R106.3.1 Approval of construction documents. Where
the Building Official issues a permit, the construction documents
shall be approved in writing or by a stamp that states "REVIEWED FOR
CODE COMPLIANCE." One set of construction documents so reviewed shall
be retained by the Building Official. The other set may be kept at
the site of work or made available at the time of inspection and shall
be open to inspection by the Building Official or a duly authorized
representative.
| |
R108.6 Work commencing before permit issuance. Any
person who commences work requiring a permit on a building, structure,
electrical, gas, mechanical or plumbing system before obtaining the
necessary permits shall be subject to a fee established by the applicable
governing authority that shall be in addition to the required permit
fees.
| |
Exceptions:
| |
1. Earthwork.
| |
2. Stakeouts and other necessary planning procedures.
| |
SECTION R202 DEFINITIONS
| |
Revise as follows:
| |
PAN FLASHING. Corrosion-resistant flashing at the
base of an opening that is integrated into the building exterior wall
to direct water to the exterior.
| |
TABLE R301.2(1): CLIMATIC AND GEOGRAPHIC DESIGN CRITERIA. The following values shall be entered into the table and footnotes
B and H to the table are amended as follows:
|
Ultimate Wind Speed:
|
115 (51)
| |
Ground Snow Load:
|
20
| |
Wind Design Speed:
|
90
| |
Wind Topographic Effects:
|
No
| |
Special Wind Region:
|
No
| |
Wind-Borne Debris Zone:
|
No
| |
Seismic Design Category:
|
B
| |
Weathering:
|
Severe
| |
Frost Line Depth:
|
30 inches
| |
Termite:
|
Moderate to Heavy
| |
Winter Design Temp:
|
6
| |
Ice Barrier Underlayment Required:
|
No
| |
Flood Hazards:
|
09-29-2010
| |
Air Freezing Index:
|
1000
| |
Mean Annual Temp:
|
56.3
|
Footnotes B and H are amended to read as follows:
| ||
B. The frost line depth may require deeper footings than indicated
in Figure R403.1(1). The jurisdiction shall fill in the frost line
depth column with thirty (30) inches, the minimum depth of footing
below finish grade.
| ||
H. The jurisdiction shall fill in this part of the table with
"No."
| ||
R302.1 Exterior walls. Construction, projections,
openings and penetrations of exterior walls of dwellings and accessory
buildings shall comply with Table R302.1(1) as amended; or dwellings
equipped throughout with an automatic sprinkler system installed in
accordance with Section P2904 shall comply with Table R302.1(2).
| ||
Exceptions:
| ||
1.
|
Walls, projections, openings or penetrations in walls perpendicular
to the line used to determine the fire separation distance.
| |
2.
|
Walls of dwellings and accessory structures located on the same
lot.
| |
3.
|
Detached tool sheds and storage sheds, playhouses and similar
structures exempted from permits are not required to provide wall
protection based on location on the lot. Projections beyond the exterior
wall shall not extend over the lot line.
| |
4.
|
Detached garages accessory to a dwelling located within two
(2) feet (610 mm) of a lot line are permitted to have roof eave projections
not exceeding four (4) inches (102 mm).
| |
5.
|
Foundation vents installed in compliance with this code are
permitted.
| |
6.
|
Cantilevered manufactured fireplaces.
| |
7.
|
Roof eave overhangs.
| |
8.
|
Uncovered decks.
|
Table R302.1(1)
| ||||
---|---|---|---|---|
Exterior Walls
| ||||
Exterior Wall Element
|
Minimum Fire-Resistance Rating
|
Minimum Fire Separation Distance
| ||
Walls
|
Fire-resistance rated
|
1 hour - tested in accordance with ASTM E 119 or UL 263 with
exposure from both sides
|
0 feet to < 3 feet
| |
Not fire-resistance rated
|
0 hours
|
> 3 feet
| ||
Projections
|
Fire-resistance rated
|
1 hour on the undersidea, b
|
2 feet
| |
Not fire-resistance rated
|
0 hours
|
3 feet
| ||
Openings in walls
|
Not allowed
|
N/A
|
< 3 feet
| |
25% maximum of wall area
|
0 hours
|
3 feet
| ||
Unlimited
|
0 hours
|
3 feet
| ||
Penetrations
|
All
|
Comply with Section R302.4
|
< 3 feet
| |
None required
|
3 feet
|
For SI: 1 foot = 304.8 mm
| |
N/A = Not Applicable
|
a. Roof eave fire-resistance rating shall be permitted to be
reduced to zero (0) hours on the underside of the eave if fireblocking
is provided from the wall top plate to the underside of the roof sheathing.
| |
b. Roof eave fire-resistance rating shall be permitted to be
reduced to zero (0) hours on the underside of the eave, provided that
gable vent openings are not installed.
| |
R302.2 Townhouses. Common walls separating townhouses
shall be assigned a fire-resistance rating in accordance with Section
R302.2, Item 1 or 2. The common wall shared by two townhouses shall
be constructed without plumbing or mechanical equipment, ducts or
vents in the cavity of the common wall. The wall shall be rated for
fire exposure from both sides and shall extend to and be tight against
exterior walls and the underside of the roof sheathing. Electrical
installations shall be in accordance with Chapters 34 through 43.
Penetrations of the membrane of common walls for electrical outlet
boxes shall be in accordance with Section R302.4.
| |
1. Where a fire sprinkler system in accordance with Section
P2904 is provided, the common wall shall be not less than a one-hour
fire-resistance-rated wall assembly tested in accordance with ASTM
E 119 or UL 263.
| |
2. Where a fire sprinkler system in accordance with Section
P2904 is not provided, the common wall shall be not less than a two-hour
fire-resistance-rated wall assembly tested in accordance with ASTM
E 119 or UL 263, or the common wall may be two independent one-hour
fire-resistance-rated wall assemblies.
| |
R302.5.1 Opening protection. Openings from a private
garage directly into a room used for sleeping purposes shall not be
permitted. Other openings between the garage and residence shall be
equipped with solid wood doors not less than 1 3/8 inches (35
mm) in thickness, solid or honeycomb-core steel doors not less than
1 3/8 inches (35 mm) thick, or 20-minute fire-rated doors.
| |
R302.5.2 Duct penetration. Ducts in the garage
and ducts penetrating the walls or ceilings separating the dwelling
from the garage shall be constructed of a minimum No. 28 gage (0.48
mm) sheet steel or other approved material and shall not have openings
into the garage.
| |
R302.13 Fire protection of floors. Floor assemblies
that are not required elsewhere in this code to be fire-resistance
rated shall be provided with 1/2-inch (12.7 mm) gypsum wallboard membrane,
5/8-inch (16 mm) wood structural panel membrane, or equivalent on
the underside of the floor framing member. Penetrations or openings
for ducts, vents, electrical outlets, lighting, devices, luminaires,
wires, speakers, drainage, piping and similar openings or penetrations
shall be permitted. Fire blocking, draft stopping, and/or additional
framing is not required.
| |
Exceptions:
| |
1. Floor assemblies located directly over a space protected
by an automatic sprinkler system in accordance with Section P2904,
NFPA 13D, or other approved equivalent sprinkler system.
| |
2. Floor assemblies located directly over a crawl space not
intended for storage or fuel-fired appliances.
| |
3. Portions of floor assemblies shall be permitted to be unprotected
where complying with the following:
| |
3.1. The aggregate area of the unprotected floor assembly does
not exceed one hundred (100) square feet per HVAC zone.
| |
3.2. Areas of the floor assembly covered by HVAC metal plenum,
trunk lines, and steel structural beams shall be considered protected.
Gypsum wallboard membrane shall be within one (1) inch of all previously
listed items.
| |
4. Wood floor assemblies using dimension lumber or structural
composite lumber equal to or greater than two-inch-by-ten-inch (50.8
mm by 254 mm) nominal dimension, or other approved floor assemblies
demonstrating equivalent fire performance.
| |
R303.3 Bathrooms. Bathrooms, water closet compartments
and other similar rooms shall be provided with aggregate glazing area
in windows of not less than three (3) square feet (0.3 m2), one-half (1/2) of which must be openable.
| |
Exception: The glazed areas shall not be required
where artificial light and a local exhaust system are provided. The
minimum local exhaust rates shall be determined in accordance with
Section M1507. Exhaust air from the space shall be exhausted directly
to the outdoors, to a ventilated soffit, or a gabled end vent.
| |
R303.4 Mechanical ventilation. Where the air infiltration
rate of a dwelling unit is three (3) air changes per hour or less
where tested with a blower door at a pressure of two tenths (0.2)
inch w.c. (50 Pa) in accordance with Section N1102.4.1.2, the dwelling
unit shall be provided with whole-house mechanical ventilation in
accordance with Section M1507.3.
| |
R303.5.2 Exhaust openings. Exhaust air shall not
be directed below six (6) feet and eight (8) inches onto public walkways.
| |
R303.8 Exterior stairway illumination. Exterior
stairways shall be provided with an artificial light source. Exterior
stairways providing access to a basement from the outdoor grade level
shall be provided with an artificial light source located at the bottom
landing of the stairway.
| |
R309.5 Fire sprinklers. Private garages shall be
protected by fire sprinklers where the garage wall has been designed
based on Table 302.1(2), Footnote a, and the homeowner has opted to
purchase a fire sprinkler system for their residence, as per Section
67.281, RSMo. Sprinklers in garages shall be connected to an automatic
sprinkler system that complies with Section P2904. Garage sprinklers
shall be residential sprinklers or quick-response sprinklers, designed
to provide a density of 0.05 gpm/ft2. Garage
doors shall not be considered obstructions with respect to sprinkler
placement.
| |
R311.3 Floors and landings at exterior doors. There
shall be a landing or floor at each required egress exterior door.
The width of each landing shall not be less than the door served.
Every landing shall have a dimension of not less than thirty six (36)
inches (914 mm) measured in the direction of travel. The slope at
exterior landings shall not exceed 1/4 unit vertical in twelve (12)
units horizontal (two percent).
| |
Exception: Exterior balconies less than sixty (60)
square feet (5.6 m2) and only accessible
from a door are permitted to have a landing less than thirty-six (36)
inches (914 mm) measured in the direction of travel.
| |
R311.3.2 Floor elevations for other exterior doors. Doors other than the required egress door shall be provided with
landings or floors not more than 7 3/4 inches (196 mm) below
the top of the threshold.
| |
Exception: A top landing is not required where
a stairway of four (4) or fewer risers is located on the exterior
side of the door, provided that door does not swing over the stairway.
| |
R311.7.5 Stair treads and risers. Stair treads
and risers shall meet the requirements of this Section. For the purposes
of this Section, dimensions and dimensioned surfaces shall be exclusive
of carpets, rugs or runners.
| |
R311.7.5.1 Risers. The riser height shall be not
more than 7 3/4 inches (196 mm). The riser shall be measured
vertically between leading edges of the adjacent treads. The greatest
riser height within any flight of stairs shall not exceed the smallest
by more than 3/8 inch (9.5 mm). Risers shall be vertical or sloped
from the underside of the nosing of the tread above at an angle not
more than thirty degrees (30°) (0.51 rad) from the vertical. Open
risers are permitted, provided that the openings located more than
thirty (30) inches (762 mm), as measured vertically, to the floor
or grade below do not permit the passage of a four-inch-diameter (102
mm) sphere.
| |
Exceptions:
| |
1. The opening between adjacent treads is not limited on spiral
stairways.
| |
2. The riser height of spiral stairways shall be in accordance
with Section R311.7.10.1.
| |
R311.7.5.2 Treads. The tread depth shall be not
less than ten (10) inches (254 mm). The tread depth shall be measured
horizontally between the vertical planes of the foremost projection
of adjacent treads and at a right angle to the tread's leading
edge. The greatest tread depth within any flight of stairs shall not
exceed the smallest by more than 3/8 inch (9.5 mm).
| |
R311.7.5.2.1 Winder treads. Winder treads shall
have a tread depth of not less than ten (10) inches (254 mm) measured
between the vertical planes of the foremost projection of adjacent
treads at the intersections with the walkline. Winder treads shall
have a tread depth of not less than six (6) inches (152 mm) at any
point within the clear width of the stair. Within any flight of stairs,
the largest winder tread depth at the walk line shall not exceed the
smallest winder tread by more than 3/8 inch (9.5 mm). Consistently
shaped winders at the walkline shall be allowed within the same flight
of stairs as rectangular treads and do not have to be within 3/8 inch
(9.5 mm) of the rectangular tread depth.
