[Amended 9-17-2013 by Ord. No. 2013-3067; 11-19-2019 by Ord. No. 2019-3431; 3-16-2021 by Ord. No. 2021-3516; 7-18-2023 by Ord. No. 2023-3713]
This Article 3 establishes minimum regulations governing the design, construction, quality of materials, erection, installation, alteration, enlargement, repair, demolition, removal, maintenance and use of one- and two-family dwellings. It provides for the issuance of permits, collection of fees, making of inspections, and provides penalties for violations of the various codes and regulations adopted as part of this Chapter 14.
The International Code Council, Inc., 2015 Edition of the International Residential Code for One- and Two-Family Dwellings (the "Residential Building Code") is hereby adopted by reference and is hereby made a part of this Article 3 with the same force and effect as if fully set forth herein, except, however, those exceptions, insertions and additions described in Section 14-3-3 of this Code. The Residential Building Code, together with the International Building Code and International Existing Building Code set forth in Article 2 of this Chapter 14, are collectively referred to as the "Building Code" for the Village.
The following items are the additions, insertions and changes
to the International Residential Code:
Section 101.1 Title.
Delete all and insert "These provisions shall be known as the
Residential Code for One- and Two- Family Dwellings of the Village
of Lincolnwood and shall be cited as such and will be referred to
herein as 'this code.' The Village of Lincolnwood shall
be inferred whenever the term 'Village' is used in this
code."
Section 101.2 Scope.
Delete all and insert "The provisions of this code shall apply
to the construction, alteration, movement, enlargement, replacement,
repair, equipment, use and occupancy, location, removal and demolition
of detached one- and two-family dwellings and townhouses with a separate
means of egress and their accessory."
Section 101.2 Scope. Exception:
Delete all and insert "The following shall be permitted to be
constructed in accordance with this code where provided with a residential
fire sprinkler system in accordance with NFPA 13D
"1.
|
Live/work units located in townhouses and complying with the
requirements of Section 419 of the International Building Code.
|
"2.
|
Owner-occupied lodging houses with five or fewer guestrooms
in accordance with NFPA 13D.
|
"3.
|
A care facility with five or fewer persons receiving custodial
care within a dwelling unit.
|
"4.
|
A care facility with five or fewer persons receiving medical
care within a dwelling unit.
|
"5.
|
A care facility for five or fewer persons receiving care that
are within a single-family dwelling."
|
Section 102.4.1 Conflicts.
Delete all and insert "Where conflicts occur between this code
as well as the Illinois Plumbing Code, most current edition, the 2014
National Electric Code NFPA 70 and the Illinois Energy Conservation
Code, most current edition and other referenced codes and standards,
this code as well as the Illinois Plumbing Code, most current edition,
the 2014 National Electric Code NFPA 70 and the Illinois Energy Conservation
Code shall apply."
Section 102.4.2 Provisions in referenced codes and standards.
Delete all and insert "Where the extent of the reference to
a referenced code or standard includes subject matter that is within
the scope of this code, the provisions of this code, as applicable,
shall take precedence over the provisions in the referenced code or
standard."
Add (new section) Exceptions: and insert lines
(1 through 3) as follows:
"1.
|
All references to Part VII Plumbing Chapters 29 through 33 throughout this code shall be deleted and referenced back to the Illinois Plumbing Code, most current edition.
|
"2.
| |
"3.
|
All references to Part VIII Electrical Chapters 34 through 43 throughout this code shall be deleted and referenced back to the 2014 National Electric Code NFPA 70."
|
Section 103.1 Creation of enforcement agency.
Delete all and insert "The Division of Building Safety, as part
of the Community Development Department, is hereby created, and the
official in charge shall be known as the 'Building Official.'"
Add (new section) 105.1.1 Failure to pick up an approved
permit within six months.
Insert "Failure to pick up an approved permit within six months
from time of initial permit submittal where contact was made to the
applicant and/or owner to pay for, pick up and set up appropriate
inspections, shall be deemed 'Work performed prior to issuance
of permit' and subject to double the standard permit fees according
to the Village's Annual Fee Resolution,[1] and Section 14-14-6 of the Village Code."
Section 105.2 Work exempt from permit. Building:
Delete all and insert:
"1.
|
Painting, papering, tiling not in showers or bathtubs, carpeting,
finish flooring, and other similar finish work but not including cabinetry
and countertops where plumbing exists.
|
"2.
|
Swings and other playground equipment."
|
Section 105.2 Work exempt from permit. Electrical:
Delete all and insert:
"1.
|
Listed cord-and-plug connected temporary decorative lighting.
|
"2.
|
Reinstallation of attachment plug receptacles but not the outlets
therefor.
|
"3.
|
Replacement of branch circuit overcurrent devices of the required
capacity in the same location.
|
"4.
|
Minor repair work, including the replacement of lamps or the
connection of approved portable electrical equipment to approved permanently
installed receptacles."
|
Section 105.3 Application for permit.
