[Adopted 12-15-2009 by Ord. No. 1054 as Secs. 9-2-1 through 9-2-3 and 9-2-5 through 9-2-13 of the 2009 Code of Ordinances]
The provisions of this article are intended to provide for the City of Lake Mills rules and regulations to improve public safety by promoting the control of fire hazards; regulating the installation, use and maintenance of equipment; regulating the use of structures, premises and open areas; providing for the abatement of fire hazards; establishing the responsibilities and procedures for code enforcement and setting forth the standards for compliance with and achievement of objectives.
Except as specifically otherwise provided herein, the provisions of this Fire Prevention Code shall apply equally on public and private property and to all locations.
A. 
National and State Fire Safety Codes adopted.
(1) 
Except as provided in Subsection B, there are hereby adopted as part of the Fire Prevention Code of the City of Lake Mills and incorporated herein as if fully set forth the following codes and standards:
(a) 
NFPA 1, 2021 edition, "Fire Prevention Code," of the National Fire Protection Association, including its incorporated Standards, Annexes, Codes and Appendixes, as published in the National Fire Codes of the National Fire Protection Association.
[Amended 11-15-2022 by Ord. No. 1249]
(b) 
Chapter SPS 310, Flammable and Combustible Liquids.
(c) 
Chapter SPS 340, Gas Systems.
(d) 
Chapter SPS 314, Fire Prevention.
(e) 
Chapters SPS 361 to 365, Commercial Building Code.
B. 
Exceptions. The following sections of Annex A of the 1987 edition of the NFPA "Fire Prevention Code" are excluded from the Lake Mills Fire Prevention Code:
3-9.1
Matches
3-9.2
Type Permitted
3-9.2.2
Packaging and Labeling
3-9.2.3
Storage Requirements
3-9.2.3.1
Vertical Openings
3-9.2.3.2
Sources of Ignition
3-9.2.3.3
Storage at Wholesale Outlets
3-9.2.3.4
Match Storage with other Commodities
C. 
Copies of incorporated codes to be filed. At least one copy each of all codes and standards incorporated in this Fire Prevention Code as set forth in Subsection A above shall be kept on file and open for public inspection during all business hours in the office of the Fire Inspector.
[Amended 11-15-2022 by Ord. No. 1249]
If the Fire Chief finds that any building or its contents or both are damaged by fire to a point where the structure and its contents or both present a health or life safety hazard to the public, the Chief may issue orders to the owner of the property on which the building is located to abate such hazard through repair or removal of the building and/or its contents. Such orders shall be served personally or by certified mail, return receipt requested, on the owner and each lienholder of record in the office of the Jefferson County Register of Deeds whose address is known or can be ascertained with reasonable diligence and include a time period to complete abatement of such hazard to extend no more than 60 days. After 60 days, the Fire Chief may order the building and contents removed. The owner of the property will be held responsible for any expenses incurred, and any expenses incurred by the City not paid within 30 days of billing shall be levied against the premises on which the building was located pursuant to Wis. Stats. § 66.0627 as a special charge for current services. Written request for extension of the time permitted to complete ordered repairs or removal shall be submitted to the Fire Chief within 45 days after the service of the notice. The written request must contain the following information: (1) the reason compliance cannot be completed within the sixty-day limit; (2) the projected date the repairs are to start; (3) the type of repairs to be conducted; and (4) the projected date repairs are to be completed.
Fire alarm systems are regulated under Chapter 246, Alarm Systems, of the Code of the City of Lake Mills.
A. 
Scope. Emergency illumination shall include all required exit lights and emergency lighting as required by this section.
B. 
Emergency lighting in public areas. Emergency lighting shall be installed in the following occupancies:
(1) 
Factories. Within any factory over two interior stories or 10,000 square feet in gross interior area.
(2) 
Offices. Within any office over two interior stories or 10,000 square feet gross interior area.
(3) 
Mercantile buildings. Within any mercantile building over two interior stories or 4,000 square feet in gross interior area.
(4) 
Places of public assembly. Within any place of public assembly (buildings with an occupancy load of 100 people or more), regardless of size.
(5) 
Residential occupancies. Residential buildings with common areas and containing 10 or more bedrooms (efficiency units shall be considered as bedrooms).
(6) 
Taverns. Within any tavern regardless of size.
(7) 
Schools and places of instruction (including day-care centers). Within any school or place of instruction housing more than 20 students.
(8) 
Health care facility. Within any health care facility regardless of size.
