Standard
| ||
---|---|---|
Minimum on pavement2
|
0.2 footcandle
| |
Maximum on pavement
|
4.0 footcandle
| |
Maximum at property line
|
0 footcandle
| |
Uniformity ratio
Maximum: minimum3
|
20:1
| |
Minimum at 5 feet above pavement4
|
0.1 footcandle
|
NOTES:
| ||
---|---|---|
1
|
For typical conditions. During periods of non-use, the illuminance
of certain parking facilities should be turned off or reduced to conserve
energy. If reduced lighting is to be used only for the purpose of
property security, it is desirable that the minimum (low point) value
not be less than 0.1 footcandle. Reductions should not be applied
to facilities subject to intermittent night use, such as at apartments,
hospitals and transportation terminals.
| |
2
|
Measured on the parking surface, without any shadowing effect
from parked vehicles or trees at points of measurement.
| |
3
|
The highest horizontal illuminance point at grade, divided by
the lowest horizontal illuminance point or area should not be greater
than the values shown.
| |
4
|
Measured at 1.5 meters (5.0 feet) above parking surface at the
point of the lowest horizontal illuminance, excluding facing outward
along boundaries.
|