The purpose of this article is to safeguard potable water supplies of the Village of Pelham from potential contamination by preventing back flow from a water user's system into the public water system. It is the intent of this article to recognize that there are varying degrees of hazard and to apply the principle that that the degrees of protection should be commensurate with the degrees of hazard. It is the intent of the Village of Pelham to comply with the requirements of New York State Sanitary Code, Part 5, Section 5-1.31, which requires that the supplier of water protect its water system in accordance with procedures acceptable to the Commissioner of Health. These mandates are set forth in the Cross Connection Control Manual published by the New York State Department of Health and to that extent, the terms, conditions and provisions of the New York State Sanitary Code, Part 5, Section 5-1.31, and the Cross Control Manual are incorporated in this Part 1 by reference as if more fully stated.
As used in this article, the following terms shall have the meanings indicated:
AIR GAP SEPARATION
A physical break between a supply pipe and a receiving vessel. The air gap shall be at least double the diameter of the supply pipe, measured vertically above the top rim of the vessel and in no case shall be less than one inch.
APPROVED CHECK VALVE
A check valve that seats readily and completely. It must be carefully machined to have free-moving parts and assured watertightness. The face of the closure element and valve seat must be bronze, composition, or other noncorrodible material which will seat tightly under all prevailing conditions of field use. Pins and bushings shall be of bronze and other noncorrodible, nonsticking material and shall be machined for easy dependable operation. The closure element shall be internally weighted or otherwise internally equipped to promote rapid and positive closure in all sizes where this feature is obtainable.
APPROVED DOUBLE CHECK VALVE ASSEMBLY
Two single independently acting check valves, including tightly closing shutoff valves located at each end of the assembly and suitable test connections. This device must be approved as a complete assembly.
APPROVED REDUCED-PRESSURE ZONE DEVICE
A minimum of two independently acting check valves together with an automatically operated pressure differential relief valve located between the two check valves. In case of leakage of either check valve, the differential relief valve, by discharging to the atmosphere, shall operate to maintain the pressure between the checks at less than the supply pressure. The unit must include tightly closing shutoff valves located at each end of the device, and each device shall be fitted with properly located test cocks. This device must also be approved as a complete assembly.
APPROVED WATER SUPPLY
Any water supply approved by the New York State Department of Health.
AUXILIARY SUPPLY
Any water supply on or available to the premises other than the approved public water supply.
CERTIFIED BACKFLOW PREVENTION DEVICE TESTER
An individual who has successfully completed a New York State Department of Health approved course in the testing of backflow prevention devices and has been issued a certificate by the New York State Department of Health.
CROSS-CONNECTION
Any unprotected connection between any part of a water system used or intended to be used as a supply of water for drinking purposes in a source or systems containing water or a substance that is not or cannot be approved as equally safe, wholesome and potable for human consumption.
WATER SUPERVISOR
The consumer or person on the premises charged with the responsibility of complete knowledge and understanding of the water supply piping within the premises and for maintaining the consumer's water system free from cross-connections and other sanitary defects, as required by this article and all other applicable laws and regulations.
WATER USER
Each individual commercial or residential property owner and its occupants or visitors served by the water system.
VACUUM BREAKER (PRESSURE-TYPE AND NONPRESSURE-TYPE)
A device that can only be used for internal plumbing control and is not acceptable as a containment device.
The water system shall be required to maintain a degree of protection commensurate with the degree of hazard regardless of whether the hazard is immediate or potential. To that extent, the Cross Connection Control Manual published by New York State Department of Health shall be used as a guide to determine where protection is required. It shall be the responsibility of the water user to provide and maintain such required protection devices and such devices shall be of a type acceptable to the New York State Department of Health.
A. 
At the service connection to any premises where there is an auxiliary water supply handled in a separate piping system with no known cross-connection, the public water supply shall be protected by an approved reduced-pressure zone device.
B. 
At the service connection to any premises on which a substance that would be objectionable, but not necessarily hazardous to health if introduced into the public water supply, is handled so as to constitute a cross-connection, the public supply shall be protected by an approved double check valve assembly.
C. 
At the service connection to any premises on which a substance of unusual toxic concentration or danger to health is or may be handled, but not under pressure, the public water supply shall be protected by an air gap separation or an approved reduced pressure zone backflow prevention device. If an air gap is installed, it shall be located as close as practical to the water meter, and all piping between the water meter and receiving tanks shall be entirely visible. If a reduced-pressure zone device is installed, it shall be located as close as possible to the property line.
D. 
At the service connection to any premises on which any material dangerous to health, or toxic substance and toxic concentration, is or may be handled under pressure, the public water supply shall be protected by an air gap separation. The air gap shall be located as close as practical to the water meter, and any piping between the water meter and receiving tanks shall be entirely visible. If these conditions cannot reasonably be met, the public water supply shall be protected with an approved reduced-pressure zone back flow prevention device, and it shall be located as close as possible to the property line.
It shall be the duty of the water user on any premises on account of which backflow protective devices are installed, to have competent inspections made at least once a year, or more often in instances where successive inspections indicate repeated failure. Devices shall be repaired, overhauled or replaced at the expense of the water user whenever they are found to be defective. These tests shall be performed by a qualified back flow prevention device tester, and all test results will be provided to the water user within 72 hours after the test is made. Records of such tests, repairs and overhaul shall also be kept and made available to the water user and the local health department upon request.