Any tanks used for the storage of gasoline, oil or other flammable
liquid in excess of 60 gallons, any portion of which have been installed
above ground level, shall have constructed under said tank or tanks
a dike or other means to prevent discharge of liquid. Where a diked
enclosure is required under this section, it shall have a capacity
not less than that of the tank or tanks served by the enclosure.
[Amended 4-10-2014 by L.L. No. 3-2014]
Failure to comply with any of the provisions of this chapter
shall be deemed a violation and the violator shall be punished as
set forth on the Village of Dryden Fine Schedule, which Fine Schedule
may be established by resolution and thereafter amended from time
to time by resolution of the Village Board of Trustees.