[Ord. No. 519 §1, 2-1-1988]
A. 
Purpose. The purpose of this Chapter is:
1. 
To protect the public potable water supply from contamination or pollution by containing within the consumer's internal distribution system or private water system contaminants or pollutants which could backflow through the service connection into the public potable water supply system.
2. 
To promote the elimination, containment, isolation, or control of existing cross-connections, actual or potential, between the public or consumer's potable water system and non-potable water systems, plumbing fixtures, and industrial-process systems.
3. 
To provide for the maintenance of a continuing program of cross-connection control which will systematically and effectively prevent the contamination or pollution of all potable water systems.
B. 
Application. This Chapter shall apply to all premises served by the public potable water system of the City of Tipton, Missouri.
C. 
Policy. This Chapter shall be reasonably interpreted by the Superintendent of Public Works. It is the Superintendent of Public Works's intent to recognize the varying degrees of hazard and to apply the principal that the degree of protection shall be commensurated with the degree of hazard.
The Superintendent of Public Works shall be primarily responsible for protection of the public potable water distribution system from contamination or pollution due to backflow or contaminants or pollutants through the water service and maintain the program to control cross-connections. The Superintendent of Public Works and consumer are jointly responsible for preventing contamination of the water system.
If, in the judgment of the Superintendent of Public Works or his/her authorized representative, cross-connection protection is required through either piping modification or installation of an approved backflow prevention device, due notice shall be given to the consumer. The consumer shall immediately comply by providing the required protection at his/her own expense; and failure, refusal, or inability on the part of the consumer to provide such protection shall constitute grounds for discontinuing water service to the premises until such protection has been provided.
[Ord. No. 519 §2, 2-1-1988]
The following definitions shall apply in the interpretation and enforcement of this Chapter:
AIR-GAP SEPARATION
The unobstructed vertical distance through the free atmosphere between the lowest opening from any pipe or faucet supplying water to a tank, plumbing fixture, or other device and the overflow level rim of the receptacle, and shall be at least double the diameter of the supply pipe measured vertically above the flood level rim of the vessel, but in no case less than one (1) inch.
AUXILIARY WATER SUPPLY
Any water source or system, other than the public water supply, that may be available in the building or premises.
BACKFLOW
The flow other than the intended direction of flow, of any foreign liquids, gasses, or substances into the distribution system of a public water supply.
BACKFLOW PREVENTION DEVICE
Any device, method, or type of construction intended to prevent backflow into a potable water system.
CONSUMER
The owner or person in control of any premises supplied by or in any manner connected to a public water system.
CONTAINMENT
Protection of the public water supply by installing a cross-connection control device or air-gap separation on the main service line to a facility.
CONTAMINATION
An impairment of the quality of the water by sewage, process fluids, or other wastes to a degree which could create an actual hazard to the public health through poisoning or through spread of disease by exposure.
CROSS-CONNECTION
Any physical link between a potable water supply and any other substance, fluid, or source, which makes possible contamination of the potable water supply due to the reversal of flow of the water in the piping or distribution system.
HAZARD, DEGREE OF
An evaluation of the potential risk to public health and the adverse effect of the hazard upon the potable water system.
1. 
Hazard, Health: Any condition, device, or practice in the water supply system and its operation which could create or may create a danger to the health and well-being of the water consumer.
2. 
Hazard, Plumbing: A plumbing type cross-connection in a consumer's potable water system that has not been properly protected by a vacuum breaker, air-gap separation or backflow prevention device.
3. 
Hazard, Pollutional: An actual or potential threat to the physical properties of the water system or to the potability of the public or the consumer's potable water system but which would constitute a nuisance or be aesthetically objectionable or could cause damage to the system or its appurtenances, but would not be dangerous to health.
4. 
Hazard, System: An actual or potential threat of severe damage to the physical properties of the public potable water system or the consumer's potable water system, or of a pollution or contamination which would have a protracted effect on the quality of the potable water in the system.
INDUSTRIAL PROCESS SYSTEM
Any system containing a fluid or solution, which may be chemically, biologically, or otherwise contaminated or polluted in a form or concentration such as would constitute a health, system, pollutional, or plumbing hazard if introduced into a potable water supply.
ISOLATION
Protection of a facility service line by installing a cross-connection control device of air-gap separation on an individual fixture, appurtenance, or system.
POLLUTION
The presence of any foreign substance (organic, inorganic or biological) in water which tends to degrade its quality so as to constitute a hazard or impair the usefulness of the water to a degree which does not create an actual hazard to the public health but which does adversely and unreasonably affect such waters for domestic use.
PUBLIC POTABLE WATER SYSTEM
Any publicly or privately owned water system supplying water to the general public which is satisfactory for drinking, culinary, and domestic purposes and meets the requirements of the Missouri Department of Natural Resources.
SERVICE CONNECTION
The terminal end of a service line from the public water system. If a meter is installed at the end of the service, then the "service connection" means the downstream end of the meter.
