[1]
Editor's Note: Ord. No. 1100, adopted April 20, 1992, amended the Code by adding a new Art. V, §§ 18-58—18-62, to Ch. 18. In order to conform to established Code format, and in order to provide for the expansion of Art. IV without the necessity of adding point numbers, the editor, at his discretion, has renumbered these provisions as §§ 18-6818-72. The original numbers of these provisions have been preserved in the history notes following each section and in the Code Comparative Table at the back of this volume in order to facilitate tracking.
[Ord. No. 1100, § 1(18-58), 4-20-1992]
No water shall be provided for internal or external use to any residential, commercial, industrial, agricultural, recreational, governmental, or public building or structure of any kind which is constructed or remodeled and in which plumbing, water piping or water fixtures are to be installed, extended or altered in any way, and for which construction a permit is required to be obtained from township (or would be required but for an exemption from a permit requirement for public or governmental agencies) unless the new, extended or altered plumbing, water piping and other water-using fixtures therein conform to the requirements and standards of this article. The provisions of this article shall apply to any such building or structure for which such a building permit is issued or would otherwise be required to be issued but for such an exemption.
[Ord. No. 1100, § 1(18-59), 4-20-1992]
(a) 
Water closets and associated flushing mechanisms. The water consumption of water closets shall not exceed an average of one and six-tenths (1.6) gallons per flush cycle over a range of test pressures from twenty (20) to eighty (80) psi. The fixture shall perform in accordance with the test requirements of the ANSI A112.19.2M and ANSI A112.19.6M.
(b) 
Urinals and associated flushing mechanisms. Urinal water consumption shall not exceed an average of one and one-half (1.5) gallons per flush cycle over a range of test pressures from twenty (20) to eighty (80) psi. The fixtures shall perform in accordance with the test requirements of ANSI A112.19.2M and ANSI A112.19.6M.
(c) 
Showerheads. Showerhead discharge rates shall not exceed three (3) gallons of water per minute over a range of test pressures from twenty (20) to eighty (80) psi. The fixture shall perform in accordance with the test requirements of ANSI A112.18.1M.
(d) 
Faucets. Sink and lavatory faucet discharge rates shall not exceed three (3) gallons of water per minute over a range of test pressures from twenty (20) to eighty (80) psi. The fixture shall perform in accordance with the test requirements of ANSI A112.18.1M.
[Ord. No. 1100, § 1(18-60), 4-20-1992]
(a) 
Special purpose equipment. The performance standards of section 18-69 shall not apply to fixtures and fittings such as emergency showers, aspirator faucets and blowout fixtures that, in order to perform a specialized function, cannot meet the specified standards.
(b) 
Exemptions. Any person(s) may apply to the township for an exemption to the terms of this article, which may be granted by council upon proof that some other device, system or procedure will save as much or more water as those set forth herein or that those set forth herein cannot be complied with without undue hardship.
[Ord. No. 1100, § 1(18-61), 4-20-1992]
Council may, from time to time, modify, add to or remove from the standards and restrictions herein.
[Ord. No. 1100, § 1(18-62), 4-20-1992]
If any person uses or applies water within the township contrary to or in violation of the restrictions herein, upon conviction thereof, such person shall be punished as set forth in section 1-9 under this Plymouth Township Code.