A. 
Ductile iron pipe and fittings.
(1) 
Ductile iron pipe shall be centrifugally cast and shall conform to the requirements of the American Water Works Association Specifications C-151, as amended and revised to date.
(2) 
Ductile iron pipe shall be thickness Class 52. All ductile iron pipe and fittings shall be cement-lined in accordance with American Water Works Association Specifications C-104, as amended.
(3) 
Ductile iron pipe shall be provided with mechanical joints, or shall be push-on Tyton® joint pipe as manufactured by the United States Pipe and Foundry Company, or approved equal, conforming to the American Water Works Association Specifications C-110 and C-111. All iron fittings, including Y-branches, shall conform to American Water Works Association Specifications C-110, latest revision, except that fittings shall be provided with joints suitable for use with the adjoining pipe. Ductile iron saddles shall be subject to the approval of the engineer.
B. 
Asbestos-cement pipe and fittings.
(1) 
Asbestos-cement pipe and fittings shall conform to the requirements of the American Society for Testing Materials Specifications C-428 for nonpressure sewer pipes, and C-296 for pressure pipes, as amended and revised to date. Asbestos-cement pipe and fittings shall be a minimum of Class 2400 for depths of cover under 10 feet, and a minimum of Class 3300 for depths of cover 10 feet or more.
(2) 
All asbestos-cement pipe and fittings shall be furnished complete with sleeve and gasket-type couplings designed for use with the size and class of pipe specified.
(3) 
Ductile iron fittings for use with asbestos-cement pipe shall conform to the requirements for ductile iron fittings hereinbefore specified.
C. 
Vitrified clay pipe and fittings.
(1) 
Vitrified clay pipe and fittings shall conform to the requirements of the American Society for Testing Materials Specifications C-700, as amended and revised to date. Vitrified clay pipe and fittings shall be extra strength.
(2) 
All vitrified clay pipe and fittings shall have factory-fabricated, gasket-type couplings with "O" ring joints which conform to the American Society for Testing Materials Specification C-425, as amended and revised to date.
D. 
Concrete. Any concrete required for cradles, pads, drop connections at manholes, and any other miscellaneous items shall be 4,000 psi conforming to the requirements set forth elsewhere herein.
Excavation and backfill shall conform to the requirements for subsurface structure excavation. The contractor shall provide adequate equipment and so operate it as to maintain an essentially dry excavation, stable trench bottoms, suitable working conditions, and protection from water damage throughout and until the completion of the work.
A. 
Pipe shall be laid in straight lines between manholes except when otherwise specifically provided or directed by the engineer. When deviation from straight line is permitted, the deflection of each joint shall not exceed the manufacturer's recommended maximum for the type of joint and size of pipe being installed. All pipe shall be laid to uniform grades between manholes.
B. 
Before making each joint, the ends of the pipes and all joint members shall be thoroughly cleaned. All jointing shall be done in strict accordance with the manufacturer's recommendation and the direction of the engineer.
C. 
No defective or leaking pipe, fittings, joints, connection, manholes or other parts of the work will be acceptable. All visible leakage of any description, and no matter where located shall be corrected by the contractor in a manner satisfactory to the engineer, whether or not the total leakage into the sewer is within the allowable maximum as determined by exfiltration tests.
A. 
Exfiltration tests shall be made under the supervision of the engineer, and no connections to flowing lines permitted until the testing is complete and satisfactory results have been obtained. The contractor shall furnish all labor, material and equipment necessary for the exfiltration tests.
B. 
Prior to the start of the exfiltration test, all construction work for the system under test shall be completed. This includes backfilling and completion of all manholes.
A. 
The test is conducted between two consecutive manholes, as directed by the engineer.
B. 
The test section of the sewer lines is plugged at each end. One of the plugs used at the manhole must be tapped and equipped for the air inlet connection for filling the line from the air compressor.
C. 
All service laterals, stubs and fittings into the sewer test section should be properly capped or plugged, and carefully braced against the internal pressure to prevent air leakage by slippage and blowouts.
D. 
Connect air hose to tapped plug selected for the air inlet.
(1) 
Then connect the other end of the air hose to the portable air control equipment which consists of valves and pressure gauges used to control:
(a) 
The air entry rate to the sewer test section; and
(b) 
To monitor the air pressure in the pipeline.
(2) 
More specifically, the air control equipment includes a shutoff valve, pressure-regulation valve, pressure-reduction valve and a monitoring pressure gauge having a pressure range from zero to five psi. The gauge should have a minimum division of 0.10 psi and an accuracy of ±0.04 psi.
E. 
Connect another air hose between the air compressor (or other source of compressed air) and the air control equipment. This completes the test equipment set up. Test operations may commence.
F. 
Supply air to the test section slowly, filling the pipeline until a constant pressure of 3.5 psig is maintained. The air pressure must be regulated to prevent the pressure inside the pipe from exceeding 5.0 psig.
G. 
When constant pressure of 3.5 psig is reached, throttle the air supply to maintain the internal pressure above 3.0 psig for at least five minutes. This time permits the temperature of the entering air to equalize with the temperature of the pipe wall. During this stabilization period, it is advisable to check all capped and plugged fittings with a soap solution to detect any leakage at these connections. If leakage is detected at any cap or plug, release the pressure in the line and tighten all leaky caps and plugs. Then start the test operation again by supplying air. When it is necessary to bleed off the air to tighten or repair a faulty plug, a new five-minute interval must be allowed after the pipeline has been refilled.
H. 