Delete all and insert "To obtain a permit, the applicant shall
first file an application therefor in writing on a form furnished
by the Division of Building Safety for that purpose. Such application
shall:
"1.
|
Identify and describe the work to be covered by the permit for
which application is made.
|
"2.
|
Describe the land on which the proposed work is to be done by
legal description, street address or similar description that will
readily identify and definitely locate the proposed building or work.
|
"3.
|
Indicate the use and occupancy for which the proposed work is
intended.
|
"4.
|
Be accompanied by construction documents and other information
as required in Section R106.1.
|
"5.
|
State the valuation of the proposed work."
|
Section 105.5 Expiration.
Delete all and insert "Every permit issued shall become invalid
unless the work authorized by such permit is commenced within 180
days after its issuance or after commencement of work if more than
180 days pass between inspections. The Building Official is authorized
to grant, in writing, one permit renewal or reissuance, for a period
not to exceed 180 days. The renewal or reissuance shall be requested
in writing and justifiable cause demonstrated. The Village Manager
is authorized to grant, in writing, any subsequent permit renewals
or reissuances, for periods not to exceed 180 days. Any subsequent
renewals or reissuances shall be in writing and justifiable cause
demonstrated. However, no permit or approval shall be valid for a
period of more than one year after the date of issuance."
Add (new section) 105.5.1 Permit fee extension.
Insert "The Building Official is authorized to grant, in writing, one permit extension, for a period not to exceed 180 days. The extension shall be requested in writing and justifiable cause demonstrated using the approved form. The Village Manager is authorized to grant, in writing, any subsequent permit extensions, for periods not to exceed 180 days. Any subsequent extensions shall be in writing and justifiable cause demonstrated using the approved form. (Refer to Village's Annual Fee Resolution, and Section 14-2-3 of the Village Code)."
Add (new section) 105.5.2 Permit fee renewal.
Insert "There shall not be any fee for the first renewal or
reissuance of any permit that extends the validity of the initial
permit for a period not to exceed 180 days. The fee for any subsequent
renewal or reissuance of any permit that extends the validity of the
initial permit for additional periods not to exceed 180 days shall
be assessed at 25% of the original cost of the original permit."
Section 106.1 Submittal documents.
Delete all and insert "Construction documents for new single-family
dwellings, two-family dwellings, townhouse dwellings, duplex dwellings,
additions to dwelling units above the first floor, modifications which
alter the roof of a dwelling unit of a substantial scope as determined
by the Building Official, shall be signed and sealed by an Illinois
licensed architect or structural engineer."
Section 106.2 Site Plan or plot plan.
Delete all and insert "The construction documents submitted
with the application for permit shall be accompanied by a site plan
showing the size and location of new construction and existing structures
on the site and distances from lot lines. The site and grading plan
shall be submitted in both paper and electronic versions. In the case
of demolition, the site plan shall show construction to be demolished
and the location and size of existing structures and construction
that are to remain on the site or plot. The Building Official is authorized
to waive or modify the requirement for a site plan where the application
for permit is for alteration or repair or where otherwise warranted."
Section 108.2 Schedule of permit fees.
Delete all and insert "On buildings, structures, electrical,
gas, mechanical and plumbing systems or alterations requiring a permit,
a fee for each permit shall be paid as required, in accordance with
the schedule as established by the applicable governing authority.
See Village's Annual Fee Resolution."[2]
And insert lines (A, 1 through 2) as follows:
"A.
|
A fee for each plan examination, building permit and inspection
shall be paid prior to the issuance of permit(s) in accordance with
the following schedule:
| ||
"1.
|
Building permit fees are set forth in the Village's Annual
Fee Resolution. Whenever the cost of construction is a factor in determining
a permit or plan review fee, the valuation of building projects shall
be established based on the greater of:
| ||
"a.
|
The cost of construction established by the International Code
Council (ICC) and published on its website. The most current schedule
shall be used based upon ICC published data; or
| ||
"b.
|
The cost of construction as stated by the applicant or agent
on the application for the relevant permit.
| ||
"2.
|
Building plan review fees are set forth in the Village's
Annual Fee Resolution. Further, an Amendment Form is required to be
submitted detailing the changes for any revisions from previously
approved plans. For building plans that have been previously reviewed,
and the permit issued, any revisions to the building plan that, based
upon the changes proposed require the review of two or more disciplines,
a plan review fee for the Amendment Form is set forth in the Village's
Annual Fee Resolution."
|
Add (new section)108.2.1 Recovery of third-party fees.