| |
Exception: The tread depth at spiral stairways
shall be in accordance with Section R311.7.10.1.
| |
Exceptions:
| |
1. For remodeling projects in existing homes, homes in urban,
infill or high-density developments, or historical buildings or dwellings,
riser height of not more than 8 1/4 inches (210 mm) and tread
depth of not more than nine (9) inches (229 mm) will be allowed.
| |
2. For remodeling projects in existing homes, stair tread and
riser will be allowed to mimic previous or existing conditions.
| |
R311.7.6 Landings for stairways. There shall be
a floor or landing at the top and bottom of each stairway. The width
perpendicular to the direction of travel shall be not less than the
width of the flight served. Landings of shapes other than square or
rectangular shall be permitted, provided the depth at the walk line
and the total area is not less than that of a quarter circle with
a radius equal to the required landing width. Where the stairway has
a straight run, the depth in the direction of travel shall not be
less than 36 inches (914 mm).
| |
Exception: A floor or landing is not required at
the top of an interior or exterior flight of stairs, including stairs
in an enclosed garage, provided that a door does not swing over the
stairs.
| |
R312.1.1 Where required. Guards shall be located
along open-sided walking surfaces, including stairs, ramps and landings
that are located more than thirty (30) inches (762 mm) measured vertically
at the edge of the walking surface to the floor or grade below. Insect
screening shall not be considered as a guard.
| |
R312.2 Window fall protection. Window fall protection
shall be provided in accordance with Sections R312.2.1 and R312.2.2.
| |
R312.2.1 Window sills, in dwelling units, where
the top of the sill of an operable window opening is located less
than twenty-four (24) (310 mm) above the finished floor and greater
than seventy-two (72) inches (1,829 mm) above the finished grade or
other surface below on the exterior of the building, the operable
window shall comply with one of the following:
| |
1. Operable windows with openings that will not allow a four-inch
diameter (102 mm) sphere to pass through the opening where the opening
is in its largest open position.
| |
2. Operable windows that are provided with window fall prevention
devices that comply with ASTM F 2090.
| |
3. Operable windows that are provided with window opening control
devices that comply with Section R312.2.2.
| |
R312.2.2 Window opening control devices. Window
opening control devices shall comply with ASTM F 2090. The window
opening control device, after operation to release the control device
allowing the window to fully open, shall not reduce the new clear
opening area of the window unit to less than the area required by
Section R310.2.1.
| |
R313.1 Townhouse automatic fire sprinkler systems. An automatic residential fire sprinkler system shall be installed
in townhouses, in accordance with Section 67.281, RSMo.
| |
Exception: An automatic residential fire sprinkler
system shall not be required where additions or alterations are made
to existing townhouses that do not have an automatic residential fire
sprinkler system installed.
| |
R313.1.1 Design and installation. Automatic residential
fire sprinkler systems for townhouses shall be designed and installed
in accordance with Section P2904 or NFPA 13D.
| |
R313.2 One- and two-family dwellings automatic fire systems. An automatic residential fire sprinkler system shall be installed
in one- and two-family dwellings. A builder of a single-family dwelling
or residence or multiunit dwellings of four or fewer units shall offer
to any purchaser on or before the time of entering into the purchase
contract the option, at the purchaser's cost, to install or equip
fire sprinklers in the dwelling, residence, or unit. Notwithstanding
any other provision of law to the contrary, no purchaser of such a
single-family dwelling, residence, or multiunit dwelling shall be
denied the right to choose or decline to install a fire sprinkler
system in such dwelling or residence being purchased by any code,
ordinance, rule, regulation, order, or resolution by any county or
other political subdivision. Any county or other political subdivision
shall provide in any such code, ordinance, rule, regulation, order,
or resolution the mandatory option for purchasers to have the right
to choose and the requirement that builders offer to purchasers the
option to purchase fire sprinklers in connection with the purchase
of any single-family dwelling, residence, or multiunit dwelling of
four or fewer units.
| |
Exception: An automatic residential fire sprinkler
system shall not be required for additions or alterations to existing
buildings that are not already provided with an automatic residential
sprinkler system.
| |
R313.2.1 Design and installation. Automatic residential
fire sprinkler systems shall be designed and installed in accordance
with Section P2904 or NFPA 13D.
| |
R323.1 General. This Section applies to storm shelters
where constructed as separate detached buildings or where constructed
as safe rooms within buildings for the purpose of providing refuge
from storms that produce high winds, such as tornadoes and hurricanes.
In addition to other applicable requirements in this code, storm shelters
shall be constructed in accordance with ICC/NSSA-500, except when
located below grade or if basement walls are fully constructed with
concrete.
| |
R403.1.7 Footings on or adjacent to slopes. The
placement of buildings and structures on or adjacent to slopes steeper
than one unit vertical in three (3) units horizontal (33.3-percent
slope) shall conform to Sections R403.1.7.1 through R403.1.7.4 or
plans as signed and sealed by a registered engineer.
|
Table R404.1.2(10) Concrete Foundation Walls
| |||
---|---|---|---|
Maximum Wall Height
|
Maximum Depth of Unbalanced Backfill
|
Minimum Nominal Wall Thickness
| |
7 feet 0 inches
|
6 feet 0 inches or less
7 feet 0 inches
|
8 inches
10 inches (Note a)
| |
8 feet 0 inches
|
6 feet 0 inches or less
7 feet 0 inches
8 feet 0 inches
|
8 inches (Note a)
8 inches (Note a)
8 inches (Note a)
| |
9 feet 0 inches
|
6 feet 0 inches or less
7 feet 0 inches
8 feet 0 inches
9 feet 0 inches
|
10 inches (Note b)
10 inches (Note b)
10 inches (Note b)
10 inches (Note b)
|
Note a:
|
Concrete foundation walls may be constructed a minimum of nominal
eight (8) inches thick where the wall height from the top of the footing
to the top of the wall does not exceed eight (8) feet. A minimum of
two #4 reinforcing bars shall be placed horizontally in the top and
bottom of the foundation wall. A minimum of two #5 reinforcing bars
shall be provided around all window and door openings in concrete
foundation and basement walls; bars shall extend a minimum of twenty-four
(24) inches beyond the corners of the openings.
| |
Note b:
|
Concrete foundation walls may be constructed a minimum of nominal
ten (10) inches thick. A minimum of two #5 reinforcing bars shall
be placed horizontally in the top, middle, and bottom of the foundation
wall. A minimum of two #5 reinforcing bars shall be provided around
all window and door openings in concrete foundation and basement walls;
bars shall extend a minimum of twenty-four (24) inches beyond the
corners of the openings.
|
The concrete minimum nominal wall thickness shall be eight (8)
inches for foundation walls in soil classes SC, MH, ML-MC and inorganic
CL when the maximum wall height is eight (8) feet.
| |
The concrete minimum wall thickness shall be ten (10) inches
for foundation walls in soil classes SC, MH, ML-CL and inorganic CL
when the maximum wall height is nine (9) feet.
| |
The concrete minimum wall thickness shall be twelve (12) inches
for foundation walls in soil classes SC, MH, ML-CL and inorganic CL
when the maximum wall height is ten (10) feet.
| |
405.1 Concrete or masonry foundations. Drains shall
be provided around concrete or masonry foundations that retain earth
and enclose habitable or usable spaces located below grade. Drainage
tiles, gravel or crushed stone drains, perforated pipe or other approved
systems or materials shall be installed at or below the area to be
protected and shall discharge by gravity or mechanical means into
an approved drainage system. Gravel or crushed stone drains shall
extend not less than one (1) foot (305 mm) beyond the outside edge
of the footing and six (6) inches (152 mm) above the top of the footing
and be covered with an approved filter membrane material. The top
of open joints of drain tiles shall be protected with strips of building
paper. Except where otherwise recommended by the drain manufacturer,
perforated drains shall be surrounded with an approved filter membrane
or the filter membrane shall cover the washed gravel or crushed rock
covering the drain. Drainage tiles or perforated pipe shall be placed
on a minimum of two (2) inches (51 mm) of washed gravel or crushed
rock not less than one sieve size larger than the tile joint opening
or perforation and covered with not less than six (6) inches (152
mm) of the same material.
| |
Exceptions:
| |
1. A drainage system is not required where the foundation is
installed on well-drained ground or sand-gravel mixture soils according
to the Unified Soil Classification System, Group I soils, as detailed
in Table R405.1.
| |
2. Drains provided as detailed in Section R405.1.2 are approved
as an alternative method to meet the requirements of this Section.
| |
R405.1.2 Soil evaluations. An evaluation of the
soil for the presence or absence of groundwater is required. The evaluation
report shall be based on either a subsurface soil investigation or
satisfactory data from adjacent areas together with an inspection
of the excavation prior to pouring concrete.
| |
R405.1.2.1 Groundwater present. Provide drain tile,
perforated pipe or other approved foundation drainage systems (such
as water channel system) around perimeter of the outside of the foundation
and inside the foundation. Drain discharge shall be by gravity to
daylight or be connected to a basement floor sump.
| |
R405.1.2.2 No groundwater present. Provide drain
tile, perforated pipe or other approved foundation drainage systems
(such as water channel system) around perimeter of the outside of
the foundation or inside the foundation. Drain discharge shall be
by gravity to daylight or be connected to a basement floor sump.
| |
R405.1.2.3 Filter membranes. An approved filter
membrane shall be placed over the top of the joints/pipe perforations.
The tile/pipe shall be placed on two (2) inches minimum of gravel
or crushed stone and have six (6) inches of minimum cover.
| |
R405.1.2.4 Drainage system. A drainage system shall
discharge by gravity to daylight or be connected to an approved sump
(fifteen (15) inches in diameter by eighteen (18) inches deep with
fitted cover). A sump pump shall be provided if the basement is finished
or partially finished with pump discharge by an approved method.
| |
R507.2.4 Deck lateral load connection. The lateral
load connection required by Section R507.1 shall be permitted to be
in accordance with Figure R507.2.3(1) or R507.2.3(2). Where the lateral
load connection is provided in accordance with Figure R507.2.3(1),
hold-down tension devices shall be installed in not less than two
locations per deck, within 24 inches of each end of the deck. Each
device shall have an allowable stress design capacity of not less
than one thousand five hundred (1,500)pounds (6672 N). Where the lateral
load connections are provided in accordance with Figure R507.2.3(2),
the hold down tension devices shall be installed in not less than
four locations per deck, and each device shall have an allowable stress
design capacity of not less than seven hundred fifty (750) pounds
(3336 N).
| |
R602.3.5 Braced wall panel uplift load path. Braced
wall panels located at exterior walls that support roof rafters or
trusses (including stories below top story) shall have the framing
members connected in accordance with one of the following:
| |
1. Fastening in accordance with Table 602.3(1) where:
| |
1.1 The ultimate design wind speed does not exceed 115 125 mph
(51 56 m/s), the wind exposure category is B, the roof pitch is 5:12
or greater, and the roof span is thirty-two (32) feet (9,754 mm) or
less.
| |
1.2 The net uplift value at the top of a wall does not exceed
100 plf (146 N/mm). The net uplift value shall be determined in accordance
with Section R802.11 and shall be permitted to be reduced by 60 plf
(86 N/mm) for each full wall above.
| |
2. Where the net uplift value at the top of a wall exceeds 100
plf (146 N/mm), installing approved uplift framing connectors to provide
a continuous load path from the top of the wall to the foundation
or to point where the uplift force is 100 plf (146 N/mm) or less.
The net uplift value shall be as determined in Item 1.2 above.
| |
2. Wall sheathing and fasteners designed to resist combined
uplift and shear forces in accordance with accepted engineering practice.
| |
R602.7.5 Supports for headers. Headers shall be
supported on each end with one or more jack studs or with approved
framing anchors in accordance with Table R602.7(1) or R602.7.(2).
