The purpose of this article is:
A. To protect the public potable water supply of the City of Rensselaer
from the possibility of contamination by isolating within its customers'
internal distribution systems or its customers' private water systems
such contaminations or pollutants which could backflow into the public
water supply system; and
B. To comply with the requirements of the New York State Sanitary Code
5-1.31.
For the purpose of this article, unless it is plainly evident
from the context that a different meaning is intended, certain terms
used herein are defined as follows:
AIR GAP SEPARATION
A physical break between a supply pipe and a receiving vessel.
The air gap shall be at least double the diameter of the supply pipe,
measured vertically above the tip rim of the vessel, and in no case
less than one inch.
APPROVED DOUBLE CHECK VALVE ASSEMBLY
An assembly of at least two independently acting approved
single check valves, including tightly closing shutoff valves on each
side of the check valve assembly and suitable test cocks plus connections
available for testing and watertightness of each valve.
APPROVED REDUCED PRESSURE PRINCIPLE BACKFLOW PREVENTION DEVICE
(RPZ)
A device incorporating two or more single check valves and
an automatically operating differential relief valve located between
the two checks, two shutoff valves, and equipped with necessary appurtenances
for testing. The device shall operate to maintain the pressure in
the zone between the two check valves, less than the pressure on the
public water supply side of the device. At cessation of normal flow,
the pressure between the check valves shall be less than the supply
pressure. In case of leakage of either check valve, the differential
relief valve shall operate to maintain this reduced pressure by discharging
to the atmosphere. When the inlet pressure is two pounds per square
inch or less, the relief valve shall open to the atmosphere, thereby
providing an air gap in the device. To be approved, these devices
must be readily accessible for maintenance and testing and installed
in a location where no part of the device will be submerged.
APPROVED SINGLE CHECK VALVE
A check valve that seats readily and completely. It must
be carefully machined to have free-moving parts and assured watertightness.
The face of the closure element and valve sear must be bronze, composition,
or other noncorrodible material which will seat tightly under all
prevailing conditions of field use. Pins and bushings shall be of
bronze or other noncorrodible, nonsticking material, machined for
easy, dependable operation. The closure element (e.g., clapper) shall
be internally weighted or otherwise internally equipped to promote
rapid and positive closure in all sizes where this feature is obtainable.
APPROVED WATER SUPPLY
Any water supply approved by, or under the public health
supervision of, a public health agency of the State of New York, County
of Rensselaer, or the City of Rensselaer. In determining what constitutes
an approved water supply, the Department of Public Health of the State
of New York (herein called "State Health Department") shall have the
final judgment as to its safety and potability.
BACKFLOW
A flow condition, induced by a differential in pressure,
that causes the flow of water or other liquids and/or gases into the
distribution pipes of a public water supply from any source other
than its intended source.
CITY
The City of Rensselaer.
CITY WATER SUPPLY
An approved water supply sold and delivered to consumers'
premises through the water distribution system of the City of Rensselaer.
COMMISSIONER
The Commissioner of Public Works of the City of Rensselaer,
or his authorized representatives.
CONSUMER
Any person to whom water is sold and/or furnished from the
City of Rensselaer.
CONTAMINATION
An impairment of the quality of the City water supply by
the presence of any foreign substance (organic, inorganic, radiological
or biological) to a degree which creates a hazard to the public health.
COUNTY HEALTH OFFICER
The Rensselaer County Health Officer, his assistants, or
authorized deputies acting as, or any other person appointed as Health
Officer of the County of Rensselaer.
CROSS-CONNECTION
Any unprotected connection between any part of the City water
distribution system used or intended to supply water for drinking
purposes and any source or system containing water or a substance
that is not or cannot be approved as safe, wholesome and potable for
human consumption.
NONTOXIC SUBSTANCE
Any substance of a nonpoisonous nature that may create a
moderate or minor hazard to the water supply system.
PERSON
Any natural person, firm, association, organization, partnership,
trust or association of persons, joint venture, corporation or company,
and includes the United States, the State of New York, the County
of Rensselaer, and special purpose district, and any officer or agent
thereof.
PREMISES
Integrated land area, including improvements thereon, undivided
by public thoroughfares or water distribution mains of the City of
Rensselaer and where all parts of the premises are operated under
the same management and for the same purpose.