Insert "The Village may recover all third-party vendor and consultant
fees incurred by the Village for residential plan review and residential
inspection. Said costs may be added to the permit fees or collected
prior to the issuance of a certificate of occupancy."
Add (new section) 109.1.6.2 Final storm sewer inspection.
Insert "A final inspection of the storm sewer, if installed,
shall be scheduled with and approved by the Public Works Department
prior to the issuance of a certificate of occupancy."
Add section 109.5 Final grading or topography survey.
Insert "If the topography of the land or property has been materially
altered in connection with any work completed thereon, a final grading/topography
survey, by an Illinois Land Surveyor, shall be submitted to the Village
for review prior to the issuance of a certificate of occupancy. The
survey shall be submitted in both paper and electronic versions and
shall include the location of the water meter."
Add (new section) 110.4.1 Deposit and compliance.
Insert "Prior to the granting of a temporary certificate of
occupancy, the applicant shall submit a deposit equal to 110% of the
cost of completion of all outstanding items necessitating the request
for a temporary certificate of occupancy. The deposit shall be forfeited
to the Village upon noncompletion of any outstanding items prior to
the expiration of the temporary certificate of occupancy."
Section 112 Board of Appeals.
Delete in its entirety and insert new section title "112
Appeals."
Add (new section) 112.1 General.
Insert lines (A, 1 through 3, B and C) as follows:
"A.
|
Any person shall have the right to appeal a decision of the
Building Official to the Village Manager. A letter for appeal shall
be based on a claim for one of the following three reasons:
| |
"1.
|
That the true intent of this code or the rules legally adopted
thereunder have been incorrectly interpreted, or
| |
"2.
|
The provisions of this code do not fully apply, or
| |
"3.
|
An equivalent or better method of construction is proposed.
| |
"B.
|
All appeals shall be filed within thirty days of the decision
of the Building Official.
| |
"C.
|
The Village Manager shall affirm, modify, or reverse the decision
of the Building Official."
|
Section 113.4 Violation penalties.
Delete all and insert "Any person who violates a provision of
this code or fails to comply with any of the requirements thereof
or who erects, constructs, alters or repairs a building or structure
in violation of the approved construction documents or directive of
the Building Official, or of a permit or certificate issued under
the provisions of this code, shall be subject to penalties as prescribed
by law or as set forth in the Village's Annual Fee Resolution."
Section 114.2 Unlawful continuance.
After paragraph insert "Violation of unlawful continuance is
subject to either penalties as prescribed by law or as set forth in
the Village's Annual Fee Resolution."
Add (new section) 114.3 Appeals.
Insert "Any permittee who is served with a stop-work order shall
have the right to appeal the issuance of the stop-work order to the
Village Manager, by filing a written appeal within seven days after
the issuance of the stop-work order. The Village Manager shall, within
seven days after receipt of the properly filed appeal, either (a)
affirm the issuance of the stop-work order, or (b) rescind or modify
the stop-work order. The failure of the Village Manager to render
a decision within seven days shall be deemed as an affirmance by the
Village Manager of the issuance of the stop-work order. All decisions
of the Village Manager made pursuant to this Section 114.3 shall be
final."
Table 301.2(1) Climatic and Geographic Design Criteria.
TABLE R301.2(1)
CLIMATE & GEOGRAPHIC DESIGN CRITERIA
| ||||||||||
---|---|---|---|---|---|---|---|---|---|---|
Wind Design
|
Seismic Design Categoryf
|
Subject to Damage From
|
Winter Design Temperaturee
|
Ice Barrier Underlayment Requiredh
| ||||||
Ground Snow Load
|
Speedd
(mph)
|
Topographic Effectsk
|
Special Wind Regioni
|
Wind borne Debris Zonem
|
Weatheringa
|
Frost Line Depthb
|
Termitec
| |||
30
|
90
|
NO
|
NO
|
NO
|
A
|
Severe
|
42 inches
|
Moderate to severe
|
Minus 4° F
|
Yes
|
TABLE R301.2(1) continued
CLIMATE & GEOGRAPHIC DESIGN CRITERIA
| |||||||||
---|---|---|---|---|---|---|---|---|---|
Flood Hazardsg
|
Aire Freezing Indexi
|
Mean Annual Temperaturej
|
Elevation
|
Latitude Winter Heating
|
Winter Heating
|
Summer Cooling
|
Altitude Correction Factor
|
Indoor Design Temperature
|
Design Temperature Cooling
|
Refer to local
|
1635
|
48.7° F
|
679 ft.