After the stabilization period, adjust the air pressure to 3.5 psig and shut off or disconnect the air supply. Observe the gauge until the air pressure reaches 3.0 psig. At 3.0 psig, commence timing with a stop watch which is allowed to run until the line pressure drops to 2.5 psig, at which time the stop watch is stopped. The time required, as shown on the stop watch, for a pressure loss of 0.5 psig is used to compute the air loss. Most authorities consider it unnecessary to determine the air temperature inside the pipe line and the barometric pressure at the time of the test.
I. 
If the time, in minutes and seconds, for the air pressure to drop from 3.0 to 2.5 psig is greater than that shown in Table 16.112.020 for the designated pipe size, the section undergoing test shall have passed and shall be presumed to be free of defects. The test may be discontinued at that time.
J. 
If the time, in minutes and seconds, for the 0.5 psig drop is less than shown in Table 16.112.020 for the designated pipe size, the section of pipe shall not have passed the test; therefore, adequate repairs must be made and the line retested.
Table 16.112.020
Time Requirement for Air Testing
Pipe Size
(inches)
Time
Minutes
Second
4
2
32
6
3
50
8
5
6
10
6
22
12
7
39
14
8
56
15
9
35
16
10
12
18
11
34
20
12
45
21
13
30
(For larger-diameter pipe, use the following: minimum time in seconds = 462 x pipe diameter in feet)
Notes for Table 16.112.020
a.
Pipe sizes with their respective recommended minimum times, in minutes and seconds, for acceptance by the air test method are shown.
b.
For eight-inch and smaller pipe only: if, during the five-minute saturation period, pressure drops less than 0.5 psig after the initial pressurization and air is not added, the pipe section undergoing test shall have passed.
c.
Multi-pipe sizes: When the sewer line undergoing test is eight-inch-or-larger-diameter pipe and includes four-inch or six-inch laterals, the figures in Table 16.112.020 for uniform sewer main sizes will not give reliable or accurate criteria for the test. Where multi-pipe sizes are to undergo the air test, the engineer can compute the average size in inches, which is then multiplied by 38.2 seconds. The results will give the minimum time in seconds acceptable for a pressure drop of 0.5 psig for the averaged diameter pipe.
K. 
Adjustment required for groundwater. An air pressure correction is required when the prevailing groundwater is above the sewer line being tested. Under this condition, the air test pressure must be increased 0.433 psi for each foot the groundwater level is above the invert of the pipe.
Where groundwater is known to exist or is anticipated in the area before the air testing would be conducted, the following procedure shall be used at the time the sewer main and manholes are constructed:
A. 
Install one-half-inch-diameter pipe nipple (threaded one or both ends, approximately 10 inches long) through the manhole wall directly on top of one of the sewer pipes entering the manhole with threaded end of nipple extending inside the manhole;
B. 
Seal pipe nipple with a threaded one-half-inch cap;
C. 
Immediately before testing, determine the groundwater level by removing the threaded cap from the nipple, blowing air through the pipe nipple to remove any obstructions, and then connect a clear plastic tube to the pipe nipple;
D. 
Hold plastic tube vertically, permitting water to rise in it to the groundwater level;
E. 
After water level has stabilized in plastic tube, measure vertical height of water, in feet, above invert of sewer pipe;
F. 
Determine air-pressure correction, which must be added to the 3.0 psig normal starting pressure of test, by dividing the vertical height in feet by 2.31. The result gives the air-pressure correction in pounds per square inch to be added;
G. 
Example:
(1) 
If the vertical height of water from the sewer invert to the top of the water column measures 11.55 feet, the additional air pressure required would be:
(11.55)
2.31
= 5 psig
(2) 
Therefore, the starting pressure of the test would be 3.0 plus 5 or 8.0 psig, and the one-half-pound drop becomes 7.5 psig. There is no change in the allowable drop (0.5 psig) or in the time requirements established for the basic air test.
Lamping of all gravity sanitary sewer lines shall be performed by the engineer in accordance with the following requirements:
A. 
Lamping consists of visually examining inside of pipe between two consecutive manholes with the aid of a light and mirror;
B. 
A light is shown from one manhole towards the other manhole;
C. 
A mirror is held at the invert of pipe and adjusted so the light and barrel of pipe can be seen;
D. 
The barrel of the pipe shall have no vertical deflection and at least 75% of the barrel shall be visible in the horizontal direction;
E. 
In the event that lamping shows the pipe not laid true and to grade, it shall be repaired and be lamped as necessary until the lamping complies with these requirements.
In addition to the visual and lamping inspections, the Township may employ the use of television cameras to inspect sewers after or during construction. If defective workmanship or materials are found, these shall be corrected and the cost of TV inspection paid for by the applicant. No TV inspection costs shall be assessed against the applicant if the workmanship and materials are found to be satisfactory.
A. 
Y-branches and service laterals which are not to be immediately connected to flowing lines shall be securely plugged with an approved type of plug which will provide a permanent watertight seal. Plugs shall be braced as shown on the standard detail. The contractor shall accurately record the station of each Y-branch placed and direction of the Y. He shall also show the location of each Y-branch on his copy of the plans and permanently mark each location with a crosscut on the curb or a two-inch-by-four-inch stake driven at the plugged end of the lateral.
B. 
All lateral connections to existing sanitary sewer lines shall be installed with bolt-on type saddles unless otherwise specified by the engineer.
Drop connections at manholes are shown on the standard details. Concrete cradles over existing pipe shall be constructed where and as directed by the engineer. All concrete work shall conform to the requirements as set forth elsewhere herein.
When so required by the engineer, the contractor shall flush such newly completed sewers as may be designated by the engineer, in order to remove any foreign matter which may have accumulated therein during construction. The contractor shall furnish all labor, material, equipment and water necessary for flushing and shall provide for the disposal of water used for flushing.