PROTECTIVE DEVICE
Any of the following devices:
B.
Approved reduced pressure principle backflow prevention device
(RPZ).
C.
Approved double check valve assembly.
D.
Approved single check valve assembly.
SERVICE CONNECTION
The terminal end of a service connection from the City water
supply at its point of delivery to the consumer. If a meter is installed,
"service connection" means the downstream end of the meter. No unprotected
takeoffs from the service line ahead of any meter or backflow protective
device located at the point of delivery to the consumer shall be permitted.
SHALL
Is mandatory; "may" is permissive.
TOXIC SUBSTANCE
Any substance (liquid, solid or gaseous), including raw sewage
and lethal substances, that when introduced into the water supply
system creates or may create a danger to the health and well being
of the consumer.
The City of Rensselaer Water Department may at any reasonable
time inspect any facility in order to determine if a hazard exists
due to an actual or potential cross-connection between the water system
and any potential source of contamination. In any case where the Commissioner
deems such hazard to exist, he may require the property owner to install
an approved backflow prevention device in every water service line
to the facility for which a potential hazard exists. Such devices
shall be installed at or as near the service connection as may be
required by the Commissioner. Such backflow preventer shall be designed
and installed in accordance with all regulations of Part 5, 1.31,
of the New York State Sanitary Code, and must be approved by the Commissioner
and the New York State Health Department prior to installations. All
costs of installation and maintenance shall be borne by the property
owner.
The following is a partial list of facilities that are especially
likely to have cross-connection hazards:
A. Auxiliary water supply. Each service connection from the City water
supply for furnishing water to premises having an auxiliary water
supply shall be protected against backflow of water from the premises
in the City water supply.
(1) If the auxiliary water supply is handled in a separate piping system
with no known cross-connections, the City water supply shall be protected
by an approved double check valve assembly installed at the service
connection to the premises. When the auxiliary water supply may be
contaminated, the Commissioner may order the City water supply protected
by an air gap separation or an approved RPZ installed at the service
connection.
(2) If the auxiliary water supply is handled in a separate piping system
and cross-connections are known to exist between the City water supply
and the auxiliary water supply which cannot presently be eliminated,
the City water supply shall be protected by an approved RPZ installed
at the service connection to the premises. When the auxiliary water
supply may be contaminated, the Commissioner may order the City water
supply protected by an air gap separation installed at the service
connection.
B. Toxic or hazardous substances under pressure. At the service connection
to any premises on which any material dangerous to health or toxic
substance in toxic concentration is or may be handled under pressure,
the City water supply shall be protected by an air gap separation.
The air gap shall be located as close as practicable to the water
meter, and all piping between the water meter and receiving tank shall
be entirely visible. If these conditions cannot reasonably be met,
the City water supply shall be protected with an approved RPZ which
is acceptable to both the Commissioner and the County Health Officer.
C. Toxic or hazardous substances not under pressure. At the service
connection to any premises on which any material dangerous to health
or toxic substance in toxic concentration is not handled under pressure
but is otherwise handled in such a manner as to constitute a cross-connection,
the City water supply shall be protected by an approved RPZ unless
such cross-connection is abated to the satisfaction of the Commissioner
and approved by the County Health Officer.
D. Nonhazardous substances. At the service connection to any premises
on which a substance that would be objectionable (but not necessarily
hazardous to health) if introduced into the City water supply is handled
in such a manner as to constitute a cross-connection, the City water
supply shall be protected by an approved double check valve assembly.
E. Sewage and storm drain treatment plants and pumping stations. At
the service connection to any sewage treatment plant or sewage pumping
station, the City water supply shall be protected by an air gap separation.
The air gap shall be located as close as practicable to the service
connection, and all piping between the service connection and receiving
tank shall be entirely visible. If these conditions cannot be reasonably
met, the City water supply shall be protected with an approved RPZ,
provided this alternative is acceptable to both the Commissioner and
the County Health Officer. A final decision in this matter shall be
made by the State Health Department.
F. Fire systems. At the service connection to any premises in which
a fire protection system is installed, the City water supply shall
be protected based on the water source and arrangement of supplies
in accordance with the following classifications:
(1) Class 1.