|
42.1
|
Minus 1° F
|
91° F
|
0
|
72° F maximum
|
75° F minimum
|
TABLE R301.2(1) continued
CLIMATE & GEOGRAPHIC DESIGN CRITERIA
| |||||||
---|---|---|---|---|---|---|---|
Heating Temperature Difference
|
Cooling Temperature Difference
|
Wind Velocity Heating
|
Wind Velocity Cooling
|
Coincident Wet Bulb
|
Daily Range
|
Winter Humidity
|
Summer Humidity
|
73° F
|
16° F
|
8.4 mph
|
5.7 mph
|
76
|
Medium 16°-25° F.
|
30%
|
50%
|
For SI: 1 pound per square foot = 0.0479 kPa, 1 mile per hour
= 0.447 m/s.
| |
a.
|
Where weathering requires a higher strength concrete or grade
of masonry than necessary to satisfy the structural requirements of
this code, the frost line depth strength required for weathering shall
govern. The weathering column shall be filled in with the weathering
index, negligible, moderate, or severe for concrete as determined
from Figure R301.2(4). The grade of masonry units shall be determined
from ASTMC34, C55, C62, C73, C90, C129, C145, C216 or C652.
|
b.
|
Where the frost line depth requires deeper footings than indicated
in Figure R403.1(1), the frost line depth strength required for weathering
shall govern. The jurisdiction shall fill in the frost line depth
column with the minimum depth of footing below finish grade.
|
c.
|
The jurisdiction shall fill in this part of the table to indicate
the need for protection depending on whether there has been a history
of local subterranean termite damage.
|
d.
|
The jurisdiction shall fill in this part of the table with the
wind speed from the basic wind speed map [Figure R301.2(5)A]. Wind
exposure category shall be determined on a site-specific basis in
accordance with Section R301.2.1.4.
|
e.
|
The outdoor design dry-bulb temperature shall be selected from
the columns of 971/2-percent values for winter from Appendix D of
the International Plumbing Code. Deviations from the Appendix D temperatures
shall be permitted to reflect local climates or local weather experience
as determined by the Building Official. [Also see Figure R301.2(1).]
|
f.
|
The jurisdiction shall fill in this part of the table with the
seismic design category determined from Section R301.2.2.1.
|
g.
|
The jurisdiction shall fill in this part of the table with (a)
the date of the jurisdiction's entry into the National Flood
Insurance Program (date of adoption of the first code or ordinance
for management of flood hazard areas), (b) the date(s) of the Flood
Insurance Study and (c) the panel numbers and dates of the currently
effective FIRMs and FBFMs or other flood hazard map adopted by the
authority having jurisdiction, as amended.
|
h.
|
In accordance with Sections R905.1.2, R905.4.3.1, R905.5.3.1,
R905.6.3.1, R905.7.3.1 and R905.8.3.1, where there has been a history
of local damage from the effects of ice damming, the jurisdiction
shall fill in this part of the table with YES. Otherwise, the jurisdiction
shall fill in this part of the table with NO.
|
i.
|
The jurisdiction shall fill in this part of the table with the
100-year return period air freezing index (BF-days) from Figure R403.3(2)
or from the 100-year (99 percent) value on the National Climatic Data
Center data table Air Freezing Index-USA Method (Base 32°F).
|
j.
|
The jurisdiction shall fill in this part of the table with the
mean annual temperature from the National Climatic Data Center data
table Air Freezing Index-USA Method (Base 32°F).
|
k.
|
In accordance with Section R301.2.1.5, where there is local
historical data documenting structural damage to buildings due to
topographic wind speed-up effects, the jurisdiction shall fill in
this part of the table with YES. Otherwise, the jurisdiction shall
indicate NO in this part of the table.
|
l.
|
In accordance with Figure R301.2(5)A, where there is local historical
data documenting unusual wind conditions, the jurisdiction shall fill
in this part of the table with YES and identify any specific requirements.
Otherwise, the jurisdiction shall indicate NO in this part of the
table.
|
m.
|
In accordance with Section R301.2.1.2 the jurisdiction shall
indicate the wind-borne debris wind zone(s). Otherwise, the jurisdiction
shall indicate NO in this part of the table.
|
n.
|
The jurisdiction shall fill in these sections of the table to
establish the design criteria using Table 1a or 1b from ACCA Manual
J or established criteria determined by the jurisdiction.
|
o.
|
The jurisdiction shall fill in this section of the table using
the Ground Snow Loads in Figure R301.2(6).
|
Section 302.1 Exterior walls.