(9) 
Place of detention. Within any place of detention regardless of size.
C. 
Battery backup for exit lights.
(1) 
All illuminated exit signs required under Wisconsin Administrative Code Chs. SPS 361 to 365 shall be equipped with emergency power to maintain illumination during power failures.
(2) 
Any illuminated exit signs installed prior to the activation of this code shall be upgraded at the time of remodeling.
D. 
Standards. Emergency illumination shall be installed in accordance with National Electrical Code 700-16.
E. 
Emergency lighting locations. Emergency lighting shall be located in hallways, stairwells, open meeting areas 1,000 square feet or larger and basements for all areas of occupancy as identified in § 362-11B.
A. 
When required. Where the municipal water system is available, and any portion of a commercial, residential or industrial building is set back more than 300 feet from the municipal fire hydrants, the owner shall install approved water hydrants at its expense, as approved by the City of Lake Mills Board of Public Works. The setback distance shall be determined by measuring the travel distance from a municipal hydrant along the center line of a municipal street or private road suitable for travel by fire apparatus.
B. 
Location.
(1) 
Hydrants determined to be necessary in accordance with Subsection A shall be freestanding and shall be installed not more than 50 feet nor less than 25 feet from the building. One hydrant shall be located at the main entryway to such building or complex. Additional hydrants shall be provided around the perimeter of the building or complex so no hydrant is more than 400 feet from any other approved hydrant as described in Subsection A. All hydrants shall be accessible to Fire Department vehicles with adequate paved surfaces no more than five feet from the hydrant location.
(2) 
All water mains, hydrants and their location shall be approved by the Lake Mills Board of Public Works and the Lake Mills Water Utility. The hydrants shall be installed in such a manner and location so as to be accessible at all times to the Fire Department. Special fees associated with the installation of hydrants on private property shall be paid by the property owner in accordance with Public Service Commission rules, regulations, and rates.
C. 
Installed prior to construction. For new construction, hydrants required by this section shall be installed and made operable prior to permitting construction to progress beyond the footing and foundation stages.
D. 
Specifications. All water mains and hydrants shall be installed in compliance with the standards of the City of Lake Mills Board of Public Works. Unrestricted access to all fire hydrants and connecting mains shall be granted to the Lake Mills Water Utility and permanent easements shall be granted by the property owner for all hydrants and connecting mains.
E. 
Blocking of fire hydrants prohibited. No person shall park any motor vehicle within 10 feet of any fire hydrant or otherwise interfere with the accessibility of any fire hydrant by piling, dumping or placing any other obstructive material or object within 10 feet of a fire hydrant without first obtaining written permission from the Fire Department. Every day during which such interference continues shall constitute a separate offense.
F. 
Marking of fire hydrants. Fire hydrants shall be marked with the curb painted yellow. The curb shall be painted to produce a twenty-foot stripe extending 10 feet to each side of the hydrant. Areas without curbs shall have a four-inch-wide yellow stripe placed on the pavement which extends 10 feet to each side of the hydrant in a line parallel to the building.
A. 
General requirements.
(1) 
Where required. All premises public or private which the Fire Department may be called upon to protect in case of fire and which are not readily accessible from public roads, shall be provided, at the property owner's(s') expense, with suitable access roads and fire lanes so that all buildings on the premises are accessible to fire apparatus.
(2) 
Fire lanes. Fire lanes shall be provided, at the property owner's(s') expense, on public or private property devoted to public use for all buildings used for human habitation or occupancy which are set back more than 100 feet from any roadway access or which exceed 30 feet in height and are set back more than 50 feet from a roadway. Fire lanes may also be designated on those private roadways where it is found by the Fire Chief that such access is necessary for fire apparatus.
(3) 
Width. Fire lanes shall be at least 20 feet in width with the closest edge of the lane at least 10 feet and no more than 30 feet from the building.
(4) 
Dead-end roads. Any dead-end road more than 300 feet long shall be provided a turnaround at the closed end of the roadway. Turnarounds can be T-type or hammerhead, cul-de-sac or curved driveway.
(5) 
Turning radius. Curves and turnarounds shall be designed for a forty-eight-foot turning radius.
(6) 
Designation, marking and maintenance of fire lanes. The designation, marking and maintenance of fire lanes shall be accomplished as specified by the Fire Chief. The current Wisconsin Department of Transportation standards for highway marking shall be used as guidelines in designating and marking fire lanes.