(a) Direct connection from public water mains only; no pumps, tanks or
reservoirs; no physical connections from auxiliary water supplies;
no antifreeze or other additives of any kind; all sprinkler drains
discharging to atmosphere, dry wells, or other safe outlets.
(b) Protection: none, other than the check valve required by the National
Fire Code.
(2) Class 2.
(a) Same as Class 1, except booster pumps may be installed in the connections
from the street mains.
(b) Protection: none, other than the check valve required by the National
Fire Code.
(3) Class 3.
(a) Direct connection from public water supply main plus one or more
of the following: elevated storage tanks; fire pumps taking suction
from aboveground covered reservoirs or tanks; and pressure tanks.
(b) Protection: double check valve assembly.
(4) Class 4.
(a) Directly supplied from public mains similar to Classes 1 and 2, and
with an auxiliary water supply on or available to the premises; or
an auxiliary supply may be located within 1,700 feet of the pumper
connection.
(b) Protection: air gap or RPZ.
(5) Class 5.
(a) Directly supplied from public mains, and interconnected with auxiliary
supplied, such as pumps taking suction from reservoirs exposed to
contamination, or rivers and ponds; driven wells; mills or other industrial
water systems; or where antifreeze or other additives are used.
(b) Protection: air gap or RPZ.
(6) Class 6.
(a) Combined industrial and fire protection systems supplied from the
public water mains only, with or without gravity storage or pump suction
tanks.
(b) Protection: determined by the Commissioner upon review of engineering
drawings of the system.
G. Lawn sprinkling systems. At the service connection to any permanently
installed, belowgrade lawn sprinkling system, the City water supply
shall be protected by an approved RPZ assembly.
H. Others. Examples of other facilities which require cross-connection
control include, but are not limited to:
(1) Beverage bottling plants.
(4) Chemical plants and plating facilities.
(6) Hospitals, medical buildings, sanitariums, morgues and mortuaries.
(10)
Metal manufacturing, cleaning and fabricating plants.
(11)
Radioactive materials production or research plants.
(12)
Restricted, classified or other facilities closed to inspection.
(13)
Sewage and storm drain facilities.
(14)
Buildings heated by boilers where treatment chemicals are used.
(15)
Buildings with certain types of air-conditioning systems.
The consumer on whose premises any protective device is installed
shall have each such device inspected and tested annually. Inspection
and tests shall be performed under the supervision of a tester certified
by the Department of Health. If successive inspections disclose repeated
failures in the operation of any device, the Commissioner may require
more frequent inspections. Each device shall be repaired, overhauled
or replaced at the expense of the consumer whenever it is found to
be defective. Records of such tests, repairs, and overhauls shall
be kept and a copy of such record forwarded to the Commissioner on
an annual basis. The Commissioner shall have the duty of determining
that the inspections required herein are performed properly. If, following
demand therefor, the consumer fails to have any of the inspections
made as required herein or to make the above-described records available,
the Commissioner shall have the right to inspect the device and the
consumer shall pay the cost thereof. The cost of any inspection made
by the Commissioner shall be billed to the consumer.
All presently installed prevention devices which do not meet the requirements of this article but were approved devices for the purposes described herein at the time of installation and which have been properly maintained shall, except for the inspection and maintained requirements under §
175-19, be excluded from the requirements of these rules so long as the Commissioner is assured that they will satisfactorily protect the City's water supply. Whenever the existing device is moved from the present location or requires more than minimum maintenance which constitutes a hazard to health, the unit shall be replaced by a backflow prevention device meeting the requirements of this article.
The Water Department is authorized to enter into restrictive
covenant agreements with various commercial, industrial and residential
facilities regarding the installation of backflow prevention devices
on their real property. These agreements shall allow backflow prevention
devices to be installed in the main building with a meter at the property
line as long as there are no taps between the meter and the main building,
while requiring that if a tap is installed between the meter and the
main building, then backflow prevention devices must be removed to
the property line. These agreements shall be binding on all successors
to the property, and may be dischargeable by the Water Department
whenever such backflow prevention devices are no longer required by
law or ordinance for said property. The agreements shall contain such
additional terms and conditions as the Water Department deems to be
appropriate.
This article shall be in full force and effect 30 days after
its adoption.