The full-height stud adjacent to each end of the header shall be end
nailed to each end of the header with four-16d nails (3.5 inches by
0.135 inches). The minimum number of full-height studs at each end
of a header shall be in accordance with Table R602.7.5.
|
Table R602.7.5
| |||
---|---|---|---|
Minimum Number of Full Height Studs at Each End of Headers
in Exterior Walls
| |||
Header Span
(feet)
|
Maximum Stud Spacing
(inches)
[per Table R602.3(5)]
| ||
16
|
24
| ||
<3
|
1
|
1
| |
4
|
1
|
1
| |
8
|
1
|
1
| |
12
|
1
|
1
| |
16
|
1
|
1
|
R602.13 Alternate simplified bracing method for one- and
two-family dwellings when the entire structure is sheathed with wood
structural panels and located in wind exposure A or B. The
construction documents shall detail the locations and widths of all
braced wall panels in accordance with this Section.
| |
R602.13.1 Wood structural sheathing. The building
exterior walls shall be sheathed with seven-sixteenths-inch (11.1
mm) or thicker plywood or OSB wood structural panels. The wood structural
panels shall be applied to all exterior walls, gable ends and band
boards. All vertical joints between panels shall be blocked. Horizontal
joints in braced wall panels shall be blocked.
| |
R602.13.2 Braced wall panel locations. Braced wall
panels shall be located in every exterior braced wall line in accordance
with the following criteria:
| |
1. The outside edge of the first braced wall panel meeting the
width established in Table R602.13.3 shall be a maximum of twelve
and five-tenths (12.5) feet (3,810 mm) or less from each end of the
braced wall line. The outside stud of the first braced wall panels
closest to the end of the braced wall line shall be secured with a
hold-down device securing the end stud to the foundation with a minimum
uplift design value of eight hundred (800) pounds.
| |
Exception: The eight-hundred-pound hold-down device
is not required when the braced wall panel is placed at the end of
the braced wall line and there is a twenty-four-inch (610 mm) wide
full height sheathed wall placed ninety degrees (90°) to the end
of the braced wall line and panel.
| |
2. The center line spacing of braced wall panels in a braced
wall line may not exceed twenty-five (25) feet (7,620 mm).
| |
R602.13.3 Braced wall panel widths. Braced wall
panel locations shall be shown on the floor plans or elevation views
and meet the widths established in Table R602.13.3.
|
Table 602.13.3
| ||||||
---|---|---|---|---|---|---|
Simplified Bracing Panel Widths
| ||||||
Width of Solid Panela, b
| ||||||
8-foot wall height
|
9-foot wall height
|
10-foot wall height
|
12-foot wall height
| |||
Plywood/OSB Panel
|
3:1
|
32 inches
|
36 inches
|
40 inches
|
48 inches
| |
Simplified Portal Wallc
|
6:1
|
16 inchesd
|
18 inchesd
|
20 inchesd
|
24 inchesd
|
a. Linear interpolation is permitted.
| |
b. Wall height is the vertical distance from the bottom of the
sole/sill plate to the top of the double top plate. An additional
two-inch (50.8 mm) variation in height is allowed for pre-cut stud
framing.
| |
c. The simplified portal wall, if applicable, shall be constructed
in accordance with the applicable detail in Figure R602.13.3. The
designer shall provide this detail on the construction documents.
| |
d. The simplified portal wall width assumes the beam is placed
under the top plate of the wall. A smaller width may be calculated
for a lower top of beam height using the 6:1 height-to-width ratio.
|
R602.13.4 Corner framing. The exterior wall corners
shall be constructed in accordance with the applicable detail in Figure
R602.10.10.4.
| |
Exception: Braced wall panels located in accordance
with Section R602.13.2.
| |
R602.13.5 Braced wall line spacing. When the perpendicular
distance between the exterior braced wall lines exceeds fifty (50)
feet (15,240 mm), the registered design professional shall include
the following certification on the drawings: The interior and exterior
wall configuration braces for the structure in accordance with or
equivalent to the lateral bracing provisions of Section R602.10 of
the International Residential Code, 2009 edition or Section 2305 of
the International Building Code, 2009 edition.
| |
R602.13.6 Maximum wall height. Walls greater than
twelve (12) feet (3,658 mm) (twelve (12) feet two (2) inches (3,708
mm) actual) in height and twelve (12) feet (3,658 mm) in width shall
be designed and detailed by the registered design professional to
resist wind loads in both the longitudinal and transverse directions.
|
OVER RAISED WOOD FLOOR OR SECOND FLOOR
|
WOOD STRUCTURAL PANEL OVERLAP OPTION
|
Figure R602.13.3
|
SIMPLIFIED PORTAL WALL
|
a. CRIPPLE WALL FRAMING CONSISTING OF STUD FRAMING, SINGLE BOTTOM
PLATE, AND DOUBLE TOP PLATE MAY BE ADDED TO THE TOP OF THE NARROW
PORTAL WALL AS LONG AS THE COMBINED HEIGHT OF THE TWO WALLS IS LESS
THAN OR EQUAL TO TWELVE (12) FEET AND THE TWO WALLS ARE STRAPPED TOGETHER
ON THE INTERIOR SIDE WITH A 16GUAGE METAL 1 1/2 INCH WIDE BY
TWENTY-ONE-INCH LONG STRAP. A MINIMUM TEN (10) INCHES OF THE STRAP
SHALL BE CONNECTED TO EACH WALL OR GABLE TRUSS WITH 9 - 16D NAILS
FOR A TOTAL OF 18-16D NAILS IN THE ENTIRE STRAP. STRAPS SHALL BE LOCATED
AT EACH END OF THE CONNECTED WALLS OR WALL AND GABLE TRUSS WHERE SPACE
ALLOWS FOR THE TEN-INCH LENGTH OF STRAP. THE SPACING BETWEEN THE STRAPS
MAY NOT EXCEED FOUR (4) FEET ON CENTER. THE STRAPS SHALL NOT BE BENT
HORIZONTALLY TO ACCOMMODATE WOOD FRAMING. IF APPLICABLE, NAILERS SHALL
BE ADDED TO ONE OF THE WALLS OR GABLE END USING A MINIMUM OF 9-16D
NAILS TO CREATE THE VERTICAL PLANE NEEDED TO MOUNT THE STRAP.
|
CORNER DETAIL
|
USED IN CONJUNCTION WITH SIMPLIFIED PORTAL WALL
|
FIGURE R602.10.10.4
|
SIMPLIFIED BRACING EXTERIOR CORNER FRAMING
|
a. END STUD INDICATED ON THE ABOVE DETAILS MAY BE SHIFTED 7/16"
TO ALLOW STUD FACE TO BE ALIGNED WITH SHEATHING, OR AN OPTIONAL NON-STRUCTURAL
FILLER PANEL MAY BE USED.
|
R905.2.8.2 Valleys. Valley linings shall be installed
in accordance with the manufacturer's instructions before applying
shingles. Valley linings of the following types shall be permitted:
| |
1. For open valleys (valley lining exposed) lined with metal,
the valley lining shall be not less than twenty-four (24) inches (610
mm) wide and of any of the corrosion-resistant metals in Table R905.2.8.2.
| |
2. For open valleys, valley lining of two plies of mineral-surfaced
roll roofing, complying with ASTM D 3909 or ASTM D 6380 Class M, shall
be permitted. The bottom layer shall be eighteen (18) inches (457
mm) and the top layer not less than thirty-six (36) inches (914 mm)
wide.
| |
3. For closed valleys (valley covered with shingles), valley
lining of one two ply of smooth roll roofing No. 15 felt complying
with ASTM D 6380 and not less than thirty-six (36) inches wide (914)
mm) ASTM D 226 Type I, ASTM D 4869 Type I, or ASTM D 6757, or valley
lining as described in Item 1 and 2 shall be permitted. Self-adhering
polymer modified bitumen underlayment complying with ASTM D 1970 shall
be permitted in lieu of the lining material.
| |
R905.2.8.5 Drip Edge. A drip edge shall be provided
at eaves and rake edges of shingle roofs. Adjacent segments of drip
edge shall be overlapped not less than two (2) inches (51 mm). Drip
edges shall extend not less than 1/4 inch (6.4 mm) below the roof
sheathing and extend up back onto the roof deck not less than two
(2) inches (51 mm). Drip edges shall be mechanically fastened to the
roof deck at not more than twelve (12) inches (305 mm) o.c. with fasteners
as specified in Section R905.2.5. Underlayment shall be installed
over the drip edge along eaves and under the underlayment along rake
edges.
| |
R1005.7 Factory-built chimney offsets. Where a
factory-built chimney assembly incorporates offsets, no part of the
chimney shall be at an angle of more than thirty degrees (30°)
(0.52 rad) from vertical at any point in the assembly, and the chimney
assembly shall not include more than four (4) elbows.
| |
Exception: When chimneys are installed per manufacturer's
installation instructions.
| |
R1006.1.1 Factory-built fireplaces. Exterior combustion
air ducts for factory-built fireplaces shall be a listed component
of the fireplace or equivalent and shall be installed according to
the fireplace manufacturer's instructions.
| |
R1006.2 Exterior air intake. The exterior air intake
on masonry fireplaces shall be capable of supplying combustion air
from the exterior of the dwelling or from spaces within the dwelling
ventilated with outdoor air such as non-mechanically ventilated crawl
or attic spaces. The exterior air intake shall not be located within
the garage or basement of the dwelling. The exterior air intake, for
other than listed factory-built fireplaces, shall not be located at
an elevation higher than the firebox. The exterior air intake shall
be covered with a corrosion-resistant screen of one-quarter-inch (6.4
mm) mesh.
| |
N1101.4 (R102.1.1) Above code programs. The Building
Official or other authority having jurisdiction shall be permitted
to deem a national, state or local energy-efficiency program to exceed
the energy efficiency required by this code. Buildings approved in
writing by such an energy-efficiency program shall be considered in
compliance with this code. The requirements identified as "mandatory"
in this chapter, as applicable, shall be met.
| |
N1101.5 (R103.2) Information on construction documents. Construction documents shall be drawn to scale upon suitable material.
Electronic media documents are permitted to be submitted when approved
by the building official. Construction documents shall be of sufficient
clarity to indicate the location, nature and extent of the work proposed,
and show in sufficient detail pertinent data and features of the building,
systems and equipment as herein governed. Details shall include, but
are not limited to, as applicable:
| |
1. Insulation materials and their R values.
| |
2. Fenestration, U factors and SHGCs.
| |
3. Area weighted U factor and SHGC calculations.
| |
4. Mechanical system design criteria.
| |
5. Mechanical and service water heating system and equipment
types, sizes and efficiencies.
| |
6. Equipment and system controls.
| |
7. Duct sealing, duct and pipe insulation and location.
| |
8. Air sealing details.
| |
N1101.5.1 (R103.2.1) Thermal envelope depiction. The building's thermal envelope shall be represented on the
construction drawings.
| |
N1101.6 (R202) Defined terms.
| |
PROJECTION FACTOR. The ratio of the horizontal
depth of an overhang, eave, or permanently attached shading device,
divided by the distance measured vertically from the bottom of the
fenestration glazing to the underside of the overhang, eave, or permanently
attached shading device.
| |
N1101.13 (R401.2) Compliance. Projects shall comply
with one of the following:
| |
1. Sections N1101.14 through N1104 as amended.
| |
2. Section N1105 and the provisions of Sections N1101.14 through
N1104 labeled "Mandatory."
| |
3. An energy rating index (ERI) approach in Section N1106.
| |
N1101.14 (R401.3) Certificate (Mandatory). A permanent
certificate shall be completed by the builder or registered design
professional and posted on a wall in the space where the furnace is
located, a utility room or an approved location inside the building.
