Table I
| |
---|---|
Capacity of Tank or Tanks Within Diked Area
(gallons)
|
Minimum Distance From Dike to Line of Adjoining Property
Which May Be Built Upon for Other Than Oil Storage Purposes
(feet)
|
1,000 to 10,000
|
75
|
10,001 to 50,000
|
100
|
50,001 to 200,000
|
150
|
200,001 to 750,000
|
200
|
750,001 to 2,500,000
|
250
|
2,500,001 and over
|
300
|
Table II
| |
---|---|
Capacity of Tank or the Larger of the Two Tanks Between
Which the Distance Is To Be Established
(gallons)
|
Minimum Space Between Nearest Points Of Tanks
(feet)
|
1,000 to 10,000
|
10
|
10,001 to 50,000
|
15
|
50,001 to 200,000
|
25
|
200,001 and above
|
Equal to the diameter of the greatest horizontal dimension of
the larger of the 2 tanks between which the distance is to be established.
|