Exciting enhancements are coming soon to eCode360! Learn more 🡪
Town of Ellicott, NY
Chautauqua County
By using eCode360 you agree to be legally bound by the Terms of Use. If you do not agree to the Terms of Use, please do not use eCode360.
Table of Contents
Table of Contents
A. 
All extensions to the sanitary sewer system owned and maintained by the town shall be properly designed in accordance with and in strict conformance with all requirements of the New York State Department of Environmental Conservation.
B. 
Plans and specifications for sewer extensions shall be submitted to and approval obtained from the Director and engineer and the New York State Department of Environmental Conservation or County Health Department before construction may proceed.
C. 
The design of sewers shall anticipate and allow for flows from all possible future extensions or developments within the immediate drainage area.
Sewer extensions may be constructed by the town under public contract if expenditure and town plan modification procedures required by state law are satisfied.
The property owner, builder or developer may construct the necessary sewer extension, if such extension is approved by the Director and the Board in accordance with the requirements set forth in this chapter and in accordance with the conditions of such approval and of the terms of the agreement between the town and the owner regarding the sewer extension. He or they must pay for the entire installation, including all expenses incidental thereto. Each building sewer must be installed and inspected as required by this chapter. The installation of the sewer extension must be subject to inspection by the Director, and the expenses for this inspection shall be paid for by the owner, builder or developer. The Director's decisions shall be final in matters of quality and methods of construction. The sewer, as constructed, must pass the infiltration or exfiltration test set forth in this chapter before it is to be used.
Main line sewer design and construction shall be in accordance with the following:
A. 
Documents.
(1) 
All work shall be in accordance with the following documents:
(a) 
Recommended Standards for Sewage Works, latest edition, as adopted by the Great Lakes — Upper Mississippi River Board of State Sanitary Engineers.
(b) 
Design and Construction of Sanitary and Storm Sewers, latest edition, as adopted by the Water Pollution Control Federation.
(2) 
Where conflicts between the two documents exist, the provisions of Recommended Standards for Sewage Works shall prevail.
B. 
Construction materials and details shall meet the following minimum requirements which may be more stringent than the above standards.
(1) 
Gravity sewers shall be PVC pipe meeting the requirements of ASTM D 3034 with elastomeric joints in compliance with ASTM D 3212. The nominal pipe size shall be eight inches or greater. The standard dimension ratio (SDR) shall be 35 or less. Ductile iron pipe meeting the requirements of AWWA C 151 shall be utilized where the minimum vertical separation between sanitary sewers and water mains specified in Recommended Standards for Sewage Works cannot be attained.
(2) 
Pressure sewers (force mains) shall be PVC pipe meeting the requirements or ASTM D 2241 with rubber-gasketed joints meeting the requirements of ASTM D 3139. The standard dimension ratio shall be 26 or less. The nominal pipe size for low pressure grinder systems shall be not less than 2 1/2 inches. The nominal pipe size for other pumping systems shall be not less than four inches.
(3) 
Manholes and other belowground structures providing access to the sewer system shall be of precast concrete construction meeting the requirements of ASTM C 478. The minimum inside diameter shall be four feet. Manholes 12 feet or more in depth shall have a minimum inside diameter of five feet. Manholes and other structures shall have a cast-iron frame and cover meeting the requirements of ASTM A 48, Class 30. The size and shape shall meet the town's standard design. Leveling brick, at least two courses thick but not more than four courses thick, shall be used to provide adjustment to meet the finish grade.
(4) 
Pump stations shall be of the submersible pump, wet-well type. All pump stations, except for grinder pump stations serving a single residential unit, shall have two pumps, each adequate to meet the anticipated peak demand. Except for small grinder pump stations, the wet well shall be of precast concrete construction. Fiberglass wet wells shall be permitted for small [serving one or two residential units] grinder pump stations. Grinder pumps shall be the standard established by the town and be of the same manufacturer. Each pump station shall be equipped with a flashing alarm light indicating pump failure. Where the location is not readily viewable from a traveled public road, the Director may require additional failure alarm systems.
(5) 
Manholes shall be installed wherever there is a change in grade or alignment and at the ends of gravity sewer systems. The spacing between manholes shall not exceed 350 feet.
(6) 
Forcemains shall have cleanouts at intervals not greater than 500 feet. Automatic air relief valves shall be installed at high points in the forcemain where air pockets may develop.
(7) 
Infiltration and exfiltration tests on gravity sewers shall be performed as specified in Recommended Standards for Sewerage Works, except the allowable infiltration/exfiltration shall not exceed 100 gallons per inch of pipe diameter per mile per day. The allowable leakage at manholes shall not exceed 0.9 gallons per foot of depth per day. Air testing may be substituted, if approved by the Director.
(8) 
Forcemains shall be tested in accordance with AWWA Specification C 600. The allowable leakage shall not exceed the following:
Test Pressure
(pounds per square inch)
Allowable Leakage per 100 Joints
(gallons per hour per inch of pipe diameter)
50
0.096
100
0.135
150
0.166
(9) 
All sewers shall be installed using open-trench methods of construction, unless otherwise approved by the Director. Pipelaying and backfilling shall be performed in accordance with ASTM Specification D 2321, except that pipe bedding material shall be installed to a depth of six inches below the pipe and to six inches above the crown of the pipe. Pipe bedding material shall be No. 1 size clean crushed gravel or stone. The pipe shall not be backfilled until inspected and approved by the Director. Backfill to grade shall use suitable material previously excavated except within public rights-of-ways where the Street Superintendent shall define the backfill material and the compaction effort required.
All sewer extensions constructed and deemed acceptable to the engineer and Board shall become the property of the town and shall thereafter be maintained by the town. Said sewers, after their acceptance by the town, shall be guaranteed against defects in materials or workmanship for 18 months. The guaranty shall be in a form acceptable to the town. At the sole discretion of the town, a completion bond or other security may be demanded as part of the guaranty.
Prior to the connection of the sewer extension to the public sewer, the owner shall provide the town with:
A. 
Instruments of transfer of all property rights necessary to operate and maintain the sewer extension with acceptable proof of title in such property.
B. 
The certification of a New York State licensed professional engineer that the sewer extension was constructed in accordance with the approved plans and specifications; and
C. 
The guaranty required by § 118-26 of this chapter.
No builder or developer shall be issued a building permit for a new dwelling or structure requiring sanitary facilities within the town unless a suitable and approved method of waste disposal is proposed. All new developments shall have an approved system of sanitary sewers.