[Adopted 3-4-2016 by Ord.
No. 14-26]
The purpose of this article is to outline the wastewater pretreatment
requirements for food preparation establishments and other commercial
facilities that discharge fats, oils, and grease in their wastewater
flow. All new and existing facilities that generate and discharge
fats, oils, and grease (FOG) in their wastewater flow shall install,
operate, and maintain a FOG pretreatment system. The requirements
of this article shall supplement and be in addition to the requirements
of the Town of Stratford's Code.
As used in this article, the following terms shall have the
meanings indicated:
A discharge authorized by this article.
The individual responsible for overseeing daily operation
of the food preparation establishment and who is responsible for overseeing
the food preparation establishment's compliance with the FOG pretreatment
program.
Any food preparation establishment at which an authorized
discharge occurs.
Any fats, oils and grease generated from the food preparation
process as identified by the most current EPA method as listed in
40 CFR 136.3.
A passive tank installed outside a building and designed
to remove fats, oils and grease from flowing wastewater while allowing
wastewater to flow through it, and as further defined herein.
Refers to properly installed and operated FOG interceptors,
FOG recovery units, and other alternate system as approved by the
Water Pollution Control Authority.
All active indoor mechanical systems designed to remove fats,
oils and grease by physical separation from flowing wastewater, as
further defined herein.
Class III and IV food service establishments and any other
facility discharging fats, oils and grease above the effluent limits
in § 5(c)(2) of the Connecticut Department of Energy and
Environmental Protection's General Permit for the Discharge of Wastewater
Associated with Food Preparation Establishments,[1] such as, but not limited to, restaurants, hotel kitchens,
hospital kitchens, school kitchens, bars, factory cafeterias and clubs.
Fats, oils, and grease generated from food preparation processes
that have been contaminated during the food preparation process, thereby
prohibiting this material from being rendered.
Written notification from the Water Pollution Control Authority
for authorization to install and/or operate an alternate FOG pretreatment
system.
A treatment works that is permitted by the Connecticut Department
of Energy and Environmental Protection for the separation and disposal
by incineration or other methods of FOG from the wastewater of a facility.
Uncontaminated fats, oils and grease from the food preparation
process that can be used as a source of material that is free of impurities
and can be recycled into products such as animal feed and cosmetics.
A closed, leakproof container for the collection and storage
of food grade fats, oil and grease.
Any physical modification of the facility's food preparation
area, food service area and/or dining area in excess of $20,000 in
any one calendar year, or a cumulative total in excess of $40,000
over any period of five years. The dollar value shall be the sum of
all renovations for all building permits issued to a facility in a
calendar year, for the food preparation, floor service and dining
areas, as determined by the Town of Stratford's Building Official.
The Stratford Water Pollution Control Authority, established
pursuant to Section 7-246 of the Connecticut General Statutes, who
shall be the authorized representative of the Town of Stratford.
[1]
Editor's Note: See now the Connecticut Department of Energy
and Environmental Protection's General Permit for the Discharge of
Wastewater Associated with Food Service Establishments.
A.Â
FOG pretreatment systems shall be provided for all new and existing
food preparation establishments, including restaurants, cafeterias,
diners, and similar nonindustrial facilities using food preparation
processes. FOG pretreatment systems shall not be required for private
living quarters or dwelling units.
B.Â
All new food preparation establishments or establishments that change
ownership as determined by the Water Pollution Control Authority shall
submit an application to install a FOG pretreatment system prior to
opening the facility. The FOG system must be installed and functioning
within 30 days of the application approval date.
C.Â
A renovation of the food preparation establishment shall require
compliance with all conditions of this article as part of the renovation.
D.Â
The Stratford WPCA may, as necessary, designate any area or areas
of its sewer system as a problem area related to fats, oils and grease.
Such designation shall be by a formal action of the WPCA and shall
be based upon evidence of excessive fats, oils and grease, including
sanitary sewer overflows, excessive maintenance or any means of inspection.
Upon notification by the WPCA, any food preparation establishment
within the problem area designation shall comply with all conditions
of this article within a reasonable time schedule established by the
WPCA.
E.Â
All existing food preparation establishments which require a new
FOG pretreatment system, as determined by the Water Pollution Control
Authority, shall submit an application for the installation of a new
FOG pretreatment system within 120 days of the enactment of this article.
The application shall be in accordance with Town of Stratford's Town
Code. The approved FOG pretreatment system shall be installed no later
than July 1, 2015.
