Department. The owner may be required to install a backflow prevention device at the service entrance if a private water source is maintained, even if it is not cross-connected to the Department's system.
(k) 
In the event that the owners install plumbing to provide potable water for domestic purposes which is on the Department's side of the backflow prevention device, such plumbing must have its own backflow prevention device installed.
(l) 
The owners shall be responsible for the payment of all permit fees, penalties, annual or semiannual device testing, retesting in the case that the device fails to operate correctly, and second reinspections for noncompliance with Department and/or Department of Health requirements.
G. 
Determination of type of backflow protection device.
(1) 
Categories; rating system; regulation.
(a) 
An acceptable backflow prevention device must be installed in every service connection to a facility. Three categories shall be considered when determining the degree of hazard posed by a facility and making the subsequent determination of the type of protection device required. The City of Beacon recognizes the threat to the public water system arising from cross-connections. All threats will be classified by degree of hazard and will require the installation of approved reduced pressure principle backflow prevention devices, reduced pressure zone assembly, (RPZA) or double check valve assembly (DCVA). The considerations are:
[1] 
Use, toxicity and availability of contaminants.
[2] 
Availability of a supplementary supply of water.
[3] 
Firefighting system evaluation.
(b) 
Based on these considerations the water supply operator and/or the City Engineer shall rate a facility as hazardous, aesthetically objectionable or nonhazardous.
[1] 
A hazardous facility must be contained through the use of an RPZA or properly designed air gap.
[2] 
An aesthetically objectionable facility must be contained through the use of a DCV, RPZA, or air gap.
[3] 
Nonhazardous facilities should be protected through an internal plumbing control program to ensure that plumbing cross-connections are adequately protected or eliminated; or through the use of a DCVA, RPZA or air gap.
(2) 
The Water Superintendent and/or the City Engineer as designated by the City Council shall determine the type of device required for each property and facility. In making this determination, the water supply operator may utilize the Sample List of Facilities Requiring Backflow Prevention, prepared by the NYSDOH and, if necessary, shall consult with the DCDOH.
(3) 
Cross-connection control by facility type.
(a) 
Hazardous types of facilities which shall require installation of an approved reduced pressure zone assembly (RPZA) or air gap in the service connection to the public water distribution system include but are not limited to:
[1] 
Sewage and industrial wastewater treatment plants and pumping stations and sewer flushers.
[2] 
Paper manufacturing or processing, dye plants, petroleum processing, printing plants, chemical manufacturing or processing, industrial fluid systems, steam generation, rubber processing and tanneries.
[3] 
Canneries, breweries, food processing, milk processing, ice manufacturing, meat packers, poultry processing and rendering companies.
[4] 
Hospitals, clinics, laboratories, veterinary hospitals, mortuaries and embalmers.
[5] 
Metal plating, photo processing, laundries, commercial car washes, commercial refrigeration systems and dry-cleaning establishments.
[6] 
Commercial greenhouses, spraying and irrigation systems using weedicides, herbicides and exterminators.
[7] 
Boiler systems, cooling towers or internal firefighter systems using conditioners, inhibitors and corrosion control chemicals.
[8] 
Residential units with lawn and irrigation systems with chemical injection.
[9] 
Residential units or facilities with service provided by both the village water distribution system and private well or water supply.
(b) 
Aesthetically objectionable types of facilities which shall require installation of an approved double check valve, RPZA or air gap in the service connection of the public water distribution system are those which include but are not limited to:
[1] 
Customer fire-protection loops and fire-storage tanks with no chemical additives.
[2] 
High-temperature potable water.
[3] 
Utilization for food-grade dyes.
[4] 
Complex plumbing systems in commercial buildings, such as but not limited to beauty salons, churches, apartment buildings, gas stations, supermarkets, nursing homes, construction sites and carnivals.
[5] 
Residential units with lawn and irrigation systems.
(c) 
It is not possible to list every circumstance and facility type that may be encountered by the Department while evaluating all users. The Department, while evaluating a facility, will rely on experience, assistance from local Health Department officials and the Cross-Connection Control Program Manual.
H. 
