Enclosure Exceptions
| |
---|---|
Building Use Group
|
Exception Conditions*
|
Business
|
When connecting not more than 2 floor levels
and less than 3,500 square feet per floor
|
When connecting not more than 3 floor levels
and the building is equipped with an automatic fire suppression system
| |
Education
|
When connecting not more than 2 floor levels
and the building is equipped with an automatic fire suppression system
|
Factory-industrial, storage
|
When connecting not more than 2 floor levels
|
When connecting not more than 3 floor levels
and the building is equipped with an automatic fire suppression system
| |
Mercantile
|
When connecting not more than 2 floor levels
and less than 2,000 square feet per floor
|
When connecting not more than 2 floor levels
and the building is equipped with an automatic fire suppression system
| |
Residential, hotels
|
When connecting not more than 2 floor levels
and the building is equipped with an automatic fire suppression system
|
Residential, apartment
|
When connecting not more than 2 floor levels
with not more than 4 dwelling units per floor
|
When connecting not more than 3 floor levels
with not more than 4 dwelling units per floor and the building is
equipped with an automatic fire suppression system
| |
Residential one- and two-family dwellings
|
In every case
|
*NOTE: One square foot = 0.093 square meters.
|