Where located on an electrical panel, the certificate shall not cover
or obstruct the visibility of the circuit directory label, service
disconnect label or other required labels. The certificate shall list
the predominant R values of insulation installed in or on ceiling/roof,
walls, foundation (slab, basement wall, crawl space wall and/or floor)
and ducts outside conditioned spaces; U factors for fenestration and
the solar heat gain coefficient (SHGC) of fenestration, and the results
from any required duct system and building envelope air leakage testing
done on the building. Where there is more than one value for each
component, the certificate shall list the value covering the largest
area. The certificate shall list the types and efficiencies of heating,
cooling and service water heating equipment. Where a gas fired unvented
room heater," electric furnace, or baseboard electric heater is installed
in this residence, the certificate shall list "gas-fired unvented
room heater," "electric furnace" or "baseboard electric heater," as
appropriate. An efficiency shall not be listed for gas-fired unvented
room heaters, electric furnaces or electric baseboard heaters.
|
Table N1102.1.2 (R402.1.2)
| ||||||||||
---|---|---|---|---|---|---|---|---|---|---|
Insulation and Fenestration Requirements by Componenta
| ||||||||||
Climate Zone
|
Fenes- tration U-Factorb
|
Skylightb U-Factor
|
Glazed Fenes- tration SHGCb, c
|
Ceiling R-Value
|
Wood Frame Wall R-Value
|
Mass Wall R-Valuei
|
Floor R-Value
|
Basementc Wall R-Value
|
Slabd R-Value & Depth
|
Crawl Spacec Wall R-Value
|
1
|
NR
|
0.75
|
0.25
|
30
|
13
|
3/4
|
13
|
0
|
0
|
0
|
2
|
0.40
|
0.65
|
0.25
|
38
|
13
|
4/6
|
13
|
0
|
0
|
0
|
3
|
0.35
|
0.55
|
0.25
|
38
|
20 or 13 + 5h
|
8/13
|
19
|
5/13i
|
0
|
5/13
|
0.35
|
0.40
|
40
|
20 or 13 + 5
|
10/13
| ||||||
4 except Marine
|
0.40
|
0.55
|
NR
|
38
|
13
|
8/13
|
19
|
0i
|
10, 2 ft
|
10/13
|
5 and Marine 4
|
0.32
|
0.55
|
NR
|
49
|
20 or 13 + 5h
|
13/17
|
30e
|
15/19
|
10, 2 ft
|
15/19
|
6
|
0.32
|
0.55
|
NR
|
49
|
20 + 5 or 13 + 10h
|
15/20
|
30e
|
15/19
|
10, 4 ft
|
15/19
|
7 and 8
|
0.32
|
0.55
|
NR
|
49
|
20 + 5 or 13 + 10h
|
19/21
|
38g
|
15/19
|
10, 4 ft
|
15/19
|
For SI: 1 foot = 304.8mm.
|
a. R-values are minimums. U-factors and SHGC are maximums. When
insulation is installed in a cavity which is less than the label or
design thickness of the insulation, the installed R-value of the insulation
shall not be less than the R-value specified in the table.
| |
b. The fenestration U-factor column excludes skylights. The
SHGC column applies to all glazed fenestration. Exception: Skylights
may be excluded from glazed fenestration SHGC requirements in Climate
Zones 1 through 3 where the SHGC for such skylights does not exceed
0.30.
| |
c. "15/19" means R-15 continuous insulation on the interior
or exterior of the home or R-19 cavity insulation at the interior
of the basement wall. "15/19" shall be permitted to be met with R-13
cavity insulation on the interior of the basement wall plus R-5 continuous
insulation on the interior or exterior of the home. "10/13" means
R-10 continuous insulation on the interior or exterior of the home
or R-13 cavity insulation at the interior of the basement wall.
| |
d. R-5 shall be added to the required slab edge R-values for
heated slabs. Insulation depth shall be the depth of the footing or
two (2) feet, whichever is less in Zones 1 through 3 for heated slabs.
| |
e. There are no SHGC requirements in the Marine Zone.
| |
f. Basement wall insulation is not required in warm-humid locations
as defined by Figure N1101.10 or Table N1101.10.
| |
g. Or insulation sufficient to fill the framing cavity, R-19
minimum.
| |
h. The first value is cavity insulation, the second value is
continuous insulation, so "13+5" means R-13 cavity insulation plus
R-5 continuous insulation.
| |
i. The second R-value applies when more than half of the insulation
is on the interior of the mass wall.
| |
j. Exception: Unfinished basements may have up to a maximum
of 20% of the total basement wall area exposed above the outside finished
grade/ground level as uninsulated concrete foundation walls. The foundation
wall area above the outside grade/ground level that may be uninsulated
is determined by the formula [.20 times the basement wall height of
all walls (including insulated exterior frame walls for walkout basements
and walls common to both basement and attached garages) times the
perimeter of these basement walls]. In unfinished areas, the basement
foundation wall insulation shall extend down to the basement floor
slab or to a minimum of twenty-four (24) inches below outside finished
grade when the grade is above the floor slab elevation.
| |
N1102.1.3 (R402.1.3) R-value computation. Insulation
material used in layers, such as framing cavity insulation, or continuous
insulation shall be summed to compute the corresponding component
R-value. The manufacturer's settled R-value shall be used for
blown insulation. Computed R-values shall not may include an R-value
for other building materials or air films. Where insulated siding
is used for the purpose of complying with the continuous insulation
requirements of Table N1102.1.2, the manufacturer's labeled R-Value
for insulated siding shall be reduced by R-0.6.
| |
N1102.1.5 (R402.1.5) Total UA alternative. If the
total building envelope UA (sum of U-factor times assembly area) is
less than or equal to the total UA resulting from using the U-factors
in Table N1102.1.4 (multiplied by the same assembly area as in the
proposed building), the building shall be considered in compliance
with Table N1102.1.2. The UA calculation shall be done using a method
consistent with the ASHRAE Handbook of Fundamentals and shall include
the thermal bridging effects of framing materials. The SHGC requirements
shall be met in addition to UA compliance.
| |
Exception: Glazed fenestration SHGC. In Climate
Zone 4, permanently shaded vertical fenestration shall be permitted
to satisfy SHGC requirements. The projection factor of an overhang,
eave, or permanently attached shading device shall be greater than
or equal to the value listed in Table N1102.2.2.1 for the appropriate
orientation. The minimum projection shall extend beyond each side
of the glazing a minimum of twelve (12) inches. Each orientation shall
be rounded to the nearest cardinal orientation (+/- forty-five degrees
(45°) or 0.79 rad) for purposes of calculations and demonstrating
compliance.
|
Table N1102.1.5
| ||
---|---|---|
Minimum Projection Factor Required by Orientation for
SHGC Exception
| ||
Orientation
|
Projection Factor
| |
North
|
>=0.40a
| |
South
|
>=0.20
| |
East
|
>=0.50
| |
West
|
>=0.50
|
a. For the north orientation, a vertical projection located
on the west-edge of the fenestration with the equivalent of PF>=0.15
shall also satisfy the minimum projection factor requirement.
| |
N1102.2.4 (R402.2.4) Access hatches and doors. Access
doors from conditioned spaces to unconditioned spaces such as attics
and crawl spaces shall be weatherstripped and insulated to a level
equivalent to the insulation on the surrounding surfaces. Access shall
be provided to all equipment that prevents damaging or compressing
the insulation. A wood-framed or equivalent baffle or retainer is
required to be provided when loose-fill insulation is installed, the
purpose of which is to prevent the loose-fill insulation from spilling
into the living space when the attic access is opened, and to provide
the permanent means of maintaining the installed R-value of the loose-fill
insulation.
| |
Exception: Vertical doors that provide access from
the conditioned to unconditioned spaces shall be permitted to meet
the fenestration requirements of Table R1102.1.2 based on the applicable
climate zone specified in Chapter 3.
| |
N1102.4 (R402.4) Air leakage (Mandatory). The building
thermal envelope shall may be designed and constructed to limit air
leakage in accordance with the requirements of Sections R1102.4.1
through R1102.4.4.
| |
N1102.4.1 (R402.4.1) Building thermal envelope. The building thermal envelope shall comply with Sections N1102.4.1.1
and N1102.4.1.2. The sealing methods between dissimilar materials
shall allow for differential expansion and contraction.
| |
N1102.4.1.1 (R402.4.1.1) Installation. The components
of the building thermal envelope as listed in Table N1102.4.1.1 shall
be installed in accordance with the manufacturer's instructions
and the criteria listed in Table N1102.4.1.1, as applicable to the
method of construction. Where required by the Building Official, an
approved third party shall inspect all components and verify compliance.
| |
N1102.4.1.2 (R402.4.1.2) Testing. The Any building
or dwelling unit shall may be tested and verified as having an air
leakage rate of not exceeding five (5) air changes per hour in Climate
Zones 1 and 2, and three air changes per hour in Climate Zones 3 through
8 Zone 4. Testing shall be conducted in accordance with ASTM E 779
or ASTM E 1827 and reported at a pressure of two-tenths (0.2) inches
w.g. (50 Pascals). Where required by the Code Official, testing shall
be conducted by an approved third party. A written report of the results
of the test shall be signed by the party conducting the test and provided
to the Code Official. Testing shall be performed at any time after
creation of all penetrations of the building thermal envelope.
| |
During testing:
| |
1. Exterior windows and doors, fireplace and stove doors shall
be closed, but not sealed, beyond the intended weatherstripping or
other infiltration control measures.
| |
2. Dampers including exhaust, intake, makeup air, backdraft
and flue dampers shall be closed, but not sealed beyond intended infiltration
control measures.
| |
3. Interior doors, if installed at the time of the test, shall
be open.
| |
4. Exterior doors for continuous ventilation systems and heat
recovery ventilators shall be closed and sealed.
| |
5. Heating and cooling systems, if installed at the time of
the test, shall be turned off.
| |
6. Supply and return registers, if installed at the time of
the test, shall be fully open.
|
Table N1102.4.1.1 (402.4.1.1)
| |||
---|---|---|---|
Air Barrier and Insulation Installation
| |||
Component
|
Air-Barrier Criteria
|
Insulation Installation Criteria
| |
General Requirements
|
A continuous air barrier shall be installed in the building
envelope.
The exterior thermal envelope contains a continuous air barrier.
Breaks or joints in the air barrier shall be sealed.
|
Air permeable insulation shall not be used as a sealing material.
| |
Ceiling/attic
|
The air barrier in any dropped ceiling/soffit shall be aligned
with the insulation and any gaps in the air barrier sealed.
Access openings, drop down stairs or knee wall doors to unconditioned
attic spaces shall be sealed.
|
The insulation in any dropped ceiling/soffit shall be aligned
with the air barrier.
| |
Walls
|
The junction of the foundation and sill plate shall be sealed.
The junction of the top plate and the top of the exterior walls
shall be sealed.
Knee walls shall be sealed.
|
Cavities within corners and headers of frame walls shall be
insulated by completely filling the cavity with a material having
a thermal resistance of R-3 per inch minimum.
Exterior thermal envelope insulation for framed walls shall
be installed in substantial contact and continuous alignment with
the air barrier.
| |
Windows, skylights and doors
|
The space between window/door jambs and framing, and skylights
and framing shall be sealed.
| ||
Rim joists
|
Rim joists shall include the air barrier.
|
Rim joists shall be insulated.
| |
Floors (including above garage and cantilevered floors)
|
The air barrier shall be installed at any exposed edge of insulation.
|
Floor framing cavity insulation shall be installed to maintain
permanent contact with the underside of subfloor decking, or floor
framing cavity insulation shall be permitted to be in contact with
the top side of sheathing, or continuous insulation installed on the
underside of floor framing; and extends from the bottom to the top
of all perimeter floor framing members.
| |
Crawl space walls
|
Exposed earth in unvented crawl spaces shall be covered with
Class I vapor retarder with overlapping joists taped.
|
Where provided instead of floor insulation, insulation shall
be permanently attached to the crawl space walls.
| |
Shafts, penetrations
|
Duct shafts, utility penetrations, and flue shafts opening to
exterior or unconditioned space shall be sealed.
| ||
Narrow cavities
|
Batts in narrow cavities shall be cut to fit, or narrow cavities
shall be filled by insulation that on installation readily conforms
to the available cavity space.
| ||
Garage separation
|
Air sealing shall be provided between the garage and conditioned
spaces.
| ||
Recessed lighting
|
Recessed light fixtures installed in the building thermal envelope
shall be sealed to the drywall.
|
Recessed light fixtures installed in the building thermal envelope
shall be air tight and IC rated.
| |
Plumbing and wiring
|
Batt insulation shall be cut neatly to fit around wiring and
plumbing in exterior walls, or insulation that on installation readily
conforms to available space shall extend behind piping and wiring.
| ||
Shower/tub on exterior wall
|
The air barrier installed at exterior walls adjacent to showers
and tubs shall separate them from showers and tubs.
|
Exterior walls adjacent to showers and tubs shall be insulated.
| |
Electrical/phone box on exterior walls
|
The air barrier shall be installed behind electrical or communication
boxes or air sealed boxes shall be installed.
| ||
HVAC register boots
|
HVAC register boots that penetrate building thermal envelope
shall be sealed to the subfloor or drywall.
| ||
Concealed sprinklers
|
When required to be sealed, concealed fire sprinklers shall
only be sealed in a manner that is recommended by the manufacturer.