F.Â
All existing food preparation establishments which have an existing FOG pretreatment system may, as determined by the Water Pollution Control Authority, keep the existing FOG pretreatment system in operation. Such facilities shall submit an application for an alternate FOG pretreatment system as described in § 172-106C. Such application shall be submitted within 120 days of the enactment of this article.
G.Â
All costs and related expenses associated with the installation and
connection of the FOG interceptor(s) or alternate FOG pretreatment
system(s) shall be borne by the food preparation establishment. The
food preparation establishment shall indemnify the Town of Stratford
and its agents for any loss or damage that may directly or indirectly
occur due to the installation of the FOG pretreatment system.
H.Â
Applications to install a FOG pretreatment or an alternate FOG pretreatment
system shall be submitted on standard forms provided by the WPCA and
shall be accompanied by a fee of $50. A letter of intent or contract
from the approved FOG cleaner/hauler shall be submitted as part of
the application.
A.Â
No facility shall discharge or cause to be discharged any wastewater
with a FOG concentration in excess of 100 milligrams per liter, as
determined by the currently approved test for total recoverable fats
and grease listed in 40 CFR 136.3, or in concentrations or in quantities
that will harm either the sewers or water pollution control facility,
as determined by the Water Pollution Control Authority.
B.Â
At no time shall the pH of the wastewater discharged from the FOG
interceptor, FOG recovery unit or other approved units, and prior
to mixing with any other wastewater from the food preparation establishment,
be less than five nor greater than 10 standard units at any time.
A.Â
An application for the design and installation of a FOG pretreatment
system shall be subject to review and approval by the Director of
Public Works per the Town of Stratford's Town Code and subject to
the requirements of all other applicable codes, ordinances and laws.
B.Â
Except as provided by § 172-106, the wastewater generated from food preparation establishments shall be treated to remove FOG using a FOG interceptor.
C.Â
Every structure at the subject facility shall be constructed, operated
and maintained in a manner to ensure that the discharge of food preparation
wastewater is directed solely to the FOG interceptor or alternate
FOG pretreatment system. No valve or piping bypass equipment that
could prevent the discharge of food preparation wastewater from entering
appropriate treatment equipment shall be present.
D.Â
The contact person at each food pretreatment establishment shall
notify the Water Pollution Control Authority when the FOG pretreatment
system is ready for inspection and connection to the public sewer.
The connection and testing shall be made under the supervision of
the plumbing inspector and/or the Water Pollution Control Authority.
E.Â
All applicable local plumbing/building codes shall be followed during
the installation of the FOG pretreatment system.
F.Â
FOG interceptor requirements.
(1)Â
The FOG interceptor shall be installed on a separate building
sewer line servicing kitchen flows and shall be connected only to
those fixtures or drains which would allow fats, oils, and grease
to be discharged. This shall include:
(a)Â
Pot sinks;
(b)Â
Pre-rinse sinks;
(c)Â
Any sink into which fats, oils, and grease are likely to be
introduced;
(d)Â
Soup kettles or similar devices;
(e)Â
Wok stations;
(f)Â
Floor drains or sinks into which kettles may be drained;
(g)Â
Automatic hood wash units;
(h)Â
Dishwashers without pre-rinse sinks; and
(i)Â
Any other fixtures or drains that are likely to allow fats,
oils or grease to be discharged.
(2)Â
No food grinder shall discharge to the FOG interceptor.
(3)Â
All wastewater flows connected to the FOG interceptor, FOG recovery
unit or other approved units shall be screened to prevent solids from
entering the treatment units. Screened solids shall be disposed of
in accordance with the applicable solid waste regulations.
(4)Â
No fixture or drain other than those listed in Subsection F(1) above shall be directly connected to the FOG interceptor unless approved by the Water Pollution Control Authority.
(5)Â
No valve or piping bypass equipment that could prevent the discharge
of wastewater associated with the food preparation establishment from
entering appropriate treatment equipment shall be present at such
food preparation establishment.
(6)Â
An outdoor FOG interceptor shall have a minimum depth of four
feet and a minimum detention time of:
(7)Â
FOG interceptors shall have a minimum of two compartments. The
two compartments shall be separated by a baffle that extends from
the bottom of the FOG interceptor to a minimum of five inches above
the static water level. An opening in the baffle shall be located
at mid-water level. The size of the opening shall be at least eight
inches in diameter but not have an area exceeding 180 square inches.
(8)Â
FOG interceptors shall be watertight and constructed of precast
concrete, or other durable material. FOG interceptors shall be located
so as to be accessible for convenient inspection and maintenance.
No permanent or temporary structures or containers shall be placed
directly over the FOG interceptor. FOG interceptors installed in areas
subject to traffic shall be designed to accommodate traffic loading.
