[Ord. No. 266, 6-11-1990]
A. 
Key Water Supply Personnel. Key Water Supply personnel can be contacted by phone or by two-way radio. Manager and Water Superintendent are responsible for making all necessary contacts in the event of an emergency.
B. 
Notification Of Public. The Manager (backup — Water Superintendent) is responsible for notifying the public of emergency conditions and any special instructions, such as boil orders, which may be necessary. News media phone numbers are listed in Section 700.440 of this Article.
C. 
Other Assistance. Manager and Water Superintendent (or designated representatives) are responsible for contacting other sources of assistance, including the Department of Natural Resources.
[Ord. No. 266, 6-11-1990]
In the event of a power failure, the operator on duty should contact Disaster Power and Light to determine the anticipated length of the outage. If the outage will last more than two (2) hours, the operator should contact the Water Superintendent and begin to prepare emergency generator and gasoline-powered high service pump for use. The Water Superintendent will contact appropriate personnel and will initiate emergency operation of the water plant. Note that all water plant control valves must be operated manually during this period. If it appears that the power failure will continue for a long period of time, water conservation measures should be installed.
[Ord. No. 266, 6-11-1990]
A. 
Source Contamination. Upon receiving report of a spill into the river, immediately contact the Manager and the Water Superintendent. Then, proceed as follows:
1. 
Try to fill all tanks and reservoirs to capacity before the contamination reaches the intakes.
2. 
Find out all you can about the material spilled, its source, estimated time of arrival, and treatment methods available to remove the contaminant.
3. 
Water Superintendent or Manager should contact the Department of Natural Resources for assistance.
4. 
The intakes should be shut down while the spill passes, if at all possible. Conservation measures may have to be initiated.
5. 
The Manager or Water Superintendent should contact one of the laboratories for help in monitoring the contaminant.
B. 
System Contamination. Should the plant or distribution system become contaminated, an attempt should be made to isolate the affected portion of the system. The public must be notified immediately not to drink the water! The affected portion should be cleaned and flushed until no traces of contamination remain.
[Ord. No. 266, 6-11-1990]
Detailed drawings of the water treatment facility and the water distribution system are available in the Water Superintendent's office. Also available are records of past operational and analytical reports.
[Ord. No. 266, 6-11-1990]
The following procedures are intended as guidelines for utilizing tank trucks or trailers to provide potable water during drought or other emergency conditions. The appropriate Department of Natural Resources regional office should be contacted before a water hauling operation is begun.
[Ord. No. 266, 6-11-1990]
Tank trucks or trailers to be used for transporting potable water should be selected with two (2) considerations in mind: the nature of the truck's normal use, and the degree of difficulty in cleaning. Commercial milk or potable water tank trucks are preferred. Trucks designed for the transport of wine, vegetable oil, beer, or other food stuffs may also be used. Trucks that have been used to haul petroleum products or other toxic substances are generally not acceptable and can be used only with the concurrence of the Department of Natural Resources.
[Ord. No. 266, 6-11-1990]
A. 
Water Trucks. Flush tanks thoroughly with potable water and inspect for particulate matter such as rust and sediment.
B. 
Milk Trucks. Scrub tanks with detergent, flush thoroughly with potable water, and inspect for cleanliness.
C. 
The following cleaning procedures may be employed for tank trucks normally used for hauling such liquids as apple juice, vinegar, wine, yeast, liquid sugar, beer, corn syrup, cottonseed oil, peanut oil, margarine oil, linseed oil, sunflower oil, and soybean oil:
1. 
Open the drain and flush with hot, potable water.
2. 
Steam with an emulsifying detergent until the tank is clean. If steam is not available, circulate the detergent at a temperature of one hundred eighty degrees Fahrenheit (180°F) to two hundred ten degrees Fahrenheit (210°F), changing the location of the nozzle to keep the interior continuously wet from top to bottom. Repeat this procedure until tank is clean.
3. 
Rinse the tank thoroughly with hot, potable water, and drain.
All hoses should be stored off the ground and should be properly capped in storage and transit to prevent contamination. All equipment should be of an approved type for water supply purposes, and should be new or obtained from a water supply application. All hoses, pumps, and other equipment should be flushed and disinfected before use.
[Ord. No. 266, 6-11-1990]
Disinfection can be accomplished by filling the clean tank with potable water containing at least fifty (50) ppm chlorine and allowing the water to stand for a minimum of twenty-four (24) hours. The table below indicates the amount of hypochlorite solution (Purex, Clorox, or other household bleach) required to produce fifty (50) ppm in various quantities of water. To insure proper mixing, the bleach must be added slowly as the tank is being filled.
Capacity of Tanks, Gallons
Gallons Bleach Required for 50 ppm*
500
½
1,000
1
1,500
2,000
2
2,500
3,000
3
3,500
4,000
4
4,500
5,000
5
*Assumes household bleach with five percent (5%) available chlorine.
If circumstances preclude the twenty-four (24) hour waiting period, special instructions for disinfecting the tank with higher chlorine concentrations for shorter periods of time can be obtained from the Department of Natural Resources.
[Ord. No. 266, 6-11-1990]
A. 
The source of water must be an approved public water supply. Tanks should be filled and emptied through an air-gap to prevent backflow and contamination of the source. Tank inlets or openings should be covered and properly sealed.
B. 
Water to be transported via tank truck must carry a free chlorine residual of one (1) ppm at the beginning of each one thousand (1,000) gallons of water. The bleach should be added during filling to insure uniform distribution.
[Ord. No. 266, 6-11-1990]
Chlorine residual should be measured frequently to insure that a minimum 0.1 ppm free chlorine residual is maintained. If time allows, tank water should be analyzed for bacterial contamination prior to use.
[Ord. No. 266, 6-11-1990; Ord. No. 420, 5-24-2021]
A. 
New London Water Plant.
B. 
Emergency Coordinator And Key Water Supply Personnel.
1. 
Mary Jane White, Mayor — 573-985-8011.
2. 
Keith Miller, Water Superintendent — 573-822-8917.
C. 
Local Sources Of Assistance.
1. 
Fire Department— James Quick.
2. 
Police Department — 573-985-4041 or 573-985-4231.
D. 
Other Sources Of Assistance.
1. 
DNR Regional Office — 660-385-8000.
2. 
Nearest Poison Control Center — 573-221-0414.
3. 
CHEMTREC — 800-424-9300.
4. 
DNR.(Jefferson City) — 573-751-3241.
5. 
Environmental Protection Agency — 816-374-3778.