Caulking or other adhesive sealants shall not be used to fill voids
between fire sprinkler cover plates and walls or ceilings.
|
a. In addition, inspection of log walls shall be in accordance
with the provisions of ICC 400.
| |
N1102.4.4 (R402.4.4) Rooms containing fuel-burning appliances. In Climate Zones 3 through 8, where open combustion air ducts provide
combustion air to open combustion fuel-burning appliances, the appliances
and combustion air opening shall be located outside the building thermal
envelope or enclosed in a room, isolated from inside the thermal envelope.
Such rooms shall be sealed and insulated in accordance with the envelope
requirements of Table N1102.1.2, where the walls, floors and ceilings
shall meet a minimum of the basement wall R-value requirement. The
door into the room shall be fully gasketed and any water lines and
ducts in the room insulated in accordance with Section N1103. The
combustion air duct shall be insulated where it passes through conditioned
space to a minimum of R-8.
| |
Exceptions:
| |
1. Direct vent appliances with both intake and exhaust pipes
installed continuous to the outside.
| |
2. Fireplaces and stoves complying with Sections N1102.4.2 and
R1006.
| |
3. Mechanical equipment in an unfinished space.
| |
N1102.4.5 (R402.4.5) Recessed lighting. Recessed
luminaires installed in the building thermal envelope shall may be
sealed to limit air leakage between conditioned and unconditioned
spaces. All recessed luminaires shall may be IC-rated and labeled
as having an air leakage rate not more than 2.0 cfm (0.944 L/s) when
tested in accordance with ASTM E 283 at a 1.57 psf (75 Pa) pressure
differential. All recessed luminaires shall may be sealed with a gasket
or caulk between the housing and interior wall or ceiling covering.
| |
N1103.1.1 (R403.1.1) Programmable thermostat. The
thermostat controlling the primary heating or cooling system of the
dwelling unit shall be capable of controlling the heating and cooling
system on a daily schedule to maintain different temperature set points
at different times of the day. This thermostat shall include the capability
to set back or temporarily operate the system to maintain zone temperatures
down to fifty-five degrees Fahrenheit (55° F.) (13° C.) or
up to eighty-five degrees Fahrenheit (85° F.) (29° C.). The
thermostat shall initially be programmed by the manufacturer with
a heating temperature set point no higher than seventy degrees Fahrenheit
(70° F.) (21° C.) and a cooling temperature set point no lower
than seventy-eight degrees Fahrenheit (78° F.) (26° C.).
| |
N1103.3.3 (R403.3.3) Duct testing (Mandatory). Ducts
shall be pressure tested to determine air leakage by one (1) of the
following methods:
| |
1. Rough in test: Total leakage shall be measured with a pressure
differential of 0.1 inch w.g. (25 Pa) across the system, including
the manufacturer's air handler enclosure if installed at the
time of the test. All registers shall be taped or otherwise sealed
during the test.
| |
2. Postconstruction test: Total leakage shall be measured with
a pressure differential of one-tenth (0.1) inch w.g. (25 Pa) across
the entire system, including the manufacturer's air handler enclosure.
Registers shall be taped or otherwise sealed during the test.
| |
Exception: A duct air leakage test shall not be
required where ducts and air handlers are located entirely within
the building thermal envelope.
| |
A written report of the results of the test shall be signed
by the party conducting the test and provided to the code official.
| |
N1103.3.5 (R403.3.5) Building cavities (Mandatory). Building framing cavities shall not be used as ducts or plenums.
| |
N1103.4.1 (R403.4.1) Protection of piping insulation. Piping insulation exposed to weather shall be protected from damage,
including that caused by sunlight, moisture, equipment maintenance
and wind, and shall provide shielding from solar radiation that can
cause degradation of the material. Adhesive tape shall not be permitted.
| |
N1103.6 (R403.6) Mechanical ventilation (Mandatory). The building shall be provided with ventilation that meets the requirements
of Section M1507 of this code or the International Mechanical Code,
as applicable, or with other approved means of ventilation. Outdoor
air intakes and exhausts shall have automatic or gravity dampers that
close when the ventilation system is not operating.
| |
N1103.6.1 (R403.6.1) Whole house mechanical ventilation
system fan efficacy. Mechanical ventilation system fans shall
meet the efficacy requirements of Table N1103.6.1.
| |
Exception: Where mechanical ventilation fans are
integral to tested and listed HVAC equipment, they shall be powered
by an electronically commutated motor.
|
Table N1103.6.1 (R403.6.1)
| ||||
---|---|---|---|---|
Mechanical Ventilation System Fan Efficacy
| ||||
Fan Location
|
Air Flow Rate Minimum (cfm)
|
Minimum Efficacy
(cfm/watt)
|
Air Flow Rate Maximum (cfm)
| |
Range hoods
|
Any
|
2.8 cfm/watt
|
Any
| |
In-line fan
|
Any
|
2.8 cfm/watt
|
Any
| |
Bathroom, utility room
|
10
|
1.4 cfm/watt
|
<90
| |
Bathroom, utility room
|
90
|
2.8 cfm/watt
|
Any
| |
For SI: one cubic foot per minute = 28.3 L/min.
|
N1103.7 (R403.7) Equipment sizing and efficiency rating
(Mandatory). Heating and cooling equipment shall be sized in
accordance with ACCA Manual S based on building loads calculated in
accordance with ACCA Manual J or other approved heating and cooling
calculation methodologies. New or replacement heating and cooling
equipment shall have an efficiency rating equal to or greater than
the minimum required by Federal law for the geographic location where
the equipment is installed.
| |
N1104 (R404) Electrical Power and Lighting Systems (Mandatory)
| |
N1104.1 (R404.1) Lighting equipment (Mandatory). Not less than seventy-five percent (75%) of the lamps in permanently
installed lighting fixtures shall be high efficacy lamps or not less
than seventy-five percent (75%) of the permanently installed lighting
fixtures shall contain only high efficacy lamps.
| |
Exception: Low voltage lighting.
| |
N1104.1.1 (R404.1.1) Lighting equipment (Mandatory). Fuel gas lighting systems shall not have continuously burning pilot
lights.
|
Table N1105.5.2(1) [R405.5.2(1)]
| |||
---|---|---|---|
Specifications for the Standard Reference and Proposed
Designs
| |||
Building Component
|
Standard Reference Design
|
Proposed Design
| |
Above-grade walls
|
Type: mass wall if proposed wall is mass; otherwise wood frame
|
As proposed
| |
Gross area: same as proposed
|
As proposed
| ||
U-factor: as specified in Table N1102.1.4
|
As proposed
| ||
Solar absorptance = 0.75
|
As proposed
| ||
Remittance = 0.90
|
As proposed
| ||
Basement and crawl space walls
|
Type: same as proposed
|
As proposed
| |
Gross area: same as proposed
|
As proposed
| ||
U-factor: from Table N1102.1.4, with insulation layer on interior
side of walls
|
As proposed
| ||
Above-grade floors
|
Type: wood frame
|
As proposed
| |
Gross area: same as proposed
|
As proposed
| ||
U-factor: as specified in Table N1102.1.4
|
As proposed
| ||
Ceilings
|
Type: wood frame
|
As proposed
| |
Gross area: same as proposed
|
As proposed
| ||
U-factor: as specified in Table N1102.1.4
|
As proposed
| ||
Roofs
|
Type: composition shingle on wood sheathing
|
As proposed
| |
Gross area: same as proposed
|
As proposed
| ||
Solar absorptance = 0.75
|
As proposed
| ||
Emittance = 0.90
|
As proposed
| ||
Attics
|
Type: vented with aperture = 1 ft2 per 300 ft2 ceiling area
|
As proposed
| |
Foundations
|
Type: same as proposed
|
As proposed
| |
Foundation wall area above and below grade and soil characteristics:
same as proposed
|
As proposed
| ||
Opaque doors
|
Area: 40 ft2
|
As proposed
| |
Orientation: North
|
As proposed
| ||
U-factor: same as fenestration from Table N1102.1.4
|
As proposed
| ||
Vertical fenestration other than opaque doors
|
Total areab =
a) The proposed glazing area, where the proposed glazing area
is less than 15 percent (15%) of the conditioned floor area
b) Fifteen percent (15%) of the conditioned floor area, where
the proposed glazing area is fifteen percent (15%) or more of the
conditioned floor area
|
As proposed
| |
Orientation: equally distributed to four cardinal compass orientations
(N, E, S and W)
|
As proposed
| ||
U-factor: as specified in Table N1102.1.4
|
As proposed
| ||
SHGC: as specified in Table N1102.1.2 except that for climates
with no requirement (NR) SHGC = 0.40 shall be used
|
As proposed
| ||
Interior shade fraction: 0.92 - (0.21 x SHGC for the standard
reference design)
|
0.92 - (0.21 x SHGC as proposed)
| ||
External shading: none
|
As proposed
| ||
Skylights
|
None
|
As proposed
| |
Thermally isolated sunrooms
|
None
|
As proposed
| |
Air exchange rate
|
Air leakage rate of 5 air changes per hour in Climate Zone 4
1 and 2, and 3 air changes per hour in Climate Zones 3 through 8 at
a pressure of 0.2 inches w.g. (50 Pa). The mechanical ventilation
rate shall be in addition to the air leakage rate and the same as
in the proposed design, but no greater than 0.01 x CFA + 7.5 x (Nbr + 1)
where:
CFA = conditioned floor area
Nbr = number of bedrooms
Energy recovery shall not be assumed for mechanical ventilation
|
For residences that are not tested, the same air leakage rate
as the standard reference design.
For tested residences, the measured air exchange ratea.
The mechanical ventilation rate
b shall be in addition to the air
leakage rate and shall be proposed.
| |
Mechanical ventilation
|
None, except where mechanical ventilation is specified by the
proposed design, in which case:
Annual vent fan energy use:
kWh/yr = 0.03942 x CFA + 29.565 x (Nbr +1)
where:
CFA = conditioned floor area
Nbr = number of bedrooms
|
As proposed
| |
Internal gains
|
IGain = 17,900 + 23.8 x CFA + 4104 x Nbr (Btu/day per dwelling unit)
|
Same as standard reference design.
| |
Internal mass
|
An internal mass for furniture and contents of 8 pounds per
square foot of floor area
|
Same as standard reference design, plus any additional mass
specifically designed as a thermal storage elementc but not integral to the building envelope or structure.
| |
Structural mass
|
For masonry floor slabs, 80% of floor area covered by R-2 carpet
and pad, and 20% of floor directly exposed to room air
|
As proposed
| |
For masonry basement walls, as proposed, but with insulation
required by Table R402.1.4 located on the interior side of the walls
|
As proposed
| ||
For other walls, for ceilings, floors, and interior walls, wood
frame construction
|
As proposed
| ||
Heating systemsd, e
|
As proposed for other than electric heating without a heat pump,
where the proposed design utilizes electric heating without a heat
pump the standard reference design shall be an air source heat pump
meeting the requirements of Section C403 of the IECC Commercial Provisions.