Delete all and insert "Construction, projections, openings and
penetrations of exterior walls of dwellings and accessory buildings
shall comply with Table R302.1(1); or dwellings equipped throughout
with an automatic sprinkler system installed in accordance with NFPA
13D with Table 302.1(2).
"Exceptions:
| |
"1.
|
Walls, projections, openings, or penetrations in walls perpendicular
to the line used to determine the fire separation distance.
|
"2.
|
Detached garages accessory to a dwelling located within 2 feet
(610 mm) of a lot line are permitted to have roof eave projections
not exceeding 4 inches (102 mm).
|
"3.
|
Foundation vents installed in compliance with this code are
permitted."
|
Add (new section) 302.1.1 Accessory buildings.
Insert "Accessory buildings, with an area over 144 sq. ft.,
located within 15 feet of a residential dwelling shall have a one-hour
fire-resistance-rated wall and ceiling throughout the entire accessory
structure."
TABLE R302.1(1)
EXTERIOR WALLS
| |||
---|---|---|---|
Exterior Wall Element
|
Minimum Fire-Resistance Rating
|
Minimum Fire Separation Distance
| |
Walls
|
Fire-resistance rated
|
1 hour - tested in accordance with ASTM E 119
or UL 263 with exposure from both sides
|
< 15 feet
|
Not fire-resistance rated
| |||
Projections
|
Not allowed
|
N/A
|
< 2 feet
|
Fire-resistance rated
|
1 hour on the undersidea, b
|
< 2 feet to < 5 feet
| |
Not fire-resistance rated
|
0 hours
|
< 5 feet
| |
Openings in walls
|
Not allowed
|
N/A
|
< 3 feet
|
25% maximum of wall area
|
0 hours
|
3 feet
| |
Unlimited
|
0 hours
|
5 feet
| |
Penetrations
|
All
|
Comply with Section R302.4
|
< 3 feet
|
None required
|
< 3 feet
|
For SI: 1 foot = 304.8 mm.
| |
NA = Not Applicable.
| |
a.
|
The fire-resistance rating shall be permitted to be reduced
to 0 hours on the underside of the eave overhang if fireblocking is
provided from the wall top plate to the underside of the roof sheathing.
|
b.
|
The fire-resistance rating shall be permitted to be reduced
to 0 hours on the underside of the rake overhang where gable vent
openings are not installed.
|
TABLE R302.1(2)
EXTERIOR WALLS - DWELLINGS WITH FIRE SPRINKLERS
| |||
---|---|---|---|
Exterior Wall Element
|
Minimum Fire-Resistance Rating
|
Minimum Fire Separation Distance
| |
Walls
|
Fire-resistance rated
|
1 hour - tested in accordance with ASTM E 119
or UL 263 with exposure from the outside
|
< 15 feet
|
Not fire-resistance rated
| |||
Projections
|
Not allowed
|
N/A
|
< 2 feet
|
Fire-resistance rated
|
1 hour on the undersideb, c
|
2 feeta
| |
Not fire-resistance rated
|
0 hours
|
3 feet
| |
Not allowed
|
N/A
|
< 3 feet
| |
Unlimited
|
0 hours
|
3 feeta
| |
Penetrations
|
All
|
Comply with Section R302.4
|
< 3 feet
|
None required
|
3 feet
|
For SI: 1 foot = 304.8 mm.
| |
NA = Not Applicable.
| |
a.
|
For residential subdivisions where all dwellings are equipped
throughout with an automatic sprinkler system installed in accordance
with NFPA 13D, the fire separation distance for exterior walls not
fire-resistance rated and for fire-resistance-rated projections shall
be permitted to be reduced to 0 feet, and unlimited unprotected openings
and penetrations shall be permitted, where the adjoining lot provides
an open setback yard that is 6 feet or more in width on the opposite
side of the property line.
|
b.
|
The fire-resistance rating shall be permitted to be reduced
to 0 hours on the underside of the eave overhang if fireblocking is
provided from the wall top plate to the underside of the roof sheathing.
|
c.
|
The fire-resistance rating shall be permitted to be reduced
to 0 hours on the underside of the rake overhang where gable vent
openings are not installed.
|
Section 302.2 Townhouses. Number 1.
Delete all and insert "Where a fire sprinkler system in accordance
with NFPA 13D is provided, the common wall shall be not less than
a two-hour fire-resistance-rated wall assembly tested in accordance
with ASTM E 119 or UL 263."
Section 302.2 Townhouses. Number 2.
