[Ord. No. 1384 § 1, 7-20-1987; Ord. No. 1686 § 1, 7-20-1992; Ord.
No. 1846 § 1, 3-20-1995; Ord. No. 2044 § 1, 11-16-1998; Ord. No. 2466 § 1, 6-18-2007; Ord. No. 2681 § 1, 4-16-2012; Ord. No. 2771 § 1, 6-16-2014; Ord. No. 2949, 3-19-2018]
A certain document, one (1) copy of which is on file in the office of the City Clerk of the City of Centralia, Missouri, being marked and designated as the "International Residential Code for One- and Two-Family Dwellings — 2015 Edition," as published by the International Code Council, be and is hereby adopted as the Residential Building Code of the City of Centralia, Missouri, for the control of residential structures as provided herein; and each and all of the regulations, provisions, penalties, conditions and terms of such "International Residential Code for One- and Two-Family Dwellings — 2015 Edition," published by the International Code Council, on file in the office of the City Clerk of the City of Centralia, Missouri, are hereby referred to, adopted and made a part hereof as if fully set out in this Chapter, with the additions, insertions, deletions and changes as hereinafter prescribed in Section
5-37.
[Ord. No. 1384 § 1, 7-20-1987; Ord. No. 1486 § 5, 6-19-1989; Ord.
No. 1686 § 2, 7-20-1992; Ord. No. 1846 § 2, 3-20-1995; Ord.
No. 2044 § 2, 11-16-1998; Ord. No. 2466 § 1, 6-18-2007; Ord.
No. 2681 § 1, 4-16-2012; Ord. No. 2707 § 3, 11-19-2012; Ord. No. 2771 § 1, 6-16-2014; Ord. No. 2949, 3-19-2018]
The International Residential Code for One- and Two-Family Dwellings
— 2015 Edition is amended by additions, deletions, and changes
including the changing of Articles, Sections, Subsections, Subsection
Titles, and the addition of new Sections and new Subsections to read
as follows:
1. Add Section R100.1:
Wherever (name of jurisdiction) appears in this code, it shall
read "City of Centralia, Missouri."
2. Add Section R100.1.1:
Wherever "Department of Building Safety" appears in this code,
it shall read "Department of Resource Management of Boone County,
Missouri."
3. Add Section R100.1.2:
Wherever "Chief Appointing Authority of the Jurisdiction" appears
in this Code, it shall read "Mayor of the City of Centralia, Missouri,
with the advice and consent of a majority of the members of the Board
of Aldermen of the City of Centralia, Missouri.
4. Delete Section R101.1 and add:
R101.1 Title: These provision shall be known as the "Residential
Code for One- and Two-Family Dwellings of the City of Centralia, Missouri,"
and shall be cited as such and will be referred to herein as "this
code."
5. Delete Section R101.2 and add:
R101.2 Scope. The provisions of the International Residential
Code for One- and Two-Family Dwellings shall apply to the construction,
alteration, movement, enlargement, replacement, repair, equipment,
use and occupancy, location and removal of detached one- and two-family
dwelling and multiple single-family dwellings (townhouses) not more
than three (3) stories in height with a separate means of egress and
their accessory structures.
Note: the provisions of this code do not apply to agricultural
buildings or structures. Where the construction of agricultural buildings
or structures requires a building permit, such structures shall be
designed and built in accordance with the provisions of the International
Building Code or other standards approved by the Code Official.
6. Delete Section R103 in its entirety and add:
SECTION R103 RESOURCE MANAGEMENT DEPARTMENT
R103.1 Enforcement Authority. The Resource Management Department
previously created by the Boone County Commission is the enforcement
agency for this code and the executive official in charge thereof
shall be known as the Building Official or the Code Official.
R103.2 Appointments. The Director of Resource Management shall
be appointed by the Boone County Commission.
R103.3 Deputies. In accordance with the prescribed procedures
of Boone County and with the concurrence of the Boone County Commission,
the Director of Resource Management shall have the authority to appoint
a Deputy Building Official, and related technical officers, inspectors,
plan examiners and other employees. Such employees shall have the
powers as delegated by the Building Official.
7. Delete Section R104.10.1 and add:
Areas prone to flooding. The Code Official shall not grant modifications to any provisions related to areas prone to flooding as established by Table R301.2(1) without the granting of a variance to such provisions under Chapter
12 of the Centralia City Code.