(9)Â
FOG interceptors constructed of precast concrete shall meet
the following requirements:
(a)Â
All concrete FOG interceptors shall be fabricated using minimum
4,000 psi concrete, per ASTM standards, with four- to seven-percent
air entrainment.
(b)Â
The FOG interceptor shall have a minimum liquid depth of 36
inches, measured from the bottom of the tank to the outlet invert.
(c)Â
The air space provided between the liquid height and the underside
of the tank top shall be a minimum of eight inches.
(d)Â
All structural seams and/or lifting holes shall be grouted with
nonshrinking cement or similar material and coated with a waterproof
sealant. In areas where seasonal high groundwater is at an elevation
greater than the bottom of the FOG interceptor, but below the top
of the FOG interceptor, the exterior top, sides and bottom shall be
coated with a waterproof sealant creating a watertight condition for
the tank. In areas where seasonal high groundwater is at an elevation
greater than the top of the FOG interceptor, the exterior of the manhole
extensions to grade shall be coated with a waterproof sealant creating
a watertight condition for the extension.
(e)Â
The manhole cover shall be placarded with the warning "Entrance
into the tank could be fatal."
(f)Â
Voids between the FOG interceptor's walls and inlet and outlet
piping shall be grouted with nonshrinking cement and coated with a
waterproof sealant.
(g)Â
The liquid capacity of the tank shall be marked on top of the
tank between the outlet access hole and the outlet wall or on the
vertical wall between the top of the tank and the top of the outlet
opening.
(h)Â
The invert elevation of the inlet shall be between three inches
and six inches above the invert elevation of the outlet.
(10)Â
All nonconcrete septic tanks must be approved for use by the
Water Pollution Control Authority.
(11)Â
Separate cleanout covers shall be provided over the inlet and
outlet of the FOG interceptor so as to provide easy access for inspection
and cleaning. Cleanout ports shall be fitted with manhole extensions
to grade. In areas subject to traffic, the extensions shall be ductile
or cast iron frames and round manhole covers. Where concrete covers
are used, the lid must either have a minimum weight of 59 pounds or
contain a locking mechanism to prevent unauthorized entrance. The
manholes, extensions and outlet access holes to the FOG interceptor
shall have a minimum inside diameter of 17 inches.
(12)Â
The inlet and outlet piping shall be PVC meeting ASTM D1785
Schedule 40 with rubber compression gaskets or solvent weld couplings.
The joints must meet ASTM D3212 specifications. The Water Pollution
Control Authority may approve other piping materials for use. The
minimum diameter of the inlet and outlet piping shall be four inches.
The inlet and outlet shall utilize a tee-pipe fitting on the interior
of the FOG interceptor. No caps or plugs shall be installed on the
tee-pipes. The tee-pipe on the inlet and outlet shall extend to within
12 inches of the bottom of the tank and at least five inches above
the static liquid level of the tank.
(13)Â
The FOG interceptor shall be set level on a consolidated, stable
base that has been mechanically compacted, with a minimum of six inches
of crushed stone so that no settling or tipping of the FOG interceptor
can occur. Select backfill shall be placed and compacted around the
FOG interceptor in a manner to prevent damage to the tank and to prevent
movement caused by frost action.
(14)Â
The outlet discharge line from the FOG interceptor shall be
directly connected to the municipal sanitary sewer.
(15)Â
The FOG interceptor shall be located so as to maintain the separating
distances from well water supplies set forth in Section 19-13-B51d
of the Public Health Code.
(16)Â
The following minimum separating distances shall be maintained
between the FOG interceptor and the items listed below:
(17)Â
When necessary due to installation concerns, testing for leakage
will be performed using either a vacuum test or water-pressure test.
(a)Â
Vacuum test. Seal the empty tank and apply a vacuum to two inches
of mercury. The tank is approved if 90% of the vacuum is held for
two minutes.
(b)Â
Water-pressure test. Seal the tank, fill with water, and let
stand for 24 hours. Refill the tank. The tank is approved if the water
level is held for one hour.
A.Â
When it is not practical for the food preparation establishment to install an outdoor, in-ground FOG interceptor per § 172-105, an alternate FOG pretreatment system may be utilized upon approval by the Water Pollution Control Authority and upon receiving a notification of approved alternative FOG pretreatment system. Approval of the system shall be based on demonstrated (proven) removal efficiencies and reliability of operation. The Water Pollution Control Authority will approve these systems on a case-by-case basis. The contact person may be required to furnish analytical data demonstrating that FOG discharge concentrations do not exceed the limits established in this article.