Fuel type: same as the proposed design
Efficiencies:
Electric: air-source heat pump with prevailing Federal minimum
standards
Non-electric furnaces: natural gas furnace with prevailing Federal
minimum standards
Non-electric boilers: natural gas boiler with prevailing Federal
minimum standards
Capacity: sized in accordance with Section N1103.7
|
As proposed
| |
Cooling systemsd, f
|
As proposed
Fuel type: electric
Efficiency: in accordance with prevailing Federal minimum standards
Capacity: sized in accordance with Section N1103.7
|
As proposed
| |
Service water heatingd, e, f
|
As proposed
Use: same as proposed design
Fuel type: same as proposed design
Efficiency: in accordance with prevailing Federal minimum standards
Use: gal/day = 30 + 10 x Nbr
Tank temperature: 120° F.
|
As proposed Gal/day = 30 + (10 x N)
Same as standard reference
| |
Thermal distribution systems
|
Duct insulation: from Section N1103.2.1
A thermal distribution system efficiency (DSE) of 0.88 shall
be applied to both the heating and cooling system efficiencies for
all systems other than tested duct systems. For tested duct systems,
the leakage rate shall be 4 cfm (113.3 L/min) per 100 ft2 (9.29 m2) of conditioned
floor area at a pressure of differential of one tenth (0.1) inches
w.g. (25 Pa)
|
As tested or specified in Table R405.5.2(2) if not tested. Duct
insulation shall be as proposed.
| |
Thermostat
|
Type: Manual, cooling temperature setpoint = 75° F.;
Heating temperature setpoint = 72° F.
|
Same as standard reference
|
For SI: 1 square foot = 0.93 m2,
1 British thermal unit = 1055 J, 1 pound per square foot = 4.88 kg/m2, 1 gallon (US) = 3.785 L, ° C. = (° F.-32)/1.8,
1 degree = 0.79 rad
|
a. Where required by the Code Official, testing shall be conducted
by an approved party. Hourly calculations as specified in the ASHRAE
Handbook of Fundamentals, or the equivalent, shall be used to determine
the energy loads resulting from infiltration.
| |
b. The combined air exchange rate for infiltration and mechanical
ventilation shall be determined in accordance with Equation 43 of
2001 ASHRAE Handbook of Fundamentals, page 26.24, and the "Whole-house
Ventilation" provisions of 2001 ASHRAE Handbook of Fundamentals, page
26.19, for intermittent mechanical ventilation.
| |
c. "Thermal storage element" shall mean a component not part
of the floors, walls or ceilings that is part of a passive solar system,
and that provides thermal storage such as enclosed water columns,
rock beds, or phase-change containers. A thermal storage element must
be in the same room as fenestration that faces within fifteen degrees
(15°) (0.26 rad) of true south, or must be connected to such a
room with pipes or ducts that allow the element to be actively charged.
| |
d. For a proposed design with multiple heating, cooling or water
heating systems using different fuel types, the applicable standard
reference design system capacities and fuel types shall be weighted
in accordance with their respective loads as calculated by accepted
engineering practice for each equipment and fuel type present.
| |
e. For a proposed design without a proposed heating system,
a heating system with the prevailing Federal minimum efficiency shall
be assumed for both the standard reference design and proposed design.
| |
f. For a proposed design home without a proposed cooling system,
an electric air conditioner with the prevailing Federal minimum efficiency
shall be assumed for both the standard reference design and the proposed
design.
| |
g. For a proposed design with a non-storage-type water heater,
a forty-gallon storage-type water heater with the prevailing Federal
minimum energy factor for the same fuel as the predominant heating
fuel type shall be assumed. For the case of a proposed design without
a proposed water heater, a forty-gallon storage-type water heater
with the prevailing Federal minimum efficiency for the same fuel as
the predominant heating fuel type shall be assumed for both the proposed
design and standard reference design.
| |
M1301.2 Identification. Each length of pipe and
tubing and each pipe fitting utilized in a mechanical system shall
bear the identification of the manufacturer.
| |
M1301.3 Installation of materials. Materials shall
be installed in strict accordance with the standards under which the
materials are accepted and approved. In the absence of such in tallation
procedures, the manufacturer's instructions shall be followed.
Where the requirements of referenced standards or manufacturer's
instructions do not conform to minimum provisions of this code, the
provisions of this code shall apply.
| |
M1301.4 Plastic pipe, fittings and components. Plastic
pipe, fittings and components shall be third-party certified as conforming
to NSF 14.
| |
M1301.5 Third-party testing and certification. Piping,
tubing and fittings shall comply with the applicable referenced standards,
specifications and performance criteria of this code and shall be
identified in accordance with Section M1301.2. Piping, tubing and
fittings shall either be tested by an approved third-party testing
agency or certified by an approved third-party certification agency.
| |
M1305.1.4.1 Ground clearance. Equipment and appliances
supported from the ground shall be level and firmly supported on a
concrete slab or other approved material extending not less than 3
two (2) inches (76 50.8 mm) above the adjoining ground. Such support
shall be in accordance with the manufacturer's installation instructions.
Appliances suspended from the floor shall have a clearance of not
less than six (6) inches (152 mm) from the ground.
| |
M1305.1.4.3 Electrical requirements. A luminaire
controlled by a switch located at the required passageway opening
and a receptacle outlet shall be installed at or near the appliance
location in accordance with Chapter 39. Exposed lamps shall be protected
from damage by location or lamp guards.
| |
Exception: Basements.
| |
M1307.2 Anchorage of appliances. Appliances designed
to be fixed in position shall be fastened or anchored in an approved
manner. In Seismic Design Categories D0, D1 and D2, and in townhouses in
Seismic Design Category C, water heaters and thermal storage units
shall be anchored or strapped to resist horizontal displacement caused
by earthquake motion in accordance with one of the following:
| |
1. Anchorage and strapping shall be designed to resist a horizontal
force equal to one-third (1/3) of the operating weight of the water
heater storage tank, acting in any horizontal direction. Strapping
shall be at points within the upper one-third (1/3) and lower one-third
(1/3) of the appliance's vertical dimensions. At the lower point,
the strapping shall maintain a minimum distance of four (4) inches
(102 mm) above the controls.
| |
2. The anchorage strapping shall be in accordance with the appliance
manufacturer's recommendations.
| |
M1401.3 Equipment and appliance sizing. Heating
and cooling equipment and appliances shall be sized in accordance
with ACCA Manual S or other approved sizing methodologies based on
building loads calculated in accordance with ACCA Manual J or other
approved heating and cooling calculation methodologies.
| |
Exception: Heating and cooling equipment and appliance
sizing shall not be limited to the capacities determined in accordance
with Manual S where either of the following conditions applies:
| |
1. The specified equipment or appliance utilizes multistage
technology or variable refrigerant flow technology, and the loads
calculated in accordance with the approved heating and cooling calculation
methodology are within the range of the manufacturer's published
capacities for that equipment or appliance.
| |
2. The specified equipment or appliance manufacturer's
published capacities cannot satisfy both the total and sensible heat
gains calculated in accordance with the approved heating and cooling
calculation methodology and the next larger standard size unit is
specified.
| |
M1411.3.1 Auxiliary and secondary drain systems. In addition to the requirements of Section M1411.3, a secondary
drain or auxiliary drain pan shall be required for each cooling or
evaporator coil where damage to any building components will occur
as a result of overflow from the equipment drain pan or stoppage in
the condensate drain piping. Such piping shall maintain a minimum
horizontal slope in the direction of discharge or not less than 1/8
unit vertical in 12 units horizontal (one-percent slope). Drain piping
shall be not less than three-quarter-inch (19 mm) nominal pipe size.
One of the following methods shall be used:
| |
1. An auxiliary drain pan with a separate drain shall be installed
under the coils on which condensation will occur. The auxiliary pan
drain shall discharge to a conspicuous point of disposal to alert
occupants in the event of a stoppage of the primary drain. The pan
shall have a minimum depth of one and five-tenths (1.5) inches (38
mm), shall be not less than three (3) inches (76 mm) larger than the
unit or the coil dimensions in width and length and shall be constructed
of corrosion-resistant material. Galvanized sheet steel pans shall
have a minimum thickness of not less than 0.0236 inch (0.6010 mm)
(No. 24 26 Gage). Non-metallic pans shall have a minimum thickness
of not less than 0.0625 inch (1.6 mm).
| |
M1501.1 Outdoor discharge. The air removed by every
mechanical exhaust system shall be discharged to the outdoors in accordance
with Section M1506.2. Air shall not be exhausted into an attic, soffit,
ridge vent or crawl space.
| |
Exception: Whole-house ventilation-type attic fans
that discharge into the attic space of dwelling units having private
attics shall be permitted.
| |
M1502.4.1 Material and size. Exhaust ducts shall
have a smooth interior finish and be constructed of metal having a
minimum thickness of 0.0157 inch (0.3950 mm) (No. 28 30 gage). The
duct shall be four (4) inches (102 mm) nominal in diameter.
| |
M1502.4.2 Duct installation. Exhaust ducts shall
be supported at intervals not to exceed twelve (12) feet (3,658 mm)
and shall be secured in place. The insert end of the duct shall extend
into the adjoining duct or fitting in the direction of airflow. Exhaust
duct joints shall be sealed in accordance with Section M1601.4.1 and
shall be mechanically fastened. Ducts shall not be joined with screws
or similar fasteners that protrude more than 1/8 inch (3.2 mm) into
the inside of the duct.
| |
M1502.4.5.1 Specified length. The maximum length
of the exhaust duct shall be thirty-five (35) feet (10,688 mm) from
the connection to the transition duct from the dryer to the outlet
terminal. Where fittings are used, the maximum length of the exhaust
duct shall be reduced in accordance with Table M1502.4.5.1. The maximum
length of the exhaust duct does not include the transition duct.
| |
Exception: The maximum developed length may be
extended to fifty-five (55) feet if clearly labeled cleanouts are
provided within twelve (12) inches of the second elbow, at every elbow
thereafter, and at least every fifteen (15) feet of developed length
thereafter.
| |
M1503.4 Makeup air required. Exhaust hood systems
capable of exhausting in excess of 400 six hundred (600) cubic feet
per minute (0.19 m3/s) shall be mechanically
or naturally provided with makeup air at a rate approximately equal
to the exhaust air rate. Such makeup air systems shall be equipped
with not less than one (1) damper. Each damper shall be a gravity
damper or an electrically operated damper that automatically opens
when the exhaust system operates. Dampers shall be accessible for
inspection, service, repair and replacement without removing permanent
construction or any other ducts not connected to the damper being
inspected, serviced, repaired or replaced. Such makeup air systems
shall be equipped with a means of closure and shall be automatically
controlled to start and operate simultaneously with the exhaust system.
| |
M1506.3 Exhaust openings. Air exhaust openings
shall terminate not less than three (3) feet (914 mm) from property
lines; three (3) feet (914 mm) from operable and nonoperable openings
into the building and ten (10) feet (3,048 mm) from mechanical air
intakes except where the opening is located three (3) feet (914 mm)
above the air intake. Openings shall comply with Sections R303.5.2
and R303.6.
| |
M1601.1 Duct design. Duct systems serving heating,
cooling and ventilation equipment shall be installed in accordance
with the provisions of this Section, and ACCA Manual D the appliance
manufacturer's installation instructions or other approved methods.
| |
M1601.1.1 Above-ground duct systems. Above-ground
duct systems shall conform to the following:
| |
1. Equipment connected to duct systems shall be designed to
limit discharge air temperature to not greater than 250° F. (121°
C.).
| |
2. Factory-made ducts shall be listed and labeled in accordance
with UL 181 and installed in accordance with the manufacturer's
instructions.
| |
2. Fibrous glass duct construction shall conform to the SMACNA
Fibrous Glass Duct Construction Standards or NAIMA Fibrous Glass Duct
Construction Standards.
| |
3. Field-fabricated and shop-fabricated metal and flexible duct
constructions shall conform to the SMACNA HVAC Duct Construction Standards
- Metal and Flexible except as allowed by Table M1601.1.1. Galvanized
steel shall conform to ASTM A 653.
| |
4. The use of gypsum products to construct return air ducts
or plenums is permitted, provided that the air temperature does not
exceed 125° F. (52° C.) and exposed surfaces are not subject
to condensation.
| |
5. Duct systems shall be constructed of materials having a flame
spread index of not greater than 200.
| |
6. Stud wall cavities and the spaces between solid floor joists
to be used as non-ducted air plenums shall comply with the following
conditions:
| |
6.1. These cavities or spaces shall not be used as a plenum
for air supply.
| |
6.2. These cavities or spaces shall not be a part of required
fire-resistance-rated assembly.
| |
6.3. Stud wall cavities shall not convey air from more than
one floor level.
| |
6.4. Stud wall cavities and joist-space plenums shall be isolated
from adjacent concealed spaces by tight-fitting fireblocking in accordance
with Section R602.8.
| |
6.5. Stud wall cavities in the outside walls of building envelope
assemblies shall not be utilized as air plenums.
