Maximum Deflection Length of:
|
Approximate Radius of Curve
With Pipe Produced by Succession of Joints with Pipe Leads of:
| |||||||
---|---|---|---|---|---|---|---|---|
Pipe Diameter
(inches)
|
Joint Opening
|
16 Feet
|
18 Feet
|
20 Feet
|
16 Feet
|
18 Feet
|
20 Feet
| |
4
|
0.41
|
14.8
|
16.7
|
18.5
|
208
|
234
|
260
| |
6
|
0.58
|
14.8
|
16.7
|
18.5
|
208
|
234
|
260
| |
8
|
0.65
|
12.9
|
14.6
|
16.2
|
238
|
268
|
297
| |
10
|
0.75
|
12.4
|
14.0
|
15.5
|
248
|
279
|
310
| |
12
|
0.75
|
10.5
|
11.9
|
13.2
|
292
|
327
|
363
| |
16
|
0.75
|
7.9
|
8.8
|
9.7
|
390
|
440
|
488
|
L = ND ** P/1,850
| ||||
Where
| ||||
L
|
=
|
The allowable leakage in gallons per hour.
| ||
N
|
=
|
The number of joints in the length of pipe tested.
| ||
D
|
=
|
The normal diameter of the pipe in inches.
| ||
P
|
=
|
The average test pressure during the leakage
test in pounds per square inch gauge.
|