8. Delete Section R105.2(1) and add:
(1)
|
One (1) story detached accessory structures, provided the floor area does not exceed one hundred sixty (160) square feet. Such buildings must comply with all setback requirements found in Chapter 31 of the Centralia City Code. Such buildings used to house hazardous materials (paint, gasoline, etc.) must be placed at least ten (10) feet from any property line and have a door that can be secured by a lock.
|
9. Delete Section R105.2(2) and add:
(2)
|
Fences not over twelve (12) feet high.
|
10. Delete Section R106.1 and add:
R106.1 Submittal documents. Construction documents, special
inspection and structural observation programs, and other data may
be required to be submitted on one (1) or more sets with each application
for a permit. The construction documents shall be prepared by a registered
design professional where required by the Statutes of the jurisdiction
in which the project is be constructed. Where special conditions exist,
the Code Official is authorized to require additional construction
documents to be prepared by a registered design professional.
14. Delete Section R113.4 and add:
R113.4 Violation penalties. Any person who shall violate a provision
of this code or shall fail to comply with any of the requirements
thereof or who shall erect, construct, alter or repair a building
or structure in violation of an approved plan or directive of the
Code Official or of a permit or certificate issued under the provisions
of the code, shall be guilty of an ordinance violation and, upon conviction,
shall be punished by a fine of from one dollar ($1.00) to not more
than five hundred dollars ($500.00). Each day that a violation continues
shall be deemed a separate offense.
15. In Section R202 delete the definition for "Accessory Structure" and
add:
ACCESSORY STRUCTURE. A structure not greater than three thousand
(3,000) square feet and not more than three (3) stories or exceeding
twenty-four (24) feet in height with separate means of egress, and
shall not exceed the height of the main structure, the use of which
is incidental to that of the main building and which is located on
the same parcel.
16. In Section R202 add new item four (4) to the definition for "Attic,
Habitable":
(4)
|
The occupiable space is provided with an egress door in accordance
with Section R311.2 or by a ramp in accordance with Section R311.8
or a stairway in accordance with Section R311.7.
|
17. In Table R301.2(1) insert the following values:
Ground Snow Load — 20 lbs./sq. ft.
Wind Speed — 90
Topographic Effects — No
Seismic Design Category — B
Weathering — Yes; Severe
Frost Line Depth — Yes; 30 inches
Termite — Moderate to Heavy
Decay — Slight to Moderate
Winter Design Temp — + 4_Fahrenheit
Ice Barrier Underlayment Required — No
Flood Hazards — 6-2-1975 and 2-2-2011 — dates
of adoption of flood regulations
3-17-2011 — date of Flood Insurance Rate Maps
Air Freezing Index — 0 to 1,000
Mean Annual Temperature — 55 Fahrenheit
18. In Table R301.5: Add note g.4: "Must also include a vertical egress
component."
19. Add new Section R301.9.
R301.9 Sediment Control. All sites are subject to providing
on-site sediment control structures to minimize to the maximum extent
practical the erosion of soil form the building site. Acceptable practices,
include, but are not limited to, use of silt fences, straw bales and
rock check dams. Failure to provide and maintain such sediment control
devises could result in inspections being withheld, issuance of a
stop work order or even revocation of the building permit.
20. In Section R302.1 add new exception 6:
6.
|
A detached accessory garage or shed located not less than three
(3) feet from any side lot line.
|
21. Delete exception to Section R302.2 and substitute:
Exception: A common two-hour fire-resistance rated wall assembly
tested in accordance with ASTME 119 or UE 263 is permitted for townhouses
if such walls do not contain plumbing or mechanical equipment, ducts
or vents in the cavity of the common wall. The wall shall be rated
for fire exposure from both sides and shall extend to and be tight
against exterior walls and the underside of the roof sheathing. Electrical
installations shall be installed in accordance with Chapter 34 through
43. Penetrations of electrical outlet boxes shall be in accordance
with Section R302.4.
22. Section R302.5.1: Delete "equipped with a self-closing device."
23. Section R302.6 Dwelling garage separation: Replace one-half (1/2)
inch gypsum board with five-eighths (5/8) inch gypsum board in referenced
Table R302.6 Dwelling/garage fire separation. Add last sentence to
paragraph of R302.6: The garage shall be completely separated from
the residence and its attic area by means of five-eighths (5/8) inch
gypsum board or equivalent applied to the garage side.