(a) 
Designated fire lanes shall be marked with signs within five feet of the beginning and within five feet of the end of fire lane, with spacing between signs not to exceed 75 feet. Each sign shall face in the direction of oncoming traffic. The curb shall be painted yellow, if there is no curb, a four inch wide stripe shall be painted the full length of the fire lane. Fire lane sign shall be affixed to a stationary pole or object. Signs shall be plainly visible.
(b) 
Roadways identified exclusively as fire lanes shall be identified with approved fire lane signs on each side facing forward and the pavement area between the signs shall be striped with four-inch-wide yellow stripes.
(c) 
Before the requirements may be enforced, the fire lane must be approved by the Fire Department. A sticker is placed on each sign indicating approval and authorizing enforcement of the provisions of this article.
(7) 
Emergency access. A written document, agreeable to the Fire Chief and for the benefit of the City, shall be required for emergency access over all fire lanes. The document shall define the area designated as a fire lane and shall specify those methods used to label or post the area as a fire lane. A copy of the document shall be kept on file at the Fire Department.
B. 
Unlawful designation of fire lanes. No person, firm or corporation shall post, damage or remove a fire lane sign without the approval of the Fire Department.
C. 
Obstruction of fire lane regulated.
(1) 
Removal of unlawfully parked vehicles. Any vehicle that is parked within a lawfully designated and marked fire lane may be removed at the vehicle owner's expense. Vehicles shall be towed away under the following circumstances:
(a) 
When a vehicle is repeatedly in violation of this section by being habitually parked in a fire lane.
(b) 
When a vehicle blocks the ingress/egress of a business, theater, nightclub, apartment complex, gymnasium or a place of public assembly.
(c) 
When the vehicle's presence threatens the life or safety of the public by impeding the ability of fire apparatus and/or emergency medical equipment to respond to an emergency.
(d) 
Removal of a vehicle under such circumstances may be authorized by the person in lawful possession of the property or by the Fire Chief, or his/her representative. The Police Department may order the towing of a vehicle at any time that the above conditions exist.
(2) 
In addition to any other remedy authorized by this section, owners of vehicles parked in fire lanes may be cited with a notice of violation on a standard "Wisconsin Uniform Citation" form issued by a member of the Police Department who has been granted citation authorization.
(3) 
Temporary loading or unloading permitted. Vehicles may stop in a fire lane while actively loading or unloading, provided the driver is present at all times. When this requirement is met, a reasonable amount of time may be allowed for the completion of the transaction.
(4) 
Obstructions other than vehicles. Whenever an obstruction is found in a designated fire lane, an inspection report with warning notice shall be issued to the property owner, occupant or responsible party requiring that if the obstruction is not removed within the specified time period, the Department may cause the removal of the obstruction with the cost of removal billed to the person(s) responsible for the obstruction.
(5) 
When it becomes necessary to obstruct a fire lane, i.e., construction, remodeling or repair, a site approval shall be required and permission obtained from the Fire Department. A copy of the authorization shall be posted at the site.
(6) 
Unapproved fire lanes. Fire lane signs posted without the approval of the Fire Department shall be removed unless the fire lane is formally established and posted as required by this section.
A. 
Required. Every building construction site shall be accessible to Fire Department apparatus by way of an access roadway. An access roadway shall be in place and accessible to fire equipment prior to the delivery of any combustible construction materials.
B. 
Design.
(1) 
Access roadways shall be extended to within 30 feet of the closest edge of the property line.
(2) 
Access roadways shall have not less than 20 feet of unobstructed width and a minimum of 13 feet six inches of vertical clearance.
(3) 
A driving surface of at least road base quality gravel shall be maintained at all times in order that all-weather integrity is assured. The road base shall be capable of supporting the imposed loads of fire apparatus.
C. 
Maintenance. During winter months, the roadways shall be maintained by the developer or property owner to include proper and timely snow removal.
D. 
Penalty for noncompliance. Failure to comply with these requirements shall result in revocation of building permits and/or refusal to issue permits.
A. 
Key box required. When access to or within a structure or an area is unduly difficult because of secured openings or where immediate access is necessary for lifesaving or firefighting purposes, the Fire Chief may require that a key box be installed in an accessible location. The key box shall be a type approved by the Fire Department and shall contain those keys found to be necessary to provide emergency access.
B. 
Property owner responsible. The property owner is responsible to assure keys maintained within a key box are those of the current type. When a change of locks within the building is necessary, the Fire Department shall be notified with new keys placed in the key box.
C. 
Removal of key prohibited. Removal of any key by other than Fire Department personnel shall be a violation of this chapter.