Existing in-use backflow prevention devices. Any existing backflow prevention device shall be allowed by the Department to continue in service unless the degree of hazard is such as to supersede the effectiveness of the present backflow prevention device, or result in an unreasonable risk to the public health. Where the degree of hazard has increased, as in the case of a residential installation converting to a business establishment, any existing backflow prevention device must be upgraded to a reduced-pressure-principle device, or a reduced-pressure-principle device must be installed in the event that no backflow prevention device was present.
I. 
Periodic testing.
(1) 
All testers of backflow prevention devices shall be approved by the NYSDOH pursuant to Section 1.13 of Part 5 of the New York State Sanitary Code, 10 NYCRR Section 5-1.31.
(2) 
The testing of backflow prevention devices shall be performed on an annual basis by the owner of any system requiring the same, and the cost of such testing shall be borne by the owner of the system. The testing procedures shall conform to the requirements of the NYSDOH and the DCDOH. Test results shall be submitted to the Department within 30 days of the completion of such testing. Late submissions of annual test results shall be subject to an administrative processing fee in the amount of $25.
(3) 
Any backflow prevention device which fails during a periodic test will be repaired or replaced. When repairs are necessary, upon completion of the repair the device will be retested at the owner's expense to ensure correct operation. High-hazard situations will not be allowed to continue unprotected if the backflow prevention device fails the test and cannot be repaired immediately. In other situations, a compliance date of not more than 30 days after the test date will be established. The owner is responsible for spare parts, repair tools or a replacement device. Parallel installation of two devices is an effective means of the owner ensuring uninterrupted water service during testing or repair of devices and is strongly recommended when the owner desires such continuity.
(4) 
Backflow prevention devices will be tested more frequently than specified above in cases where there is a history of test failures and the water supply operator feels that, due to the degree of hazard involved, additional testing is warranted. Cost of the additional testing will be borne by the owner.
(5) 
Testing is not required when fixture isolation is achieved with the utilization of a nontestable backflow prevention device.
J. 
Residential dual check assembly.
(1) 
Effective the date of the acceptance of this cross-connection control program for the City of Beacon, all new residential buildings, which includes one-family and two-family dwellings, will be required to install a residential dual check assembly immediately downstream of the water meter. Installation of this residential dual check assembly on the retrofit basis on existing service lines will be instituted at a time and at a potential cost to the homeowner as deemed necessary by the Department.
(2) 
The owners must be aware that installation of a residential dual check assembly results in a potential closed plumbing system within the residence. As such, provisions may have to be made by the owners to provide for thermal expansion within the closed loop system, i.e., the installation of thermal expansion devices and/or pressure relief valves.
K. 
Strainers. The Department strongly recommends that all new retrofit installations of reduced-pressure-principle devices and double check valve backflow prevention devices include the installation of strainers located immediately upstream of the backflow prevention device. The installation of strainers will preclude the fouling of the backflow prevention devices due to both foreseen and unforeseen circumstances occurring to the water supply system, such as water main repairs, water main breaks, fires, periodic cleaning and flushing of mains, etc. These occurrences may stir up debris within the water main that will cause fouling of backflow prevention devices installed without the benefit of strainers.
L. 
Penalties for offenses; corrective action.
(1) 
Any person violating any provision of this chapter shall be subject to a penalty as prescribed in § 1-3.
(2) 
Notwithstanding the penalties hereinabove provided, the City of Beacon may maintain an action or proceeding in a court of competent jurisdiction to compel compliance with or to restrain by injunction the violation of any provision of this chapter.
[Amended 12-5-2016 by L.L. No. 17-2016]
In the event that a change in ground elevation leaves a service pipe insufficiently buried, the property owner shall promptly lower or raise his service pipe to conform to the new ground elevation. In case the property owner fails or neglects to make such alterations promptly, the supply of water will be shut off until the alterations are completed, and a new charge, as set forth in the schedule of rates established pursuant to § 219-29, will be made to cover the labor and expense by the City resulting from the property owner's failure so to do.
[Amended 12-5-2016 by L.L. No. 17-2016]
In all places where steam boilers, hot-water tanks, refrigerating or air-conditioning units are supplied with water from the water system, the property owner or consumer must see that the plumber places a suitable safety valve, vacuum valve or other proper device to prevent damage from collapse or explosion when water is shut off. The City shall not be liable for any damage resulting from sudden shutting off of the supply of water from any steam boiler or other fixture deriving its supply from the water supply.