Delete all and insert "Where a fire sprinkler system in accordance
with NFPA 13D is not provided, the common wall shall be not less than
a two-hour fire-resistance-rated wall assembly tested in accordance
with ASTM E 119 or UL 263."
TABLE R302.6
DWELLINGS-GARAGE SEPARATION
| |
---|---|
Separation
|
Material
|
From the residence and attics
|
Not less than 5/8-inch gypsum board or equivalent applied to
the garage side
|
From habitable rooms above garages
|
Not less than 5/8-inch Type X gypsum board or equivalent
|
Structure(s) supporting floor/ceiling assemblies used for separation
required by this section
|
Not less than 5/8-inch gypsum board or equivalent
|
Garages located less than 3 feet from a dwelling unit on the
same lot
|
Not less than 5/8-inch gypsum board or equivalent applied to
the interior side of exterior walls that are within this area
|
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
|
Section 303.4 Mechanical ventilation.
Delete all and insert "Where the air infiltration rate of a
dwelling unit is 5 air changes per hour or less where tested with
a blower door at a pressure of 0.2 inch w.c (50 Pa) in accordance
with the 2018 Illinois Energy Conservation Code Section R402.4.1.2,
the dwelling unit shall be provided with whole-house mechanical ventilation
in accordance with Section M1505.4.
Section 309.5 Fire sprinklers.
Delete all and insert "Private garages shall be protected by
fire sprinklers where the garage wall has been designed based on Table
R302.1(2), Note a. Sprinklers in garages shall be connected to an
automatic sprinkler system in accordance with NFPA 13D. Garage sprinklers
shall be residential sprinklers or quick-response sprinklers, designed
to provide a density of 0.05 gpm/ft2. Garage doors shall not be considered
obstructions with respect to sprinkler placement.
Section 310.4 Bars, grilles, covers and screens.
Delete all and insert "Bars, grilles, covers, screens or similar
devices shall be placed over emergency escape and rescue openings,
area wells, or window wells, and the minimum net clear opening size
shall comply with Sections R310.2.1 through R310.2.3, and such devices
shall be releasable or removable from the inside without the use of
a key, tool, special knowledge or force greater than that required
for the normal operation of the escape and rescue opening.
Add (new section) 312.1.5 Design.
Insert "Guards shall not be designed or installed in such a
manner as to create a ladder effect."
Section 313.1 Townhouse automatic fire sprinkler systems.
Exception:
Delete all and insert "For additions, alterations or remodeling
of townhouses, refer to the 2018 International Life Safety Code adopted
amendments Section 43.6.4.1, 43.6.4.2 and 43.8.1.1"
Section 313.1.1 Design and installation.
Delete all and insert "Automatic residential fire sprinkler
systems for townhouses shall be designed and installed in accordance
with NFPA 13D."
Section 313.2 One- and two-family dwellings automatic
fire systems. Exception:
Delete all and insert "For additions, alterations or remodeling
of one- and two-family dwellings, refer to the 2018 International
Life Safety Code adopted amendments Section 43.6.4.1, 43.6.4.2 and
43.8.1.1"
Section 313.2.1 Design and installation.
Delete all and insert "Automatic residential fire sprinkler
systems shall be designed and installed in accordance with NFPA 13D."
Section 320 Accessibility.
Delete in its entirety.
Section 321.3 Accessibility.
Delete all and insert "Elevators or platform lifts that are
part of an accessible route shall comply with the 2018 Illinois Accessibility
Code and the 2017 ICC A117.1 Accessible and Usable Buildings and Facilities."
Section 322.1.7 Protection of water supply and sanitary
sewer system.
Delete all and insert "New and replacement water supply systems shall be designed to minimize or eliminate infiltration of floodwaters into the systems in accordance with the plumbing provisions of this code. New and replacement sanitary sewage systems shall be designed to minimize or eliminate infiltration of floodwaters into systems and discharges from systems into floodwaters in accordance with the 2014 Illinois Plumbing Code and the Village of Lincolnwood Ordinance Chapter 12 Water and Sewers."
Section 401.3 Drainage.
Delete all and insert "Surface drainage shall utilize
methods of conveyance and/or detention to manage stormwater in a way
that does not create adverse impacts on neighboring properties. Lots shall be graded to drain surface water away from foundation
walls. The grade shall fall not fewer than six inches (152 mm) within
the first 10 feet (3048 mm)."
Section 401.4 Soil tests.
Delete all and insert "Where quantifiable data created by accepted
soil science methodologies indicate expansive soils, compressible
soils, shifting soils or other questionable soil characteristics are
likely to be present, the Building Official shall determine whether
to require a soil test to determine the soil's characteristics
at a particular location. This test shall be done by an approved agency
using an approved method.
