Enclosure. All shafts shall be enclosed as required by sections of this code for exits, except elevator and supplemental stairway shafts which are immediately adjacent to and not separated from floor openings connecting the same floors served by the shaft. The opening protectives shall provide a substantial barrier to fire penetration. Building service shafts such as trash chutes, utility and duct shafts shall be enclosed as required by this code.
All means of egress shall be equipped with artificial lighting in accordance with the building code. Emergency lighting shall be provided in accordance with the building code.
All exits shall be indicated with exit signs in accordance with the building code.
A sign shall be provided at each floor landing in all interior stairways more than three stories above grade, designating the floor level above the floor of discharge. All elevator lobby call stations on all floor levels in buildings more than 75 feet (22,860 millimeters) above grade shall be marked with approved signs reading as follows: "Use Stairways in Case of Fire — Do Not Use Elevators."
A. 
High-hazard use. All buildings and portions thereof of high-hazard use shall be equipped with an approved automatic fire suppression system.
B. 
Commercial range hoods. All range hoods and connecting duct systems when used in conjunction with frying and cooking operations, except domestic range hoods not used for commercial purposes, shall be equipped with an approved automatic fire suppression system.
C. 
Fire standpipes. All buildings having floors used for human occupancy located more than six stories above grade shall be provided with standpipes according to the building code, except that an automatic water supply, hose and cabinets are not required. The standpipes shall have an approved fire department connection with hose connections at each floor level.
D. 
Smoke detectors. Smoke detectors shall be installed in accord with the requirements of the Uniform Fire Safety Act[1] or the Village ordinance governing the installation of smoke detectors.[2]
[1]
Editor's Note: See N.J.S.A. 52:27D-192 et seq.
[2]
Editor's Note: See Ch. 149, Fire Prevention, Art. II.
E. 
Fire alarm system. All buildings of educational use shall be equipped with a manual fire alarm system in accordance with the requirements of the Uniform Fire Safety Act.
All buildings having floors used for human occupancy served by elevators shall have at least one elevator equipped with emergency controls, and all elevators shall be equipped with car recall activated by a smoke detector in each lobby in accordance with the building code.
Smoke and heat detection. Each recirculating air or exhaust system which serves more than one floor in buildings which exceed six stories in height shall be equipped with approved smoke and heat detection devices in accordance with the mechanical code. The devices shall stop the fan(s) automatically and shall be of the manual reset type. Automatic fan shutdown is not required when the system is part of an approved smoke removal or control system.