24. Section R303.4 Mechanical ventilation: Delete in its entirety and
add:
Section R303.4 Mechanical ventilation. The dwelling unit shall
be provided with whole-house mechanical ventilation in accordance
with Section M1507.3. Alternatively, an insulated cut from the outside
connected to the return air or HVAC unit ahead of the filter with
balancing damper may be provided. The duct size shall be based on
the conditioned area the HVAC unit serves. The duct size shall be
based on the conditioned area the HVAC unit serves. The duct shall
be four (4) inches diameter for areas one thousand five hundred (1,500)
square feet or less, six (6) inches diameter for areas over one thousand
five hundred (1,500) square feet and less than or equal to two thousand
four hundred (2,400) square feet, and eight (8) inches diameter for
areas over two thousand four hundred (2,400) square feet.
25. Section R303.6: Add Exception:
Exception: Bathroom exhaust fans may be exhausted into a soffit
vent if composed of approved materials as determined by the Code Official.
26. Add Section R307.3:
R307.3 Water closet: All water closets shall be spaced at least
fifteen (15) inches from the centerline of the fixture to any wall
or plumbing fixture, except the centerline of the water closet may
be spaced twelve (12) inches if located next to a bathtub.
27. Section R311.7.5.1 Risers: Delete the first sentence and add: The
maximum riser height shall be seven and three-fourth (7 3/4) inches
(200 mm).
The rest of the paragraph remains the same. Add Exception:
Exception: Closed risers are not required on exterior stairs
where the height is less than ten (10) feet above grade.
28. Section R312.2 Height. Delete in its entirety.
29. Section R313.1 Townhouse Automatic Fire Sprinkler Systems. Delete
in its entirety.
30. Section R313.2 One- and Two-Family Dwelling Automatic Fire Sprinkler
System. Delete in its entirety.
31. Delete Section R313 in its entirety and add:
R313 Automatic Fire Sprinkler System. A builder of a single-family
dwelling or residences or multi-unit dwelling of four (4) or fewer
units shall offer to any purchaser on or before the time of entering
into the purchase contract the option at the purchaser's cost
to install or equip an automatic fire sprinkler system in the dwelling,
residence or unit. Notwithstanding any provision of law to the contrary,
no purchaser of such a single-family dwelling, residence, or multi-unit
dwelling shall be denied the right to choose or decline to install
an automatic fire sprinkler system in such dwelling or residence being
purchased by any code, ordinance, rule, regulations, order or resolution
by any county or other political subdivision. Any county or other
political subdivision shall provide in any such code, ordinance, rule,
regulations, order or resolution the mandatory option for purchasers
to have the right to choose and the requirement that the builders
offer to purchasers the option to purchase an automatic fire sprinkler
system in connection with the purchase of any single-family dwelling,
residence, or multi-family dwelling of four (4) or fewer units.
32. Delete Section R315.2 in its entirety and add:
R315.2 When required in existing dwellings. Where work requiring
a permit occurs inside an existing dwelling that has an attached garage
or inside an existing dwelling within which fuel-fired appliances
exist, a carbon monoxide alarm shall be provided in the immediate
vicinity of the bedrooms.
33. Section R322 Flood Resistant construction. Delete in its entirety. All construction must comply with Centralia City Code, Chapter
12 Flood Regulations.
34. Amend Table R401.4.1 PRESUMPTIVE LOAD-BEARING VALUES OF FOUNDATION
MATERIALS: Load-bearing Pressure (pounds per square foot) column,
change values for clay, sandy clay, silty clay, clayey silt, silt
and sandy silt (CL, ML, MH and CH) from one thousand five hundred
(1,500) to two thousand (2,000), leaving footnote b.
35. Amend Figure R403.1(1) Concrete and Masonry Foundation Details:
A monolithic slab with integral footing shall have the following:
a #4 reinforcement bar spaced a minimum of forty-eight (48) inches
on centers to provide connection of footing to slab. The vertical
rods shall extend to within four (4) inches of the bottom of the footing
and be turned to provide a horizontal leg that extends a minimum of
twelve (12) inches into the slab.
36. Section R403.3 Frost-protected shallow foundations. Delete in its
entirety.
37. For Section R404.1 Concrete and masonry foundation walls. Add additional
paragraph:
Drawings showing options labeled as Drawing 1.1, 1.2, 1.3, 1.4,
2.1, 2.2, 3.1 and 3.2 are intended to be alternative methods to comply
with lateral support of foundation walls and subsections for connection
of foundation to floor; and option labeled as Drawing 4 is intended
to be in compliance with subsections for reinforcement in walls and
connection of foundation walls to floor.
NOTE: Drawings as stated above are on file in the office of
the Building Official.
38. For Section R404.4 Retaining Walls: Change twenty-four (24) inches
(610 mm) to read forty-eight (48) inches (1,219 mm); rest of the paragraph
remains as stated.