"Where the top of a proposed concrete floor slab is set at 8'
0" below grade, soil borings shall be performed and a geotechnical
report showing the determination of seasonally high water tables shall
be provided to the Village. Based on those determinations, a drainage
plan shall be provided at time of permit submittal that demonstrates
how groundwater discharge will be mitigated without negative impacts
to the public right-of-way or adjacent properties to the satisfaction
of the Village Engineer."
Add (new section) 401.4.3 Bracing, shoring and reinforcement
requirements.
Insert "For any excavation greater than three feet in depth
occurring within five feet of any property line or right-of-way, the
owner of the property to be excavated shall reinforce or brace adjacent
land, buildings and structures so as to prevent any sagging, settling,
cracking or collapse occurring to the adjacent land, sidewalks, fences,
structures, foundations or walls. Where bracing, shoring or reinforcement
is required because of the depth of excavation and distance to the
property line or right-of-way, and where that excavation is less than
five feet in depth, an Illinois-licensed architect or professional
engineer shall design such bracing, shoring or reinforcement, and
shall stamp and seal the plans therefor. Where that excavation is
five feet or greater in depth, an Illinois-licensed structural engineer
shall design such bracing, shoring or reinforcement, and shall stamp
and seal the plans therefor. Installation of the bracing, shoring
or reinforcement shall be in accordance with such design requirements
and as directed by the structural or professional engineer. The owner
of the property to be excavated shall be responsible for the cost
of any required bracing, shoring or reinforcement."
Section 402.1 Wood foundations.
Delete in its entirety.
Section 403.1 General.
Delete all and insert "All exterior walls shall be supported
on continuous solid or fully grouted masonry or concrete footings,
or other approved structural systems that shall be of sufficient design
to accommodate all loads according to Section R301 and to transmit
the resulting loads to the soil within the limitations as determined
from the character of the soil. Footings shall be supported on undisturbed
natural soils or engineered fill. Concrete footing shall be designed
and constructed in accordance with the provisions of Section R403
or in accordance with ACI 332."
Section 403.1.1 Minimum size.
Delete "Footings for wood foundations shall be in accordance
with the details set forth in Section R403.2, and Figures R403.1(2)
and R403.1(3)."
Figure R403.1(2) Permanent Wood Foundation Basement Wall
Section.
Delete in its entirety.
Figure R403.1(3) Permanent Wood Foundation Crawl Space
Section.
Delete in its entirety.
Section 403.1.4.1 Frost Protection.
Delete all and insert "Except where otherwise protected from
frost, foundation walls, piers and other permanent supports of buildings
and structures shall be protected from frost by one or more of the
following methods:
"1.
|
Extended below the frost line specified in Table R301.2.(1).
|
"2.
|
Erected on solid rock.
|
"Footings shall not bear on frozen soil unless the frozen condition
is permanent.
| |
"Exceptions:
| |
"1.
|
Protection of freestanding accessory structures with an area
of 400 square feet (56 m2) or less, of light-frame construction, with
an eave height of 10 feet (3,048 mm) or less shall not be required.
|
"2.
|
Protection of freestanding accessory structures with an area
of 400 square feet (37 m2) or less, of other than light-frame construction,
with an eave height of 10 feet (3,048 mm) or less shall not be required.
|
"3.
|
Protection of decks, not as a part of a required landing, step
or stair, under 120 sq. ft., and not supported by a dwelling need
not be provided with footings that extend below the frost line."
|
Section 403.2 Footings for wood foundations.
Delete all.
Section 404.1 Concrete and masonry foundation walls.
Delete and insert "Concrete foundation walls shall be selected
and constructed in accordance with the provisions of Section R404.1.3.
Masonry foundation walls shall be selected and constructed in accordance
with the provisions of Section R404.1.2.
"Section R404 shall be applicable when engineering reports show
soils that are within the categories applicable to this Section R404
and design criteria for lateral support will be addressed by the design
professional."
Section 404.2 Wood foundation walls.
Delete in its entirety.
Section 405.2 Wood foundations.
Delete in its entirety
Section 406.3 Dampproofing for wood foundations.
Delete in its entirety.
Section 502.1.2 Prefabricated wood I-joists.
Delete all and insert "Structural capacities and design provisions
for prefabricated wood I-joists shall be established and monitored
in accordance with ASTM D5055.
"In the event that prefabricated wood I-joists or other engineered
open-web wood trusses are used for the construction of a floor-ceiling
assembly, the engineered trusses or I-joists shall be protected by
a one-hour fire-resistance-rated assembly."
