Type
|
Pipe Diameter
(inches)
|
Hazen-Williams "C"
| ||
---|---|---|---|---|
Service Connections
| ||||
Copper
|
3/4 – 3
|
130
| ||
PVC
|
3/4 – 4
|
130
| ||
DIP
|
3
|
100
| ||
Distribution Mains
| ||||
PVC
|
4 – 8
|
120
| ||
PVC
|
8 – 12
|
130
| ||
DIP
|
4 – 8
|
100
| ||
DIP
|
10 – 12
|
110
| ||
DIP
|
16 – 24
|
120
| ||
Transmission Mains
| ||||
All material
|
16 – 20
|
120
| ||
All material
|
24 and larger
|
130
|
Fire Flow
(gpm)
|
Color
|
Reflective tape on
| |
---|---|---|---|
1,500 or greater
|
Blue
|
Around bonnet flange
| |
1,000 to 1,499
|
Green
|
Around bonnet flange
| |
500 to 999
|
Orange
|
Around bonnet flange
| |
All hydrant barrels shall be painted yellow
|
Q
|
=
|
Quantity of sewage in cubic feet per second (design flow). All
flow calculations shall be expressed in GPM, GPD, MGD and CFS.
| |
V
|
=
|
Velocity in feet per second
| |
A
|
=
|
Required cross section area of conduit in square feet
|
V
|
=
|
1.486 R2/3S1/2
| |
n
| |||
n
|
=
|
Coefficient of roughness as indicated in Appendix W[6]
| |
S
|
=
|
Slope in feet per foot
| |
R
|
=
|
Hydraulic radius-area divided by wetted perimeter
|
Material
|
"C" factor
| |
---|---|---|
DIP (new)
|
140
| |
DIP (design)
|
120
| |
DIP (old)
|
100
|
T = 4V/Q
| ||||
Where:
| ||||
T
|
=
|
pump cycle time (time between pump starts) in minutes
| ||
V
|
=
|
volume of wet well between the lead pump start and pump stop
elevations, in gallons
| ||
Q
|
=
|
pump rate of the lead pump, in gallons per minute
|