The purpose of this chapter is to:
A. Protect the public potable water supply served by the
Westminster Water and Sewer Commission from the possibility of contamination
or pollution by isolating such contaminants or pollutants which could backflow
or backsiphon into the public water system.
B. Promote the elimination or control of existing cross-connections,
actual or potential, between its customers in-plant potable system and nonpotable
systems.
C. Provide for the maintenance of a continuing program of
cross-connection control which will effectively prevent the contamination
or pollution of all potable water systems by cross-connection.
The statutory authority for this chapter shall be:
A. As provided in the Federal Safe Drinking Water Act of
1974, (Public Law 93-523), and the Commonwealth of Massachusetts Drinking
Water Regulations, 310 CMR 22.22, the water purveyor has the primary responsibility
for preventing water from unapproved sources or any other substances from
entering the public potable water system.
B. Westminster Water and Sewer Commission Rules and Regulations,
adopted March 13, 1995.
The Water Commission shall be responsible for the protection of the
public potable water distribution system from contamination or pollution due
to the backflow or backsiphonage of contaminants or pollutants. If, as a result
of a survey of the premises, the Commission determines that an approved backflow
prevention device is required at the town's water service connection
or as in-plant protection on any customer's premises, the Commission
or its delegated agent shall issue a cross-connection violation form to said
customer to install approved backflow prevention devices. The customer shall,
within a time frame determined by the Commission, install such approved device
or devices at his own expense, and failure or refusal or inability on the
part of the customer to install said device or devices within the specified
time frame shall constitute a ground for discontinuing water service to the
premises until such device or devices have been properly installed.
As used in this chapter, the following terms shall have the meanings
indicated:
AIR GAP SEPARATION
The method of preventing backflow through the use of an unobstructed
vertical distance through the free atmosphere between the lowest opening from
any pipe or faucet supplying water to a tank, plumbing fixture or other device
and the flood level rim of the receptacle.
APPROVED
Accepted by the reviewing authority as meeting an applicable specification
stated or cited in this chapter or as suitable for the proposed use.
ATMOSPHERIC VACUUM BREAKER
An approved backflow device used to prevent back siphonage which
is not designed for use under static line pressure.
AUXILIARY WATER SUPPLY
Any water supply of unknown or questionable quality on or available
to the premises other than the supplier's approved public potable water
supply.
BACK PRESSURE
Pressure created by mechanical means or other means which causes
water or other liquids or substances to flow or move in a direction opposite
to that which is intended.
BACK SIPHONAGE
A form of backflow due to reduced or subatmospheric pressure within
a water system.
BACKFLOW
The flow of water or other liquids, mixtures or substances into the
distribution pipes or a potable water supply from any source other than the
intended source.
BACKFLOW PREVENTER WITH INTERMEDIATE ATMOSPHERIC VENT
A device having two independently operating check valves separated
by an intermediate chamber with a means for automatically venting it to the
atmosphere, in which the check valves are force loaded to a normally closed
position and the venting means is force loaded to a normally open position.
BAROMETRIC LOOP
A loop of pipe rising at least 35 feet, at its topmost point, above
the highest fixture it supplies.
COMMISSION
The Town of Westminster Water Commission.
CONTAMINANT
Any physical, chemical, biological or radiological substance or matter
in water.
CROSS-CONNECTION
Any actual or potential connection between a distribution pipe of
potable water from a public water system and any waste pipe, soil pipe, sewer,
drain or other unapproved source.
CROSS-CONNECTION VIOLATION FORM
A violation form, designated by the Department, which is sent to
the owner by the water supplier, with copies sent to the Department, plumbing
inspectors and Board of Health, delineating cross-connection violations found
on the owner's premises and a procedure for corrective action.
DEPARTMENT
The Massachusetts Department of Environmental Protection.
DOUBLE CHECK VALVE ASSEMBLY
A backflow prevention device which incorporates an assembly of check
valves, with shut-off valves at each end and appurtenances for testing.
IN-PLANT PROTECTION
The location of approved backflow prevention devices in a manner
which provides simultaneous protection of the public water system and the
potable water system within the premises.
OWNER
Any person maintaining a cross-connection installation or owning
or occupying premises on which cross-connections can or do exist.
PERMIT
A document issued by the Department which allows a cross-connection
installation.
PERSON
Any individual, corporation, company, association, trust, partnership,
the commonwealth, a municipality, district or other subdivision or instrumentality
of the United States, except that nothing herein shall be constructed to refer
to or to include any American Indian tribe or the United States Secretary
of the Interior in his capacity as trustee of Indian lands.
PRESSURE VACUUM BREAKER
An approved backflow prevention device designed to prevent only back
siphonage and which is designed for use under static line pressure and which
has necessary appurtenances for testing.
REDUCED PRESSURE BACKFLOW PREVENTER
An approved backflow prevention device incorporating two more check
valves, an automatically operating differential relief valve located between
the two checks, two shut-off valves and necessary appurtenances for testing.
RESIDENTIAL DUAL CHECK
An assembly of two spring-loaded, independently operating check valves
without tightly closing shut-off valves and test cocks; generally employed
immediately downstream of the water meter to act as a containment device.
REVIEWING AUTHORITY
The Department, its designee or the local plumbing inspector, authorized
by MGL C. 142 and licensed by the Board of State Examiners of Plumbers and
Gas Fitters, whichever is responsible for the review and approval of the installation
of an approved backflow prevention device.
The Commission recognizes the threat to the public water system arising
from cross-connections. As such, the Commission, whereas it is responsible
for the quality of the public water supply, may require a containment device
on the water service entrance to any customer who, as a result of unprotected
cross-connections, could contaminate the public water supply system.
The Commission shall not allow a cross-connection to exist within the
public water supply system unless it is considered necessary and all appropriate
approvals and permits have been issued.
Any existing backflow preventer shall be allowed by the Commission to
continue in service unless the degree of hazard is such as to supersede the
effectiveness of the present backflow preventer or result in an unreasonable
risk to the public health. Where the degree of hazard has increased, as in
the case of a residential installation converting to a business establishment,
any existing backflow preventer must be upgraded to a reduced pressure backflow
preventer, or a reduced pressure backflow preventer must be installed in the
event that no backflow device was present.
The Commission strongly recommends that all new and retrofit installations
of reduced pressure backflow preventers and double check valve assemblies
include the installation of strainers located immediately upstream of the
backflow device. The installation of strainers will preclude the fouling of
backflow devices due to both foreseen and unforeseen circumstances occurring
to the water supply system such as water main repairs, water main breaks,
fires, periodic cleaning and flushing of mains, etc. These occurrences may
stir up debris within the water main that will cause fouling of backflow devices
installed without the benefit of strainers.
The initial backflow prevention device test is $50. All repeat tests
are $75.