|
Table M1601.1.1
| |||||
---|---|---|---|---|---|
Duct Construction Minimum Sheet Metal Thickness for Single
Dwelling Unitsa
| |||||
Round Duct Diameter
(inches)
|
Static Pressure
| ||||
1/2-inch Water Gage
|
1-inch Water Gage
| ||||
Thickness
(inches)
|
Thickness
(inches)
| ||||
Galvanized
|
Aluminum
|
Galvanized
|
Aluminum
| ||
<12
|
0.013
|
0.018
|
0.013
|
0.018
| |
12 to 14
|
0.013
|
0.018
|
0.016
|
0.023
| |
15 to 17
|
0.016
|
0.023
|
0.019
|
0.027
| |
18
|
0.016
|
0.023
|
0.024
|
0.034
| |
19 to 20
|
0.019
|
0.027
|
0.024
|
0.034
|
Rectangular Duct Dimension
(largest dimension)
|
Static Pressure
| ||||
---|---|---|---|---|---|
1/2-inch Water Gage
|
1-inch Water Gage
| ||||
Thickness
(inches)
|
Thickness
(inches)
| ||||
Galvanized
|
Aluminum
|
Galvanized
|
Aluminum
| ||
<8
|
0.013
|
0.018
|
0.013
|
0.018
| |
9 to 10
|
0.013
|
0.018
|
0.016
|
0.023
| |
11 to 12
|
0.016
|
0.023
|
0.019
|
0.027
| |
13 to 16
|
0.019 0.016
|
0.027
|
0.019
|
0.027
| |
17 to 18
|
0.019
|
0.027
|
0.024
|
0.034
| |
19 to 20
|
0.024 0.019
|
0.034
|
0.024
|
0.034
|
For SI: 1 inch = 25.4 mm, 1 inch water gage = 249 Pa.
|
M1601.4.1 Joints, seams and connections. Joints
of duct systems shall be made substantially airtight in an unconditioned
area by means of tapes, mastics, liquid sealants, gasketing or other
approved closure systems. Closure systems used with rigid fibrous
glass ducts shall comply with UL 181A and shall be marked 181A-P for
pressure-sensitive tape, 181A-M for mastic or 181A-H for heat-sensitive
tape. Closure systems used with flexible air ducts and flexible air
connectors shall comply with UL 181B and shall be marked 181B-FX for
pressure-sensitive tape or 181B-M for mastic. Duct connections to
flanges of air distribution system equipment or sheet metal fittings
shall be mechanically fastened. Mechanical fasteners for use with
flexible non-metallic air ducts shall comply with UL 181B and shall
be marked 181B-C. Crimp joints for round metal ducts shall have a
contact lap of at least one and one-half (1 1/2) means of at
least three sheet metal screws or rivets equally spaced around the
joint. Closure systems used to seal metal ductwork shall be installed
in accordance with the manufacturer's installation instructions.
| |
Longitudinal and transverse joints, seams and connections in
metallic and nonmetallic ducts shall be constructed as specified in
SMACNA HVAC Duct Construction Standards Metal and Flexible and NAIMA
Fibrous Glass Duct Construction Standards. Joints, longitudinal and
transverse seams, and connections in ductwork shall be securely fastened
and sealed with welds, gaskets, mastics (adhesives), mastic plus embedded
fabric systems, liquid sealants or tapes. Tapes and mastics used to
seal fibrous glass ductwork shall be listed and labeled in accordance
with UL 181A and shall be marked "181A P" for pressure-sensitive tape,
"181A-M" for mastic or "181A-H" for heat sensitive tape.
| |
Tapes and mastic used to seal metallic and flexible air ducts
and flexible air connectors shall comply with UL 181B and shall be
marked "181B-FX" for pressure-sensitive tape or "181B-M" for mastic.
Duct connections to flanges of air distribution system equipment shall
be sealed and mechanically fastened. Mechanical fasteners for use
with flexible nonmetallic air ducts shall comply with UL 181B and
shall be marked 181 B-C. Crimp joints for round metallic ducts shall
have a contact lap of not less than one (1) inch (25 mm) and shall
be mechanically fastened by means of not less than three sheet metal
screws or rivets equally spaced around the joint.
| |
Closure systems used to seal all ductwork shall be installed
in accordance with the manufacturer's instructions.
| |
Exceptions:
| |
1. Spray polyurethane foam shall be permitted to be applied
without additional joint seals.
| |
2. Where a duct connection is made that is partially inaccessible,
three (3) screws or rivets shall be equally spaced on the exposed
portion of the joint so as to prevent a hinge effect.
| |
3. For ducts having a static pressure classification of less
than two (2) inches of water column (500 Pa), additional closure systems
shall not be required for continuously welded joints and seams and
locking type joints and seams of other than snap lock and button-lock
types.
| |
Continuously welded and locking-type longitudinal joints and
seams in ducts operating at static pressure less than two (2) inches
of water column (500 Pa) pressure classification shall not require
additional closure systems.
| |
M1602.2 Return air openings. Return air openings
for heating, ventilation and air conditioning systems shall comply
with all of the following:
| |
1. Openings shall not be located less than ten (10) feet (3,048
mm) measured in any direction from an open combustion chamber or draft
hood of another appliance located in the same room or space.
| |
2. The amount of return air taken from any room or space shall
be not greater than the flow rate of supply air delivered to such
room or space.
| |
2. Return and transfer openings shall be sized in accordance
with the appliance or equipment manufacturers' installation instructions,
Manual D or the design of the registered design professional.
| |
3. Return air shall not be taken from a closet, bathroom, toilet
room, kitchen, garage, mechanical room, boiler room, furnace room
or unconditioned attic.
| |
Exceptions:
| |
1. Taking return air from a kitchen is not prohibited where
such return air openings serve the kitchen only, and are located not
less than ten (10) feet (3,048 mm) from the cooking appliances.
| |
2. Dedicated forced-air systems serving only the garage shall
not be prohibited from obtaining return air from the garage.
| |
3. Taking return air from an unconditioned crawl space shall
not be accomplished through a direct connection to the return side
of a forced-air furnace. Transfer openings in the crawl space enclosure
shall not be prohibited.
| |
4. Return air from one dwelling unit shall not be discharged
into another dwelling unit.
| |
G2408.4 (305.7) Clearances from grade. Equipment
and appliances installed at grade level shall be supported on a level
concrete slab or other approved material extending not less than two
(2) inches (76 50.8 mm) above adjoining grade or shall be suspended
not less than six (6) inches (152 mm) above adjoining grade. Such
supports shall be installed in accordance with the manufacturer's
installation instructions.
| |
G2409.1 (308.1) Scope. This Section shall govern
the reduction in required clearances to combustible materials, including
gypsum board, and combustible assemblies for chimneys, vents, appliances,
devices and equipment. Clearance requirements for air-conditioning
equipment and central heating boilers and furnaces shall comply with
Sections G2409.3 and G2409.4.
| |
G2412.9 (401.9) Identification. Each length of
pipe and tubing and each pipe fitting, utilized in a fuel gas system,
shall bear the identification of the manufacturer.
| |
G2412.10 (401.10) Third-party testing and certification. Piping, tubing and fittings shall comply with the applicable referenced
standards, specifications and performance criteria of this code and
shall be identified in accordance with Section G2412.9. Piping, tubing
and fittings shall either be tested by an approved third-party testing
agency or certified by an approved third-party certification agency.
| |
G2415.3 (404.3) Prohibited locations. Piping shall
not be installed in or through a ducted supply, return or exhaust,
or a clothes chute, chimney or gas vent, dumbwaiter or elevator shaft.
Piping installed downstream of the point of delivery shall not extend
through any townhouse unit other than the unit served by such piping.
| |
G2428.3.16 (504.3.20) Chimney and vent locations. Tables G2428.3(1), G2428.3(2), G2428.3(3) and G2428.3(4) shall be
used only for chimneys and vents not exposed to the outdoors below
the roof line. A Type B vent or listed chimney lining system passing
through an unused masonry chimney flue shall not be considered to
be exposed to the outdoors. Where vents extend outdoors above the
roof more than five (5) feet (1,524 mm) higher than required by Figure
G2427.6.3 and where vents terminate in accordance with the Section
G2427.6.3, Item 2, the outdoor portion of the vent shall be enclosed
as required by this section for vents not considered to be exposed
to the outdoors or such venting system shall be engineered. A Type
B vent shall not be considered to be exposed to the outdoors where
it passes through an unventilated enclosure or chase insulated to
a value of not less than R8.
| |
G2439.7.4.1 (614.8.4.1) Specified length. The maximum
length of the exhaust duct shall be 35 feet (10,688 mm) from the connection
to the transition duct from the dryer to the outlet terminal. Where
fittings are used, the maximum length of the exhaust duct shall be
reduced in accordance with Table G2439.7.4.1. The maximum length of
the exhaust duct does not include the transition duct.
| |
Exception: The maximum developed length may be
extended to fifty-five (55) feet if clearly labeled cleanouts are
provided within twelve (12) inches of the second elbow, at every elbow
thereafter, and at least every fifteen (15) feet of developed length
thereafter.
| |
G2442.4 (618.4) Prohibited sources. Outdoor or
return air for forced-air heating and cooling systems shall not be
taken from the following locations:
| |
1. Closer than ten (10) feet (3,048 mm) from an appliance vent
outlet, a vent opening from a plumbing drainage system or the discharge
outlet of an exhaust fan, unless the outlet is three (3) feet (914
mm) above the outside air inlet.
| |
2. Where there is the presence of objectionable odors, fumes
or flammable vapors; or where located less than ten (10) feet (3,048
mm) above the surface of any abutting public way or driveway; or where
located at grade level by a sidewalk, street, alley or driveway.
| |
3. A hazardous or insanitary location or a refrigeration machinery
room as identified in the International Mechanical Code.
| |
4. A room or space, the volume of which is less than twenty-five
percent (25%) of the entire volume served by such system. Where connected
by a permanent opening having an area sized in accordance with Section
G2442.2, adjoining rooms or spaces shall be considered as a single
room or space for the purpose of determining the volume of such rooms
or spaces.
| |
Exception: The minimum volume requirement shall
not apply where the amount of return air taken from a room or space
is less than or equal to the amount of supply air delivered to such
room or space.
| |
5. A room or space containing an appliance where such a room
or space serves as the sole source of return air.
| |
Exception: This shall not apply where:
| |
1. The appliance is a direct-vent appliance or an appliance
not requiring a vent in accordance with Section G2425.8.
| |
2. The room or space complies with the following requirements:
| |
2.1. The return air shall be taken from a room or space having
a volume exceeding one cubic foot for each 10 Btu/h (9.6L/W) of combined
input rating of all fuel-burning appliances therein.
| |
2.2. The volume of supply air discharged back into the same
space shall be approximately equal to the volume of return air taken
from the space.
| |
2.3. Return-air inlets shall not be located within ten (10)
feet (3,048 mm) of a draft hood in the same room or space or the combustion
chamber of any atmospheric burner appliance in the same room or space.
| |
3. Rooms or spaces containing solid-fuel-burning appliances,
provided that return-air inlets are located not less than ten (10)
feet (3,048 mm) from the firebox of such appliances.
| |
6. A closet, bathroom, toilet room, kitchen, garage, boiler
room, furnace room or unconditioned attic.
| |
Exceptions:
| |
1. Where return air intakes are located not less than ten (10)
feet (3,048 mm) from cooking appliances and serve only the kitchen
area, taking return air from a kitchen area shall not be prohibited.
| |
2. Dedicated forced air systems serving only a garage shall
not be prohibited from obtaining return air from the garage.
| |
3. Where a closet is provided with a supply register, taking
return air from the closet shall not be prohibited.
| |
7. A crawl space by means of direct connection to the return
side of a forced-air system. Transfer openings in the crawl space
enclosure shall not be prohibited.
| |
P2503.5.1 Rough plumbing. DWV systems shall be
tested on completion of the rough piping installation by water or,
for piping systems other than plastic, by air without evidence of
leakage. Either test shall be applied to the drainage system in its
entirety or in sections after rough-in piping has been installed,
as follows:
| |
1. Water test. Each section shall be filled with water to a
point not less than five (5) feet (1,524 mm) above the highest fitting
connection in that section, or to the highest point in the completed
system. Water shall be held in the section under test for a period
of fifteen (15) minutes. The system shall prove leak free by visual
inspection.
| |
2. Air test. The portion under test shall be maintained at a
gauge pressure of five (5) pounds per square inch (psi) (34 kPa) or
ten (10) inches of mercury column (34 kPa). This pressure shall be
held without introduction of additional air for a period of fifteen
(15) minutes.
| |
P2603.4 Pipes through foundation walls. A pipe
that passes through a foundation wall shall be provided with a relieving
arch, or a pipe sleeve shall be built into the foundation wall. The
sleeve shall be two (2) pipe sizes greater than the pipe passing through
the wall.
| |
1. In Section P2603.5.1, insert "30" into the first [NUMBER].
| |
2. In Section P2603.5.1, insert "30" into the second [NUMBER].
| |
P2690.1 Identification. Each length of pipe and
each pipe fitting, trap, fixture, material and device utilized in
a plumbing system shall bear the identification of the manufacturer
and any markings required by the applicable referenced standards.
