[Adopted 12-14-2009 by Ord. No. 33-K-1.A[1]]
[1]
Editor's Note: This ordinance also repealed former Art. III, International Building Code, adopted 12-14-2006 by Ord. No. 33-K-1.A, as amended.
This article shall be known as the "Lower Pottsgrove Township Building Code."
[Amended 8-18-2022 by Ord. No. 360]
Except as amended and modified by the Pennsylvania Uniform Construction Code (Act 45 of 1999), 34 Pa. Code Chapters 401 through 405, a certain document being marked and designated as the International Building Code, 2018 Edition (hereinafter the "2018 IBC"), as published by the International Code Council, Inc., be and is hereby adopted as the Building Code of the Township of Lower Pottsgrove, Montgomery County, in the Commonwealth of Pennsylvania, for the control of buildings and structures as herein provided, and each and all of the regulations, provisions, penalties, conditions, and terms of said 2018 IBC, are hereby referred to, adopted, and made a part hereof, as if fully set out in the article, as set forth herein. Three copies of the 2018 IBC are on file at the Lower Pottsgrove Township Building.
A. 
Creation of the enforcement agency. The Code Administration Office is here by created, and the official in charge thereof shall be known as the "Code Administration Officer." References in the International Building Code to the "building official" shall mean the Code Administration Officer. The Code Administration Officer shall be appointed by the Board of Commissioners of Lower Pottsgrove Township and shall serve at its pleasure.
B. 
Assistant Code Administration Officer. The Board of Commissioners may designate an employee as an assistant, who shall exercise all the powers of the Code Official during the temporary absence or disability of the Code Administration Officer. The Assistant Code Administration Officer shall serve at the pleasure of the Board of Commissioners. The Assistant Code Administration Officer may also be referred to herein as the "Assistant Code Official."
Certificate of insurance. The owner or his authorized representative, together with the contractor, shall provide the Township with a certificate of insurance naming the Township as a certificate holder. The certificate shall indicate the amount of contractors liability and workers' compensation coverage that is provided and the policy expiration dates. Contractors liability insurance shall be for damages or injury resulting from said construction, operation or demolition of work performed under valid permit. The certificate of insurance shall be required prior to the issuance of a permit.
The fees to be charged by the Township shall be adopted by and from time to time may be amended by the Board of Commissioners of Lower Pottsgrove Township by resolution duly adopted by the Board.
A. 
Change in occupant/owner/tenant/occupant nonresidential occupancies. Any change in ownership, occupant, tenant, use group change or any other type of change in the way any building is being used shall require a new use and occupancy permit and an inspection prior to occupancy. No change or re-occupancy shall take place prior to the issuance of a new use and occupancy permit.
B. 
Transfer of ownership. Within 10 days of transfer of ownership, an application and an inspection is required. This applies to all use groups except one and two-family dwellings.
A. 
All persons who own one or more residential dwelling units within the Township of Lower Pottsgrove, or the agent or manager for the owner, which are not owner-occupied, are required to report to the Township in writing certain information about the occupants of said dwelling units as provided as follows:
(1) 
Each report shall list, under the column headings of name, resident address and whether they are adult or minor, all persons occupying said property owner's dwelling unit or units.
(2) 
Reports required under this section shall be filed with the Township Code Official within one month from the effective date of this article.
(3) 
Reports shall be supplemented within 15 days of the arrival of occupants not previously reported or the departure of occupants previously reported.
B. 
Failure to report occupants correctly as prescribed above shall constitute a violation of this section and this article by the owner, agent, or manager of the premises.
If the Code Official determines that more than 50% of any structure has been damaged by a natural disaster, structural collapse, fire, or other disaster, the Code Official shall require the structure to be demolished. Every building damaged shall be inspected and a determination shall be made on a case-by-case basis. The cost and responsibility of performing the demolition shall be the owner's.
[Amended 8-18-2022 by Ord. No. 360]
The 2009 IBC is hereby changed and supplemented as follows:
The 2018 IBC is hereby changed and supplemented with the following:
A. 
Add a new Section 708.10 to read as follows:
708.10 Use Groups A, B, E, F, H, I, M, R, S, and U structures having more than one tenant and/or owner/occupier shall provide tenant separation walls between each such tenant and/or owner/occupier. Said walls shall consist of a minimum one-hour Underwriters' Laboratory ("UL") fire-rated assembly, unless other sections of this code require a higher rating. All fire-rated tenant separation walls shall be constructed of material consistent with the type of construction of the building.
B. 
Sections 903.2.1.1 (Group A-1), 903.2.1.3 (Group A-3), and 903.2.1.4 (Group A-4), Condition 1, shall be deleted and a new Condition 1 shall be inserted to read as follows:
(1) 
The fire area exceeds 5,000 square feet (464 m2).
C. 
Section 903.2.3, Condition 1, shall be deleted and a new Condition 1 shall be inserted to read as follows:
(1) 
Throughout all Group E fire areas greater than 5,000 square feet (464 m2) in area.
D. 
Section 903.2.4 shall be deleted and a new section shall be inserted to read as follows:
903.2.4 Groups F-1 and F-2. An automatic fire-suppression system shall be provided for any building or structure where Use Groups F-1 and F-2 fire areas exceed 5,000 square feet (464 m2) in area.