A. 
Scope. Automatic sprinkler systems shall be tested, installed, and maintained in operable condition in all new occupancies and locations hereafter set forth.
B. 
Installation. Except for one- and two-family dwellings, the installation of any automatic fire sprinkler systems shall be completed in accordance with NFPA 13, "Installation of Sprinkler Systems," or NFPA 13R, "Installation of Sprinkler Systems in Residential Occupancies up to Four Stories in Height." In one- and two-family dwellings, automatic fire sprinkler systems shall be installed in accordance with NFPA 13D, "Standards for the Installation of Sprinkler Systems in one and two Family Dwellings and Mobile Homes."
C. 
Monitoring requirements. New automatic sprinkler systems installed under this chapter shall be monitored by an approved central station monitoring service, except in the following occupancies:
(1) 
One- and two-family dwellings and mobile homes.
(2) 
Apartments, townhouses, and condominiums with less than 50 dwelling units.
D. 
Maintenance: annual inspection. All automatic sprinkler systems shall be properly maintained for efficient service as specified in NFPA 25, 1995, "Standard for the Care and Maintenance of Sprinkler Systems." Maintenance shall be the responsibility of the building owner.
E. 
Where required. Automatic sprinkler systems shall be installed and maintained in operable condition in the following new occupancies and locations:
(1) 
Within all new factories, workshops, office buildings, mercantile establishments, warehouses, passenger terminal, exhibition buildings, and places of public assembly with less than a one-hundred-person occupant load:
(a) 
Where the building is of Class 1 or Class 2 fire-resistive construction and is 10,000 square feet or more in total area;
(b) 
Where the building is of Classes 3 through 8 non-fire-resistive construction and is 7,000 square feet or more in total area; or
(c) 
Buildings of three interior stories or more in height, regardless of area.
(2) 
Within new repair garages, motor vehicle storage garages and body shops:
(a) 
Where the building is of Class 1 or Class 2 fire-resistive construction, and is 10,000 square feet or more in total area;
(b) 
Where the building is of Classes 3 through 8 non-fire-resistive construction, and is 7,000 square feet or more in total area;
(c) 
Where the building has three interior stories or more in height, regardless of area; or
(d) 
In any basement or subbasement if a vehicle can be parked therein.
(3) 
Within the following residential occupancies:
(a) 
Multiple-family dwellings, apartment buildings, townhouses, condominiums, hotels, motels, dormitories, fraternities, sorority houses and other places of abode, except one- and two-family dwellings, under the following requirements:
[1] 
New residential buildings having three interior stories or less in height or having no more than four living units shall have sprinklers installed in the basement, crawl spaces, stairways and corridors.
[2] 
New residential buildings with more than three interior stories in height or containing more than a total of four living units shall be protected by an automatic sprinkler system installed throughout the building regardless of size or type of construction.
[3] 
New residential buildings with no common interior area shall provide direct access to the sprinkler system riser on the outside of the building for use by Fire Department personnel.
(b) 
Automatic sprinkler systems are not required in one- and two-family dwellings, but when installed, shall meet the following requirements:
[1] 
Any installation of an automatic sprinkler system within a one- or two-family dwelling shall be installed in accordance with NFPA 13D, "Standards for the Installation of Sprinkler Systems in One- and Two-Family Dwellings and Mobile Homes."
[2] 
Automatic sprinkler systems installed within one- and two-family dwellings shall have two copies of the plans submitted to the Fire Department for review and conditional approval.
[3] 
Residential quick-response sprinkler heads are to be used.
[4] 
The installation of the sprinkler system shall be inspected by the Fire Department prior to enclosing of wall and ceiling spaces.
[5] 
A hydrostatic test shall be conducted on the system in the presence of a Fire Department inspector.
[6] 
A final inspection by the Fire Department shall be conducted prior to placing system in service.
(4) 
New theaters and buildings of public assembly over one-hundred-person occupancy. Automatic sprinklers shall be installed throughout such buildings regardless of size or type of construction.
(5) 
New health care facilities, including hospitals, nursing homes, convalescent and group care centers. Automatic sprinklers shall be installed throughout such buildings regardless of size or type of construction.
(6) 
New detention and correctional facilities. Automatic sprinklers shall be installed throughout the building, regardless of size or construction.
(7) 
New schools, colleges and universities:
(a) 
Where the building is of Class 1 or Class 2 fire-resistive construction, and is 10,000 square feet or more in total area, automatic sprinklers shall be installed throughout the building.