C.Â
Alternate FOG pretreatment systems shall meet the requirements of § 172-105A through E, shall be installed immediately downstream of each of the fixtures and drains listed in § 172-105F(1), and shall meet the requirements of § 172-105F(2), (3) and (5).
D.Â
Alternate FOG pretreatment system requirements.
(1)Â
FOG recovery units shall be sized to properly pretreat the measured
or calculated flows using methods approved by the Water Pollution
Control Authority.
(2)Â
FOG recovery units shall be constructed of corrosion-resistant
material, such as stainless steel or plastic.
(3)Â
Solids shall be intercepted and separated from the effluent
flow using a strainer mechanism that is integral to the unit.
(4)Â
The FOG recovery units shall operate using a skimming device,
automatic draw-off, or other mechanical/hard-wired electrical means
to automatically remove separated FOG. This automatic skimming device
shall be controlled using a timer or level control. The operation
of the automatic skimming device shall be field-adjustable. The FOG
recovery unit's timer shall be set to operate the unit no less than
once per day.
(5)Â
FOG recovery units shall be fitted with an internal or external
flow-control device to prevent the exceedence of the manufacturer's
recommended design flow.
(6)Â
FOG recovery units shall be located to permit frequent access
for maintenance and inspection.
E.Â
Other alternate FOG pretreatment systems.
(1)Â
Other alternate FOG pretreatment systems that do not meet the requirements of § 172-105F or § 172-106D may be considered for approval by the Water Pollution Control Authority on a case-by-case basis. The application shall include:
(a)Â
Documented evidence that the proposed alternate FOG pretreatment system will not discharge FOG concentrations that exceed the discharge limits per § 172-104.
(b)Â
Plans and specifications for the proposed system, including
plans and profile of system installation, manufacturer's literature,
documentation of performance and any other information detailing the
proposed alternate system.
(c)Â
A written operation and maintenance plan, which shall include
the schedule for cleaning and maintenance, copies of maintenance log
forms, a list of spare parts to be maintained at the subject facility,
and a list of contacts for the manufacturer and supplier. Following
receipt of written notification of approved alternate FOG pretreatment
system from the Water Pollution Control Authority, the operation and
maintenance plan shall be maintained on the premises. The plan shall
be made available for inspection on demand by the Water Pollution
Control Authority.
(d)Â
A written FOG minimization plan, which shall include procedures
for all food preparation establishment employees to minimize FOG entering
the wastewater collection system.
(e)Â
A description of a FOG pretreatment training program for food
preparation establishment employees in FOG minimization procedures.
(2)Â
A notification of approved alternate FOG pretreatment system may be granted for a duration not to exceed three years, with extensions, when demonstrated to the satisfaction of the Water Pollution Control Authority that the proposed alternate FOG pretreatment system, operation and maintenance plan, FOG minimization plan and FOG pretreatment training program are adequate to maintain FOG concentration in the wastewater discharge below the limits set in § 172-104.
A.Â
The FOG pretreatment system shall be maintained continuously in satisfactory
and effective operation, at the food preparation establishment's expense.
B.Â
The contact person shall be responsible for the proper removal and
disposal, by appropriate means, of the collected material removed
from the FOG pretreatment system.
C.Â
The contact person may use hot water, steam, chemicals, or biological
additives in the normal course of facility maintenance, but may not
intentionally use hot water, steam, physical means, chemicals, or
biological additives that will cause the release of fats, oils, and
grease from the FOG interceptor, FOG recovery unit or other approved
unit.
D.Â
The contact person shall ensure that the FOG interceptor is inspected
when pumped to ensure that all fittings and fixtures inside the interceptor
are in good condition and functioning properly. The depth of grease
inside the tank shall be measured and recorded in the maintenance
log during every inspection, along with any deficiencies and the identity
of the inspector.
E.Â
The contact person shall determine the frequency at which its FOG
interceptor(s) shall be pumped, according to the following criteria:
(1)Â
The FOG interceptor shall be cleaned by a subsurface sewage
disposal cleaner whenever 25% of the operating depth of the FOG interceptor
is occupied by fats, oils, grease, and settled solids, or a minimum
of once every three months, whichever is more frequent. Cleaning of
FOG interceptors shall include the complete removal of all contents,
including floating materials, wastewater and settled sludge. Decanting
back into the FOG interceptor shall not be permitted, FOG interceptor
cleaning shall include scraping excessive solids from the walls, floors,
baffles and all piping.
(2)Â
If the contact person can provide data demonstrating that less
frequent cleaning of the FOG interceptor will not result in a grease
level in excess of 25% of the operating depth of the FOG interceptor,
the Water Pollution Control Authority may allow less frequent cleaning.
