[Added by Ord. No. 999, 9/16/2019]
1. 
Fences and Walls.
[Figure 8-801]
Flood Control: Standards for Fencing/Walls
Fence/Wall Type
Uses of Fencing/Walls Permitted
AE Zones
Floodway
A
Yes
Yes
B
Yes
Yes, with limited cross fencing
C
Design specifications required
Design specifications required
D
Yes, if elevated
Review of design required
E
Yes, if elevated
No
F
Review of design required
No
Fence/Wall Types:
A.
"Open" barbed, or barbless, wire. For floodplain management purposes, barbed and/or barbless wire will be considered "open" if there is no more than one horizontal strand per foot of height and no more than one vertical wire, or post, every six feet.
B.
"Open" pipe, or rail, fencing (e.g., corrals). For floodplain management purposes, pipe/rail fencing will be considered "open" if the horizontal pipes/rails occupy less than 10% of the area fenced and vertical posts are spaced not less than eight feet from each other.
C.
Breakaway/collapsible fencing.
D.
Other wire, pipe, or rail type fencing (e.g., field, chicken wire, etc.) which does not meet the "open" requirements described above.
E.
Chain-link fencing.
F.
Continuous Fencing or Masonry Walls. For floodplain management purposes, "continuous fencing" shall be solid panels, and/or components which create a solid panel, which do not meet the criteria of "open" (above).
* Individual horizontal wire strands can be placed below the flood height, provided they are spaced no closer than six inches apart. Individual vertical wire strands can be placed below the flood height, provided that they are spaced not closer than six feet apart. For wire, pipe, or rail fencing that does not meet the "open" requirements, and for wood or masonry walls/fences, the bottom of the wall/fence must be elevated to or above the elevation of the water during the one-percent flood event. Wood and masonry fencing/walls do not need to be elevated if they provide enough openings at their bases to allow the free flow of floodwaters without increasing the depth of water at all. Said openings' dimensions shall be equivalent to one square inch per one square foot of area enclosed. In the case that an area is not "enclosed" by said fencing/wall, openings shall be required to be one square inch for each square foot of lot area, exclusive of structures.
[Added by Ord. No. 999, 9/16/2019]
Refer to the following regarding floor levels:
8-802.tif
8-802a.tif
[Added by Ord. No. 999, 9/16/2019]
Refer to the following regarding minor rehabilitation:
8-803.tif
Figure 8-2. Minor rehabilitations use flood-resistant methods and materials
Neither structure would benefit from post-FIRM flood insurance rates because they are not elevated.
[Added by Ord. No. 999, 9/16/2019]
Refer to the following regarding reconstruction:
8-804.tif
Figure 8-10, A reconstructed house is new construction.
This example is for A Zones only. A new building in the V Zone must be elevated on piles or columns.
[Added by Ord. No. 999, 9/16/2019]
Example 8. Post-FIRM building — substantial improvement.
Substantial improvements made to a post-FIRM structure must meet the requirements of the current ordinances. Figure 8-9 shows a lateral addition made after a map revision took place and the BFE was increased.
8-805.tif
Figure 8-9. Substantial Improvements to post-FIRM buildings must be elevated above the new BFE. Nonresidential buildings may be floodproofed.
[Added by Ord. No. 999, 9/16/2019]
Example 5. Vertical addition — residential.
When the proposed substantial improvement is a full or partial second floor, the entire structure must be elevated (Figure 8-6). In this instance, the existing building provides the foundation for the addition. Failure of the existing building would result in failure of the addition, too.
8-806.tif
Figure 8-6, Vertical addition to a residential building in a V Zone.
The new structure would benefit from post-FIRM flood insurance rates.