E. 
Section 903.2.7 shall be deleted and a new section shall be inserted to read as follows:
903.2.7 Groups B and M. An automatic fire-suppression system shall be provided for any building or structure where Use Groups B or M fire areas exceed 5,000 square feet (464 m2) in area.
F. 
Section 903.2.9 shall be deleted and a new section shall be inserted to read as follows:
903.2.9 Group S-1. An automatic fire-suppression system shall be provided for any building or structure where Use Group S-1 fire areas exceed 5,000 square feet (464 m2) in area.
G. 
Section 903.2.9.1 shall be deleted and a new section shall be inserted to read as follows:
903.2.9.1 Repair Garages. An automatic fire-suppression system shall be provided throughout all buildings used as repair garages in accordance with Section 406, as shown, where the S-1 fire areas exceed 5,000 square feet (464 m2) in area.
H. 
Sections 903.2.10 and 903.2.10.1 shall be deleted and a new Section 903.2.10 shall be inserted as follows:
903.2.10 Group S-2. An automatic fire-suppression system shall be provided for any building or structure where Use Group S-2 fire areas exceed 5,000 square feet (464 m2) in area.
I. 
Paragraph 1 of Section 903.2.11 shall be deleted and a new Paragraph 1 shall be inserted as follows:
In all occupancies other than Group U, excepting Animal Housing Facilities, as defined hereinafter, an automatic sprinkler system shall be installed for building design or hazards in the locations set forth in Sections 903.2.11.1 through 903.2.11.7.
J. 
A new Section 903.2.11.7 shall be added to read as follows:
903.2.11.7 Animal Housing Facilities. All Animal Housing Facilities, as defined by NFPA 150, where animals are kept for any purpose including, but not limited to, barns, stables, kennels, animal shelters, veterinary facilities, zoos, laboratories, and racetracks shall be equipped with an automatic fire-suppression system where the floor area of the Animal Housing Facility exceeds 5,000 square feet (464 m2) in area.
K. 
A new Section 903.3.1.4 shall be added to read as follows:
903.3.1.4 NFPA 13 "Light Hazard Systems." All NFPA 13 "Light Hazard Systems" shall be designed to have a maximum of 168 square feet (or less) sprinkler head spacing. This is the maximum that sprinkler heads shall be spaced in any occupancy permitted to be designed under a "light hazard" type classification in accordance with NFPA 13.
L. 
A new Section 903.3.1.5 shall be added to read as follows:
903.3.1.5 Safety Factor. All NFPA 13, 13R, and 13D fire-suppression systems shall be designed to provide a safety factor of 10 pounds per square inch (psi), as defined in NFPA 13.
M. 
A new Section 1013.7 shall be added to read as follows:
1013.7 Additional Locations/Low-Level Exit Signs. All A-1, A-2, A-3, B, E, R, I-1, and I-2 occupancies that are required to have more than one exit or exit access shall be supplemented by additional low-level exit signs reading "EXIT" on the face of the sign. Additional exit signs shall be located on the latch side of the door frame wall within six inches to eight inches of the floor in addition to the exit sign located above, or an egress access area. Self-illuminated or luminous exit signs shall be UL-listed for this purpose and approved by the Fire Marshal or Code Administration Officer.
N. 
A new Section 1210.0 shall be added to read as follows:
1210.0 Radon. At the time of application for a building permit, plans must depict reasonable measures to be constructed below grade level for future radon gas mitigation. Designs should accommodate the addition of a venting system for removal of radon gas from the premises in the future, should such radon gas be determined to be present at levels that exceed the maximum safe concentrations of radon gas as determined by the United States Environmental Protection Agency. A minimum four-inch diameter perforated pipe shall be installed below the basement slab around the interior perimeter of the foundation and shall terminate into a sump pit of sufficient size to accommodate the installation of a radon mitigation system.
O. 
A new Section 1809.5.1 shall be added to read as follows:
1809.5.1 Frost Line. For shallow foundation footings governed under this section, the frost line in Lower Pottsgrove Township shall be a minimum of 36 inches below grade. This shall be considered a minimum depth to the bottom of the footing.
P. 
A new Section 3303.8 shall be added to read as follows:
3303.8 Extermination Required. The applicant shall show proof that a building or structure scheduled for demolition pursuant to this section has been subject to the extermination of rodents, vermin, and other pests no less than two weeks prior to the scheduled demolition.
[1]
Editor's Note: Former §§ 100-15.4 and 100-15.5 were repealed 8-18-2022 by Ord. No. 360.
The granting of any permit under this article by the Township or any of its designated officials shall not constitute a representation, guarantee, or warranty of any kind by the Township or any of its officials or employees as to the proper manner of construction or repairs and shall create no liability upon or a cause of action against the Township, officials or employees for any damages or injury that may result pursuant thereto.
Nothing in this article shall be construed to affect any suit or proceeding pending in court, or any rights acquired, or liability incurred, or any cause or causes of action acquired or existing, under any act or article, nor shall any preexisting legal right or remedy of any character be lost, impaired or affected by this article.
[Amended 8-18-2022 by Ord. No. 360]
This article shall become effective as provided by law..