SUPERINTENDENT OF PUBLIC WORKS
The owner, operator, or individual in responsible charge of the public water system.
[Ord. No. 519 §3, 2-1-1988]
A. 
No water service connection shall be installed or maintained to any premises where actual or potential cross-connections to the public potable or consumer's water system may exist unless such actual or potential cross-connections are abated or controlled to the satisfaction of the Superintendent of Public Works, and as required by the laws and regulations of the Missouri Department of Natural Resources.
B. 
No connection shall be installed or maintained whereby an auxiliary water supply may enter a public potable or consumer's water system unless such auxiliary water supply and the method of connection and use of such supply shall have been approved by the Superintendent of Public Works and the Missouri Department of Natural Resources.
C. 
No water service connection shall be installed or maintained to any premises in which the plumbing system, facilities, and fixtures have not been constructed and installed using acceptable plumbing practices considered by the Superintendent of Public Works as necessary for the protection of health and safety.
[Ord. No. 519 §4, 2-1-1988]
A. 
The consumer's premises shall be open at all reasonable times to the Superintendent of Public Works, or his/her authorized representative, for the conduction of surveys and investigations of water use practices within the consumer's premises to determine whether there are actual or potential cross-connections to the consumer's water system through which contaminants or pollutants could backflow into the public potable water system.
B. 
On request by the Superintendent of Public Works or his/her authorized representative, the consumer shall furnish information on water use practices within his/her premises.
C. 
It shall be the responsibility of the water consumer to conduct periodic surveys of water use practices on his/her premises to determine whether there are actual or potential cross-connections to his/her water system through which contaminants or pollutants could backflow into his/her or the public potable water system.
[Ord. No. 519 §5, 2-1-1988]
A. 
The type of protection required by this Chapter shall depend on the degree of hazard which exists, as follows:
1. 
An approved air-gap separation shall be installed where the public potable water system may be contaminated with substances that could cause a severe health hazard.
2. 
An approved air-gap separation or a reduced pressure principle backflow prevention device shall be installed where the public potable water system may be contaminated with a substance that could cause a system or health hazard.
3. 
An approved air-gap separation or an approved reduced pressure backflow prevention device or an approved double-check valve assembly shall be installed where the public potable water system may be polluted with substances that could cause a pollutional hazard not dangerous to health.
[Ord. No. 519 §6, 2-1-1988]
A. 
An approved backflow prevention device shall be installed on each service line to a consumer's water system serving premises where, in the judgment of the Superintendent of Public Works or the Missouri Department of Natural Resources, actual or potential hazards to the public potable water system exist. The type and degree of protection required shall be commensurate with the degree of hazard.
B. 
An approved air-gap separation or reduced pressure principal backflow prevention device shall be installed at the service connection or within any premises where, in the judgment of the Superintendent of Public Works or the Missouri Department of Natural Resources, the nature and extent of activities on the premises, or the materials used in connection with the activities, or materials stored on the premises, would present an immediate and dangerous hazard to health should a cross-connection occur, even though such cross-connection may not exist at the time the backflow prevention device is required to be installed. This includes but is not limited to the following situations:
1. 
Premises having an auxiliary water supply, unless the quality of the auxiliary supply is acceptable to the Superintendent of Public Works and the Missouri Department of Natural Resources.
2. 
Premises having internal cross-connections that are not correctable, or intricate plumbing arrangements which make it impractical to ascertain whether or not cross-connections exist.
3. 
Premises where entry is restricted so that inspection for cross-connections cannot be made with sufficient frequency or at sufficiently short notice to assure the cross-connections do not exist.
4. 
Premises having a repeated history of cross-connections being established or re-established.
5. 
Premises, which due to the nature of the enterprise therein, are subject to recurring modification or expansion.
6. 
Premises on which any substance is handled under pressure so as to permit entry into the public water supply, or where a cross-connection could reasonably be expected to occur. This shall include the handling of process waters and cooling waters.
7. 
Premises where materials of a toxic or hazardous nature are handled such that if backsiphonage or backpressure should occur, a serious health hazard may result.
C. 
The following types of facilities fall into one (1) or more of the categories of premises where an approved air-gap separation or reduced pressure principle backflow prevention device is required by the Superintendent of Public Works and the Missouri Department of Natural Resources to protect the public water supply and must be installed at these facilities unless all hazardous or potentially hazardous conditions have been eliminated or corrected by other methods to the satisfaction of the Superintendent of Public Works and the Missouri Department of Natural Resources:
Approved backflow prevention devices are required for the following facilities:
Auxiliary Water Systems
A.G., R.P.D.
Beverage Bottling Plants
A.G., R.P.D. or D.C.A.*
Packing Houses
A.G., R.P.D.
Cold Storage Plants
A.G., R.P.D.
Film Laboratories
A.G., R.P.D.
Hospitals, Medical Buildings
Sanitariums, Morgues, Autopsy Facilities
A.G. or R.P.D.