Section 507.1 Decks.
Delete all and insert "Wood-framed decks shall be in accordance
with this section, the 2015 or most current AWC DCA6 Prescriptive
Residential Wood Deck Construction Guide, the ICC Deck Construction
guide based on the 2021 International Residential Code or Section
301 for materials and conditions not prescribed herein. Where supported
by attachment to an exterior wall, decks shall be positively anchored
to the primary structure and designed for both vertical and lateral
loads.
"Such attachment shall not be accomplished by use of toenails
or nails subject to withdrawal. Where positive connection to the primary
building structure cannot be verified during inspection, decks shall
be self-supporting. For decks with cantilevered framing members, connections
to exterior walls or other framing members shall be designed and constructed
to resist uplift resulting from the full live load specified in Table
R301.5 acting on a cantilevered portion of the deck."
Section 602.4 Interior load-bearing walls.
Delete all and insert "Interior load-bearing walls shall be
constructed, framed and fireblocked as specified for exterior walls.
Interior load-bearing walls that contain plumbing fixtures, flues
or ducts shall be constructed of a minimum two-inch by six-inch lumber."
Section 602.5 Interior nonbearing walls.
Delete all and insert "Interior nonbearing walls shall be permitted
to be constructed with 2-inch by 3-inch (51 mm by 76 mm) studs spaced
24 inches (610 mm) on center or, where not part of a braced wall line,
2-inch by 4-inch (51 mm by 102 mm) flat studs spaced at 16 inches
(406 mm) on center. Interior nonbearing walls that contain plumbing
fixtures, flues or ducts shall be constructed of a minimum two-inch
by six-inch lumber. Interior nonbearing walls shall be capped with
not less than a single top plate. Interior nonbearing walls shall
be fireblocked in accordance with Section R602.8."
Add (new section) Section 703.1.3 Application of other
laws.
Insert "The provisions of this section shall not be deemed to nullify any provisions of the Zoning Ordinance Chapter 15 or any other ordinance, law or statute of the Village pertaining to the exterior locations or allowed percentages of specific exterior covering materials. All exterior walls shall be constructed in accordance with the applicable standards set forth in the Village of Lincolnwood Zoning Ordinance Chapter 15."
Add (new section) Section 806.3.1 Insulation Baffles.
Insert "Where eave vents are provided, insulation baffles shall
be installed between the rafters at the eaves to maintain air flow
from the soffit vents."
Chapter 11 [RE] Energy Efficiency.
Delete in its entirety.
Section 2406.2 (303.3) Prohibited locations.
Delete all and insert "Appliances shall not be located in sleeping
rooms, bathrooms, toilet rooms, storage closets, crawl spaces or surgical
rooms, or in a space that opens only into such rooms or spaces, except
where the installation complies with one of the following:"
Part VII Plumbing
Chapter 25 Plumbing Administration.
Delete in its entirety.
Chapter 26 General Plumbing Requirements.
Delete in its entirety.
Chapter 27 Plumbing Fixtures.
Delete in its entirety.
Chapter 28 Water Heaters.
Delete in its entirety.
Chapter 29 Water Supply and Distribution.
Delete in its entirety.
Chapter 30 Sanitary Drainage.
Delete in its entirety.
Chapter 31 Vents.
Delete in its entirety.
Chapter 32 Traps.
Delete in its entirety.
Chapter 33 Storm Drainage.
Delete in its entirety.
Part VIII Electrical
Chapter 34 General Requirements.
Delete in its entirety.
Chapter 35 Electrical Definitions.
Delete in its entirety.
Chapter 36 Services.
Delete in its entirety.
Chapter 37 Branch Circuit and Feeder Requirements.
Delete in its entirety.
Chapter 38 Wiring Methods.
Delete in its entirety.
Chapter 39 Power and Lighting Distribution.
Delete in its entirety.
Chapter 40 Devices and Luminaires.
Delete in its entirety.
Chapter 41 Appliance Installation.
Delete in its entirety.
Chapter 42 Swimming Pools.
Delete in its entirety.
Chapter 43 Class 2 Remote-Control Signaling and Power-Limited
Circuits.
Delete in its entirety.
Appendix F, Passive Radon Gas Controls, as set forth in the
International Residential Code for One- and Two-Family Dwellings is
hereby adopted by reference and is hereby made a part of this Article
3 with the same force and effect as if fully set forth herein.
Appendix H, Patio Covers, as set forth in the International
Residential Code for One- and Two-Family Dwellings is hereby adopted
by reference and is hereby made a part of this Article 3 with the
same force and effect as if fully set forth herein.