(b) 
Where the building is of Classes 3 through 8 non-fire-resistive construction, automatic sprinklers shall be installed throughout the building.
(8) 
High-hazard occupancy. Throughout any new building which by reason of its construction or combustible occupancy is deemed a severe life or property hazard by the Fire Chief. This includes but shall not be limited to:
(a) 
Aircraft/helicopter hangers, aircraft/helicopter servicing.
(b) 
Dry-cleaning establishments using or storing volatile or flammable liquids.
(c) 
Enameling or Japanning operations.
(d) 
Mills.
(e) 
Paint and varnish: manufacturing, storage, handling, spraying or other related operations.
(f) 
Pyroxylin products.
(g) 
Smoke houses.
(h) 
Storage of combustible and flammable gases such as acetylene, hydrogen, liquid propane, etc., in excess of 1,000 cubic feet.
(i) 
Storage of combustible and flammable liquids such as kerosene, oil gasoline, etc., in excess of 500 gallons.
(j) 
Woodworking establishments.
(k) 
Chemical works.
(l) 
Warehouses with materials piled 15 feet or more in height.
(m) 
Explosive and pyrotechnic manufacturing and storage.
(n) 
Basements over 2,500 square feet and containing combustible materials or storage therein.
F. 
Exceptions. Automatic fire sprinkler systems are not required in the following:
(1) 
Rooms or buildings used for the manufacture or storage of aluminum powder, calcium carbide, calcium phosphide, metallic sodium or potassium, quick lime, magnesium powder, sodium peroxide or like materials where the application of water may cause or increase combustion.
(2) 
Any location where the Fire Chief determines that the use of water as a fire-extinguishing agent would increase the hazard. However, an automatic fire suppression system using an extinguishing agent other than water, or an automatic smoke detection system, shall be installed.
(3) 
One- and two-family dwellings.
(4) 
In new factories, workshops, office buildings, mercantile establishments, warehouses, passenger terminals, exhibition buildings, places of public assembly with less than one-hundred-person occupant load, and new repair garages, motor vehicle storage garages and body shops, if:
(a) 
The building is of Class 1 or 2 fire-resistant construction and is less than 10,000 square feet in total area.
(b) 
The building is of Class 3, 4, 5, 6, 7 or 8 non-fire-resistant construction and is less than 7,000 square feet in total area.
G. 
Buildings in areas without municipal water supply. Any building of a size or use that falls within the requirements of Subsection E, erected within an area not served by the municipal water system shall be constructed to structurally support a sprinkler system. Once municipal water is available, the building owner shall have 90 days to install an automatic sprinkler system which conforms to this chapter.
H. 
Large buildings in areas with inadequate municipal water supply. Any building having a total area of 25,000 square feet or more erected for any of the uses described in Subsection E shall install an automatic sprinkler system at the time of construction. Water for the system shall be supplied by a pressure tank or other approved water source capable of delivering the required water flow for a period of 30 minutes if monitored by a central station monitoring service or 60 minutes if unmonitored.
I. 
Plan review: installation, inspection.
(1) 
Approval of plans required. No automatic sprinkler equipment shall be installed or altered in any building until plans have been submitted to and reviewed by the Fire Department. Three copies of the plans and specifications shall be submitted for review. Conditionally approved plans shall be stamped with the date of review. One copy shall be returned to owner, two retained by the Department for field use and property file reference.
(a) 
Plans. Plans for sprinkler systems (including drawings, diagrams as needed) shall be submitted to the Fire Department for review and conditional approval. Plans shall be conditionally approved prior to any installation or construction.
(b) 
Calculations. Calculations shall be submitted with all plans. In the event a pipe schedule is used, a written report with verified pressure information shall be submitted. The engineer completing such calculations shall stamp and sign the report.
(2) 
Installation and inspection services required.
(a) 
The installation of underground piping shall be inspected by the Fire Department prior to being covered.
(b) 
The installer shall provide advance notice to the Fire Department for any required installation inspection.
(3) 
System requirements. All required building automatic sprinkler systems shall comply with the following, provided existing systems not in compliance on the effective date of this article shall have until January 1, 1997, to come into compliance.
(a) 
System drain. The building automatic sprinkler system shall have a drain piped to the outside of the building or to a drain suitable to handle the required flows.
(b) 
Inspector's test valve. The system shall have an inspector's test valve piped so as to discharge to the outside of the building.
