[Rev. Ords. 1989, § 5-41]
No person shall store, keep or have in possession for any purpose
or use in any building or place within the town more than five gallons
of naphtha, gasoline, benzene, benzol or other hydrocarbon that will
flash or inflame at a less temperature than 110° F. unless such
person shall have first filed with the town council a statement of
the maximum quantity to be kept, stored, or had in possession and
of the place where and the manner in which it is to be kept, stored
or had in possession by such person. The town council with regard
to the public safety must have first approved in writing the maximum
quantity, place where, and manner in which it is to be stored, kept
or had in possession. It shall not be stored, kept or had in possession
by such person in any greater quantity, or in any such other place
or manner, than so specified in the approval. Any such approval may
be rescinded at any time at the pleasure of the town council.
[Rev. Ords. 1989, § 5-42]
Not more than five barrels in the aggregate of any one or more of the substances stated in §
5-41 shall be stored or kept in any building or place within a thickly settled area or a business section of the town except in a steel tank which shall be located under ground, and the top of such tank which is located in any building shall be below the level of the lowest floor or basement in the building containing the same. All pipes shall be arranged to drain back into the supply tank. If in the opinion of the town council the public safety will be as well or better protected by having the tank other than underground, then it shall be in such other location as may be approved in writing by the town council in the manner aforesaid. Any such approval may be rescinded at any time at the pleasure of the town council.
[Rev. Ords. 1989, § 5-43]
Filler pipes shall not be less than 1 1/4 inches in diameter
and located outside of the building, and shall be provided with a
screw plug or cap and kept securely locked when not in use.
[Rev. Ords. 1989, § 5-44]
Vent pipes shall not be less than one inch in diameter. They
shall be carried to a point not less than 12 feet above the ground
level at the filling point. They shall terminate not less than five
feet from any door or window opening. They shall be fitted with an
approved weather hood screened with a noncorrosive wire screen, not
coarser than no. 30 mesh.
[Rev. Ords. 1989, § 5-45]
It shall be the duty of the fire chief to enforce the provisions
of this article and such rules and regulations as may be prescribed
by the town council for the safety of the inhabitants. All violations
shall be reported for prosecution.
[Rev. Ords. 1989, § 5-46]
Nothing in this article shall apply to the storage of naphtha,
benzine, gasoline or other hydrocarbon in tanks or vehicles using
the same for fuel or motive power.