Nipples created from the cutting and threading of approved pipe shall
not be required to be identified.
| |
Exception: Where the manufacturer identification
cannot be marked on pipe fittings and pipe nipples because of the
small size of such fittings, the identification shall be printed on
the item packaging or on documentation provided with the item.
| |
P2609.2 Installation of materials. Materials used
shall be installed in strict accordance with the standards under which
the materials are accepted and approved. In the absence of such installation
procedures, the manufacturer's instructions shall be followed.
Where the requirements of referenced standards or manufacturer's
instructions do not conform to minimum provisions of this code, the
provisions of this code shall apply.
| |
P2609.3 Plastic pipe, fittings and components. Plastic
pipe, fittings and components shall be third-party certified as conforming
to NSF 14.
| |
P2609.4 Third-party certification. Plumbing products
and materials required by the code to be in compliance with a referenced
standard shall be listed by a third-party certification agency as
complying with the referenced standards. Products and materials shall
be identified in accordance with Section P2609.1.
| |
P2706.3 Prohibited waste receptors. Plumbing fixtures
that are used for washing or bathing shall not be used to receive
the discharge of indirect waste piping.
| |
Exceptions:
| |
1. A kitchen sink trap is acceptable for use as a receptor for
a dishwasher.
| |
2. A laundry tray is acceptable for use as a receptor for a
clothes-washing machine.
| |
3. A drain or waste pipe above a trap is acceptable for use
as a receptor for mechanical equipment condensate drains.
| |
P2801.8 Water heater seismic bracing. In Seismic
Design Categories D0, D1 and D2 and townhouses in Seismic Design Category
C, water heaters shall be anchored or strapped in the upper one-third
(1/3) and in the lower one-third (1/3) of the appliance to resist
a horizontal force equal to one-third (1/3) of the operating weight
of the water heater, acting in any horizontal direction, or in accordance
with the appliance manufacturer's recommendations.
| |
P2903.5 Water hammer. The flow velocity of the
water distribution system shall be controlled to reduce the possibility
of water hammer. A water-hammer arrestor shall be installed where
quick-closing valves are used. Water-hammer arrestors shall be installed
in accordance with the manufacturer's installation instructions.
Water-hammer arrestors shall conform to ASSE 1010.
| |
P2904.1 General. When installed, the design and
installation of residential fire sprinkler systems shall be in accordance
with NFPA 13D or Section 2904, which shall be considered equivalent
to NFPA 13D. Partial residential sprinkler systems shall be permitted
to be installed only in buildings not required to be equipped with
a residential sprinkler system. Section P2904 shall apply to stand-alone
and multipurpose wet-pipe sprinkler systems that do not include the
use of antifreeze. A multipurpose fire sprinkler system shall provide
domestic water to both fire sprinklers and plumbing fixtures. A stand-alone
sprinkler system shall be separate and independent from the water
distribution system. A backflow preventer shall not be required to
separate a stand-alone system from the water distribution system.
| |
R3201.2.1 Trap seal protection. Trap seals of emergency
floor drain traps and traps subject to evaporation shall be protected
by one of the methods in Sections P3201.2.1.1 through P3201.2.1.4.
| |
Exception: Basement floor drains with a condensate
line draining to it.
| |
E3609.3 Bonding for other systems. An intersystem
bonding termination for connecting intersystem bonding conductors
required for other systems shall be provided external to enclosures
at the service equipment or metering equipment enclosure and at the
disconnecting means for any additional buildings or structures. The
intersystem bonding termination shall comply with the following:
| |
1. It shall be accessible for connection and inspection.
| |
2. It shall consist of a set of terminals with the capacity
for connection of not less than three (3) intersystem bonding conductors.
| |
3. It shall not interfere with opening of the enclosure for
a service, building or structure disconnecting means, or metering
equipment.
| |
4. Where located at the service equipment, it shall be securely
mounted and electrically connected to an enclosure for the service
equipment, to the meter enclosure, or to an exposed nonflexible metallic
service raceway, or shall be mounted at one of these enclosures and
connected to the enclosure or to the grounding electrode conductor
with a 6 AWG or larger copper conductor.
| |
5. Where located at the disconnecting means for a building or
structure, it shall be securely mounted and electrically connected
to the metallic enclosure for the building or structure disconnecting
means, or shall be mounted at the disconnecting means and connected
to the metallic enclosure or to the grounding electrode conductor
with a 6 AWG or larger copper conductor.
| |
6. It shall be listed as grounding and bonding equipment. (250.94)
| |
E3701.5.1 Disconnecting means. Each multiwire branch
circuit shall may be provided with a means that will simultaneously
disconnect all ungrounded conductors at the point where the branch
circuit originates. [210.4(B)]
| |
E3901.2.2 Wall Space. As used in this Section,
a wall space shall include the following.
| |
1. Any space that is two (2) feet or more in width, including
space measured around corners, and that is unbroken along the floor
line by doorways and similar openings, fireplaces, and fixed cabinets.
| |
2. The space occupied by fixed panels in exterior walls, excluding
sliding panels.
| |
3. The space created by fixed room dividers such as railings
and freestanding bar type counters.
| |
E3902.2 Garage and accessory building receptacles. 125-volt, single-phase, 15- or 20-ampere receptacles installed in
garage and grade-level portions of unfinished accessory buildings
used for storage or wok areas shall have ground-fault circuit-interrupter
protection for personnel. [210.8(A)(2)]
| |
Exception: Fastened-in-place appliances or outlets
designated for refrigerators/freezers.
| |
E3902.5 Unfinished basement receptacles. 125-volt,
single-phase, 15- and 20-ampere receptacles installed in unfinished
basements shall have ground-fault circuit-interrupter protection for
personnel. For purposes of this Section, unfinished basements are
defined as portions or areas of the basement not intended as habitable
rooms and limited to storage areas, work areas, and similar areas.
[210.8(A)(5)]
| |
Exceptions:
| |
1. A receptacle supplying only a permanently installed fire
alarm or burglar alarm system. Receptacles installed in accordance
with this exception shall not be considered as meeting the requirements
of Section E3901.9.
| |
2. Fastened-in-place appliances or outlets designated for refrigerators/freezers.
| |
E3902.6 Kitchen receptacles. 125-volt, single-phase,
15- and 20-ampere receptacles that serve countertop surfaces shall
have ground-fault circuit-interrupter protection for personnel. [210.8(A)(6)]
| |
Exception: Fastened-in-place appliances or outlets
designated for refrigerators/freezers.
| |
E3902.9 Laundry areas. 125 volt, single-phase,
15- and 20-ampere receptacles installed in laundry areas shall have
ground-fault circuit-interrupter protection for personnel. [210.8(A)(9)]
| |
E3902.10 Kitchen dishwasher branch circuit. Ground-fault
circuit-interrupter protection shall be provided for outlets that
supply dishwashers in dwelling unit locations. [210.8(D)]
| |
E3902.14 Location of ground-fault circuit interrupters. Ground-fault circuit interrupters shall be installed only in a readily
accessible location. [210.8(A)]
| |
E3902.16 Arc-fault circuit-interrupter protection. Branch circuits that supply 120-volt, single-phase, 15- and 20-ampere
outlets installed in kitchens, family rooms, dining rooms, living
rooms, parlors, libraries, dens, bedrooms, sunrooms, recreation rooms,
closets, hallways, laundry areas and similar rooms or areas shall
be protected by any of following: [120.12(a)]
| |
1. A listed combination-type arc fault circuit interrupter,
installed to provide protection of the entire branch circuit. [210.12(A)(1)]
| |
2. A listed branch/feeder type AFCI installed at the origin
of the branch circuit in combination with a listed outlet-branch-circuit-type
arc fault circuit interrupter installed at the first outlet box on
the branch circuit. The first outlet box in the branch circuit shall
be marked to indicate that it is the first outlet of the circuit.
[210.12(A)(2)]
| |
3. A listed supplemental arc protection circuit breaker installed
at the origin of the branch circuit in combination with a listed outlet-branch-circuit-type
arc fault circuit interrupter installed at the first outlet box on
the branch circuit where all of the following conditions are met:
| |
3.1. The branch circuit wiring shall be continuous from the
branch circuit overcurrent device to the outlet-branch-circuit arc
fault circuit interrupter.
| |
3.2. The maximum length of the branch circuit wiring from the
branch circuit overcurrent device to the first outlet shall not exceed
fifty (50) feet (15.2 m) for 14 AWG conductors and seventy (70) feet
(21.3 m) for 12 AWG conductors.
| |
3.3 The first outlet box in the branch circuit shall be marked
to indicate that it is the first outlet of the circuit. [210.12(A)(3)]
| |
4. A listed outlet-branch-circuit-type arc fault circuit interrupter
installed at the first outlet on the branch circuit in combination
with a listed branch circuit overcurrent protective device where all
of the following conditions are met:
| |
4.1 The branch circuit wiring shall be continuous from the branch
circuit overcurrent device to the outlet-branch-circuit arc fault
circuit interrupter.
| |
4.2 The maximum length of the branch circuit wiring from the
branch circuit overcurrent device to the first outlet shall not exceed
fifty (50) feet (15.2 m) for 14 AWG conductors and seventy (70) feet
(21.3 m) for 12 AWG conductors.
| |
4.3 The first outlet box in the branch circuit shall be marked
to indicate that it is the first outlet on the circuit.
| |
4.4 The combination of the branch circuit overcurrent device
and outlet branch circuit AFCI shall be identified as meeting the
requirements for a system combination type AFCI and shall be listed
as such. [210.12(A)(4)]
| |
5. Where metal outlet boxes and junction boxes and RMC, IMC,
EMT, Type MC or steel armored Types AC cables meeting the requirements
of Section E3908.8, metal wireways or metal auxiliary gutters are
installed for the portion of the branch circuit between the branch
circuit overcurrent device and the first outlet, a listed outlet branch
circuit type AFCI installed at the first outlet shall be considered
as providing protection for the remaining portion of the branch circuit.
[210.12(A)(5)]
| |
6. Where a listed metal or nonmetallic conduit or tubing or
Type MC cable is encased in not less than two (2) inches (50.8 mm)
of concrete for the portion of the branch circuit between the branch
circuit overcurrent device and the first outlet, a listed outlet branch
circuit type AFCI installed at the first outlet shall be considered
as providing protection for the remaining portion of the branch circuit.
[210.12(A)(6)]
| |
Exception: AFCI protection is not required for
an individual branch circuit supplying only a fire alarm system where
the branch circuit is wired with metal outlet and junction boxes and
RMC, IMC, EMT or steel sheathed armored cable Type AC or Type MC meeting
the requirements of Section E3908.8.
| |
E3902.17 Arc-fault circuit interrupter protection for
branch circuit extensions or modifications. Where branch circuit
wiring is modified, replaced, or extended in any of the areas specified
in Section E3902.16, the branch circuit shall be protected by one
of the following:
| |
1. A combination -type AFCI located at the origin of the branch
circuit.
| |
2. An outlet branch circuit type AFCI located at the first receptacle
outlet of the existing branch circuit. [210.12(B)]
| |
Exception: AFCI protection shall not be required
where the extension of the existing conductors is not more than six
(6) feet (1.8 m) 30 feet (9.5 m) in length and does not include any
additional outlets or devices. [210.12(B) Exception]
| |
E4002.14 Tamper resistant receptacles. In areas
specified in Section E3901.1, 125-volt, 15- and 20-ampere receptacles
shall be listed tamper-resistant receptacles. [406.12(A)]
| |
Exception: Receptacles in the following locations
shall not be required to be tamper-resistant.
| |
1. Receptacles located more than 5.5 feet (1,676 mm) above the
floor.
| |
2. Receptacles that are part of a luminaire or appliance.
| |
3. A single receptacle for a single appliance or a duplex receptacle
for two (2) appliances where such receptacles are located in spaces
dedicated for the appliances served and, under conditions of normal
use, the appliances are not easily moved from one place to another.
The appliances shall be cord-and-plug-connected to such receptacles
in accordance with Section E3909.4. [406.12(A) Exception]
|