(c) 
Alarm bells or horns. Alarm bells or horns shall be installed on all systems. One bell or horn shall be installed on the inside of the building and a second bell or horn installed on the outside of the building. The sprinkler alarm shall be tied into the building alarm system in buildings equipped with a local alarm system.
(4) 
Acceptance test. The sprinkler system shall have a hydrostatic test performed by the installer in the presence of a Fire Department inspector. The sprinkler system shall be tested by flows of the main drain and inspector's test. The installer shall notify the Fire Department prior to any test being conducted.
J. 
Annual testing. A qualified sprinkler technician shall inspect the automatic sprinkler system at least annually. The provisions of NFPA 25, 1995, Chapters 1 through 7, shall be used as the inspection criteria.
K. 
Lock box required. Buildings equipped with an automatic sprinkler system shall be provided with a standard lock box of a type approved by the Department. The lock box shall be located in a place approved by the Fire Department. Properly identified keys to gain access to the building and the building automatic sprinkler system shall be maintained in the lock box. Removal of any key by persons other than Fire Department personnel shall be considered a violation of this article.
L. 
Retroactive provisions. The provisions of (9)(C)1, System Drains, and (10), Annual Testing, shall apply to all sprinkler systems installed within the City of Lake Mills. Systems not in compliance with the provisions of (9)(C)1 shall have until January 1, 1997, to come into compliance.
A. 
Scope. Standpipe and hose systems shall be installed and maintained in operable condition in the following occupancies and locations in the City:
(1) 
In any new building over three interior stories.
(2) 
Within any building 100,000 square feet or more in total gross area.
(3) 
Within any building having a horizontal dimension of 300 or more feet.
B. 
Installation standards. Standpipe and hose systems shall be installed in accordance with NFPA 14, 1993, "Standards for Installation of Standpipe and Hose Systems." Standpipe and hose systems required in Subsection A(1), (2) and (3) shall be of Class I or III types, as specified in NFPA 14, 1993. Wet standpipe systems may be an integral part of an approved automatic sprinkler system, provided calculations for required fire flows have been submitted with sprinkler system plans.
[Amended at time of adoption of Code (see Ch. 1, General Provisions, Art. I)]
C. 
Maintenance. Standpipe and hose systems shall be maintained in accordance with NFPA 14, "Standards for Installation of Standpipe and Hose Systems."
D. 
Areas without municipal water supply. Any building erected which falls within the criteria described in this chapter in an area which does not have a municipal water supply shall construct a dry type standpipe and hose system which the Fire Department can connect to in the event of an emergency.
E. 
Areas with an inadequate municipal water supply. Any building erected for any of the uses described in Subsection A of this section in an area in which the municipal water supply cannot, for any reason, provide the water pressure or volume necessary to operate a standpipe and hose system shall have an approved fire pump or secondary water supply installed to provide the required water flow for that occupancy.
F. 
Conditional approval required prior to installation of standpipe and hose systems. No standpipe and hose system shall be installed or altered in any building until three copies each of the following plans and calculations have been submitted to, reviewed and conditionally approved by the Lake Mills Fire Department. Conditionally approved plans shall be stamped with the date of review. One copy shall be returned to the owner, one copy kept on file in the Fire Department office, and one copy to the Lake Mills Water Utility.
(1) 
Plans and specifications. Plans (including drawings, diagrams as needed) shall be submitted, on all standpipe and hose systems to the Department for review and conditional approval.
(2) 
Calculations. Hydraulic calculations shall be submitted with all plans. The engineer producing the calculations shall stamp and sign the calculations.
G. 
Installation of standpipe and hose systems; inspection required.
(1) 
Underground piping. The installation of underground piping shall be inspected by an inspector from the Fire Department prior to being covered.
(2) 
Acceptance test, standpipe and hose systems:
(a) 
After installation, standpipe and hose systems shall have a hydrostatic test performed by the installer in the presence of an inspector from the Lake Mills Fire Department. The system shall be tested by the installer in accordance with NFPA 14, 1993.
(b) 
The installer shall give advance notice to the Fire Department for any test to be conducted.
(3) 
Installer responsible for compliance. Failure to comply with the listed items can result in enforcement action against the installer.
H. 
Standpipe and hose system test requirements. Inspection of a standpipe and hose system shall be conducted annually by a qualified sprinkler/standpipe technician in accordance with NFPA 14, Chapter 8. Exception: Hydrostatic testing of underground piping may be omitted during annual testing. An inspection report shall be completed on the system inspected, and a copy of the report shall be submitted to the Fire Department to be kept on file.