Nursing or Convalescent Homes and Clinics
D.C.A.
Irrigation system, separate from domestic systems, such as parks, playgrounds, cemeteries, golf courses, schools, estates
A.G. or R.P.D.
Lawn sprinkling systems adjunct to domestic systems
D.C.A.
Sewage Treatment Plants
A.G. or R.P.D.
Power Plants
R.P.D.
Laundries and Laundromats
R.P.D.
Car Washing Facilities
R.P.D.
Water Loading Stations
A.G. or D.C.A.
Industries using toxic substances
R.P.D.
Stockyards
R.P.D.
(*
 "A.G." refers to air-gap; "R.P.D." refers to reduced pressure backflow device; "D.C.A." refers to double-check valve assembly.)
D. 
The Superintendent of Public Works and the Missouri Department of Natural Resources, at their discretion, may require a device at other facilities dangerous to public health.
[Ord. No. 519 §7, 2-1-1988]
A. 
Any backflow prevention device required by this Chapter shall be of a model or construction approved by the Superintendent of Public Works and the Missouri Department of Natural Resources.
1. 
Air-gap separation to be approved shall be at least twice the diameter of the supply pipe, measured vertically above the top rim of the vessel, but in no case less than one (1) inch.
2. 
A double-check valve assembly for a reduced pressure principle backflow prevention device shall be approved by the Superintendent of Public Works, and shall appear on the current "list of approved backflow prevention devices" established by the Missouri Department of Natural Resources.
B. 
Existing backflow prevention devices approved by the Superintendent of Public Works at the time of installation and properly maintained shall, except for inspection and maintenance requirements, be excluded from the requirements of this Chapter so long as the Superintendent of Public Works is assured that they will satisfactorily protect the water system. Whenever the existing device is moved from its present location, or requires more than minimum maintenance, or when the Superintendent of Public Works finds that the maintenance constitutes a hazard to health, the unit shall be replaced by a backflow prevention device meeting the requirements of this Chapter.
[Ord. No. 519 §8, 2-1-1988]
A. 
Backflow prevention devices required by this Chapter shall be installed at a location and in a manner approved by the Superintendent of Public Works and shall be installed at the expense of the water consumer.
B. 
Backflow prevention devices installed on the service line to the consumer's water system shall be located on the consumer's side of the water meter, as close to the meter as is reasonably practical, and prior to any other connection.
C. 
Backflow prevention devices shall be located so as to be readily accessible for maintenance and testing, protected from freezing, and where no part of the device will be submerged or subject to flooding by any fluid.
[Ord. No. 519 §9, 2-1-1988]
A. 
It shall be the duty of the consumer at any premises on which backflow prevention devices required by this Chapter are installed to have inspections, tests, and overhauls made in accordance with the following schedule or more often where inspections indicate a need.
1. 
Air-gap separations shall be inspected at the time of installation and at least every twelve (12) months thereafter.
2. 
Double-check valve assemblies shall be inspected and tested for tightness at the time of installation and at least every twelve (12) months thereafter. They shall be dismantled, inspected internally, cleaned, and repaired whenever needed and at least every thirty (30) months.
3. 
Reduced pressure principle backflow prevention devices shall be inspected and tested for tightness at the time of installation and at least every twelve (12) months thereafter. They shall be dismantled, inspected internally, cleaned, and repaired whenever needed and at least every five (5) years.
B. 
Inspections, tests, and overhauls of backflow prevention devices shall be made at the expense of the water consumer and shall be performed by the State of Missouri certified backflow prevention device tester.
C. 
Whenever backflow prevention devices required by this Chapter are found to be defective, they shall be repaired or replaced at the expense of the consumer without delay.
D. 
The water consumer must maintain a complete record of each backflow prevention device from purchase to retirement. This shall include a comprehensive listing that includes a record of all tests, inspections, and repairs. Copies of installation records, records of inspection, tests, repairs, and overhauls shall be sent to the Superintendent of Public Works no later than five (5) working days from the time of installation, inspection, tests, repairs or overhauls. This correspondence should be addressed to the: City of Tipton, Box 517, Attn: City Engineer, Tipton, Missouri 65081.
E. 
Backflow prevention devices shall not be bypassed, made inoperative, removed, or otherwise made ineffective without specific authorization by the Superintendent of Public Works.
[Ord. No. 519 §10, 2-1-1988]
A. 
The Superintendent of Public Works shall deny or discontinue, after reasonable notice to the occupants thereof, the water service to any premises wherein any backflow prevention device required by this Chapter is not installed, tested, and maintained in a manner acceptable to the Superintendent of Public Works, or if it is found that the backflow prevention device has been removed or bypassed, or if an unprotected cross-connection exists on the premises.
B. 
Water service to such premises shall not be restored until the consumer has corrected or eliminated such conditions or defects in conformance with this Chapter to the satisfaction of the Superintendent of Public Works.