The contact person shall provide data, including plumbing receipts,
for four consecutive cleanings of the FOG interceptor, complete with
a report from the grease trap/interceptor cleaner indicating the grease
level at each cleaning, and the FOG interceptor maintenance log.
(3)Â
A maintenance log shall be maintained in the premises and shall
include the following information: dates of all activities; volume
pumped; grease depth measured at the time of inspection; and any maintenance
work or changes in equipment associated with such discharge that has
taken place since the last inspection; grease trap/interceptor cleaner's
name, title and signature; location of the waste disposal; means of
disposal for all material removed from the FOG interceptor; and the
name of the individual recording the information. The maintenance
log and grease trap/interceptor cleaner's receipts shall be made available
to the Water Pollution Control Authority for inspection on demand.
Interceptor cleaning, inspection records and all cleaning and maintenance
logs and analytical results from any monitoring elected to be done
by the owner of the food preparation establishment shall be maintained
on file a minimum of five years.
F.Â
All material removed and hauled from FOG pretreatment systems must
be performed by a subsurface sewage disposal cleaner or entity approved
by the Water Pollution Control Authority. Pumped material shall be
disposed of at a regional FOG disposal facility.
G.Â
The contact person shall be responsible to submit maintenance reports
to the Water Pollution Control Board every two years. Reports shall
be submitted before July 1 in each odd year (2013, 2015, 2017, etc.).
The contact person shall notify the WPCA within 30 days of changing
approved FOG cleaners/haulers.
H.Â
The contact person shall be responsible for the cost and scheduling
of all actions needed to comply with this article. The contact person
shall be notified, in writing, of violations of this article by the
Water Pollution Control Authority. Actions to comply with this article
shall be completed within the time limits as given below:
Violation
|
Days from Inspection to Correct Violation
| |
---|---|---|
Equipment not registered
|
30
| |
Equipment not properly installed
|
90
| |
Major violations (outdoor and indoor)
|
30
| |
Major violations
|
90
|
A.Â
The contact person shall make every practical effort to reduce the
amount of FOG contributed to the sewer system.
B.Â
Renderable fats, oils and grease shall be stored in a separate, covered,
leakproof, renderable FOG container, stored out of reach of vermin,
and collected by a renderer.
C.Â
Small quantities of FOG scraped or removed from pots, pans, dishes
and utensils shall be directed to the municipal solid waste stream
for disposal.
A.Â
If any analytical results from monitoring data elected to be done
by the contact person or owner of the food preparation establishment,
or other information, indicates that a violation of an effluent limitation
or another condition of this article has occurred, the contact person
shall immediately take steps to identify, correct and mitigate the
results of any and all conditions causing or contributing to such
violation and shall take reasonable steps to prevent further such
violation. A log of such violations shall be maintained on site and
contain, at a minimum, the following information:
(1)Â
The condition(s) or effluent limitation(s) violated;
(2)Â
The analytical results or other information demonstrating such
violation;
(3)Â
The cause of the violation, if known;
(4)Â
Dates and times during which the violation continued;
(5)Â
If the violation was not corrected immediately upon being discovered,
the anticipated time it is expected to continue and, upon correction,
the date and time of correction;
(6)Â
Steps taken and planned to reduce, eliminate and prevent a reoccurrence
of the violation, and the dates such steps have been or will be executed;
(7)Â
The name, title and signature of the individual recording the
information and the date and time of such recording.
B.Â
The contact person shall be required to report, in writing, such
violation and such corrective action to the Commissioner of the Department
of Energy and Environmental Protection and the Water Pollution Control
Authority within five days of the contact person's learning of such
violation.
C.Â
All reports made by the contact person shall be certified in the
following manner: "I have personally examined and am familiar with
the information submitted in this document and all attachments thereto,
and I certify that, based on reasonable investigation, including my
inquiry of those individuals responsible for obtaining the information,
the submitted information is true, accurate and complete to the best
of my knowledge and belief. I understand that a false statement made
in the submitted information may be punishable as a criminal offense,
in accordance with Section 221-6 of the Connecticut General Statues
pursuant to Section 53a-157b of the Connecticut General Statutes and
in accordance with any other applicable statute."
E.Â
Immediately upon learning or having reason to believe that an authorized
discharge may cause or has caused a sewer blockage, or may adversely
affect the operations of the Stratford sewer system, the contact person
shall immediately notify the Water Pollution Control Authority and
the Commissioner of the Department of Energy and Environmental Protection.