THROWING LIGHTED MATCHES, CIGARS OR CIGARETTES,
CARPET SWEEPINGS, NAPHTHALENE, CAMPHOR BALLS OR FLAKES, FLOOR SCRAPINGS,
OIL SOAKED RAGS, PAINT CANS, AEROSOL CONTAINERS OR ANY OTHER FLAMMABLE
OR HIGHLY COMBUSTIBLE OR EXPLOSIVE SUBSTANCE INTO INCINERATOR CHUTES
IS UNLAWFUL AND SUBJECTS THE OFFENDER TO A PENALTY.
|
Location
|
Clearance
(feet)
| |
---|---|---|
Above streets, driveways, parking spaces and
other use areas where motor vehicles are permitted
|
18
| |
Above areas accessible to pedestrians only
|
10
| |
Above buildings and structures
|
8
| |
Horizontal clearance from any window, door,
porch, balcony or other similar point of access
|
6
| |
Horizontal clearance from the periphery of any
swimming pool
|
15
|
Table I - Communal Kitchen Equipment Requirements
| |||
---|---|---|---|
Number of Occupants Served
| |||
Equipment
|
12 and Less
|
13 or More
| |
Sink
|
24-inch front
|
Additional 24-inch unit for each multiple of
6 occupants, or fraction thereof
| |
Range
|
4-burners
|
Additional 4-burner unit for each multiple of
6 occupants, or fraction thereof
| |
Oven*
|
6 cubic feet
|
Additional 6-cubic-foot unit for each multiple
of 6 occupants, or fraction thereof
| |
Refrigerator
|
12 cubic feet
|
additional 1 cubic foot per occupant
| |
Storage cabinets
|
42 cubic feet
|
additional 1 1/2 cubic feet per occupant
| |
*May be separate unit or part of range unit.
|
TABLE II - Mechanical Ventilation Requirements
| ||
---|---|---|
Space
|
Minimum Ventilation
| |
Shower rooms, locker rooms, dressing rooms
|
6 air changes per hour
| |
Recreation rooms
|
2 air changes per hour
| |
Lounges, reception rooms, dining rooms, meeting
rooms
|
4 air changes per hour
| |
Workshops, service rooms, paint storage rooms,
utility service rooms
|
1 air change per hour
| |
Laundry rooms
|
2 air changes per hour
| |
Central kitchens
|
4 air changes per hour
| |
Hoods for cooking equipment in central kitchens
|
100 cfm per square foot of hood
| |
Central dining rooms
|
4 air changes per hour
| |
Garage areas:
| ||
Above grade exceeding 1,000 square
feet
|
4 air changes per hour
| |
Below grade
|
6 air changes per hour
| |
Passageways, hallways, corridors and stairways:
| ||
Above grade
|
1/2 air change per hour
| |
Below grade
|
1 air change per hour
|