A permit shall be obtained for any of the following:
A. The storage, handling or use of Class I or Class II flammable
liquids in excess of one gallon in a dwelling or other place of human habitation
or in excess of six gallons in any other building or other occupancy or in
excess of 10 gallons outside of any building, except that no permit shall
be required for the following:
(1) For the storage or use of flammable liquids in the fuel
tank of a motor vehicle, aircraft, motorboat, mobile power plant or mobile
heating plant.
(2) For the storage or use of paints, oils, varnishes or
similar flammable mixtures when such liquids are stored for maintenance, painting
or similar purposes for a period of not more than 30 days.
B. Storage, handling or use of Class III flammable liquids
in excess of 25 gallons in a building or in excess of 60 gallons outside of
a building, except for fuel oil used in connection with oil-burning equipment.
C. For the manufacture, processing, blending or refining
of flammable liquids.
D. For the storage of flammable liquids in stationary tanks.