39. Delete Section R405.1 Concrete or masonry foundations and add:
Section R405.1 Concrete or masonry foundations. Drains shall
be provided around all concrete or masonry foundations that retain
earth and enclose habitable or usable spaces located below grade.
Drainage tiles, gravel or crushed stone drains, shall be installed
at or below the area to be protected and shall discharge by gravity
or mechanical means into an approved drainage system. Gravel or crushed
stone drains shall extend at least one (1) foot (305 mm) beyond the
outside edge of the footing and six (6) inches (152 mm) above the
top of the footing and be covered with an approved filter membrane
material and shall include a drain tile pipe as shown in Figure R405.1.
The drain pipe can be placed directly on top of the footing. The top
of open joints of the drainage tiles or perforated pipe shall be protected
with strips of building paper, and the drainage tiles or perforated
pipe shall be placed directly on the top of the footing or placed
on a minimum of two (2) inches (51 mm) of washed gravel or crushed
rock at least one (1) size larger than the tile joint opening or perforation
and covered with not less than six (6) inches (152 mm) of the same
material. Foundation Drainage Figure R405.1 as adopted, shall be considered
to satisfy the provision of this Subsection.
NOTE: Foundation Figure R405.1 as stated above is on file in
the office of the Building Official.
40. Delete the first paragraph of Section R502.11.4 and add:
Truss design drawings. Truss design drawings, prepared in compliance
with Section R502.11.1 shall be available on-site at the time of inspection
and shall be provided to the Building Official at that time. Truss
design drawing shall be provided with the shipment of trusses delivered
to the job site. Truss design drawings shall include, at a minimum,
the information specified below: (remainder of Section unchanged).
41. After the last line of Section R802.3.1 add:
Rafter ties shall be spaced not more than four (4) feet (1,219
mm) on center.
42. Delete Section N1102.1 and add:
Section N1102.1 Insulation and fenestration criteria. The building
thermal envelope shall meet the requirements listed below.
43. Replace Table N1102.1 INSULATION AND FENESTRATION REQUIREMENTS BY
COMPONENT with:
BUILDING AREA AND REQUIRED INSULATION VALUE
|
---|
1.
|
Ceiling or roof — R-38.
|
2.
|
Exterior wall — R-15.5 for the assembly.
|
3.
|
Floor above unheated area or crawl space and ducts in ventilated
attic or crawl space — R-19
|
4.
|
Walls separating one- and two-family dwellings form garage areas,
walls facing ventilated attic spaces and finished exterior basement
walls — R-13.
|
5.
|
All windows shall have a maximum Thermal Transmittance (U) value
of 0.35.
|
6.
|
Skylights shall have a maximum U-0.60.
|
7.
|
M Wall — R-5, or R-10 when more than half the insulation
is on the interior.
|
8.
|
Basement walls or crawl space walls — R-10 if continuous
insulation, or R-13 if framing cavity insulation.
|
9.
|
All slab-on-grade with embedded heating systems must have a
minimum of R-5 insulation installed beneath the slab. Insulation shall
have a sufficient compressive strength to bear the weight of the structure
and be of a type approved for underground installation. Insulation
shall be required under the full heated area of the slab, except where
the slab bears on footings, and within twelve (12) inches of any opening
in the slab to the interior space.
|
10.
|
All exterior walls shall have a vapor retarder, capable of reducing
vapor transmission to less than one (1) perm, installed on the inside
of the warm surface side of the insulated wall or ceiling. Only those
ceilings that are attached directly to the underside of the roof rafters,
such as flat roofs or cathedral ceilings, are required to install
the vapor retarder.
|
44. Delete Section N1102.2.9 Slab-on-grade floors.
45. Amend Table N1102.4.2 Air Barrier and insulation inspection as follows:
Under heading "component," line item for "recessed lighting,"
in criteria column remove the word "airtight."
46. Delete last sentence of Section N1103.1.1 Programmable thermostat
and add:
The thermostat should initially be programmed with a heating
temperature set point no higher than 70° F. (21° C.) and a
cooling temperature set point no lower than 78° F. (26° C.).
47. Delete Section N1103.2.2 Sealing and add:
N1103.2 Sealing. Ducts, air handlers, filter boxes and building
cavities used as ducts shall be sealed. Joints and seams shall comply
with Section M1601.4
Exception: duct tightness is not required if the air handler
and all ducts are located within conditioned space.
48. Delete Section N1104.1 Lighting equipment and add:
N1104.1 Lighting equipment: A minimum of fifty percent (50%)
of the lamps in permanently installed lighting fixtures should be
high efficiency lamps.
49. Section M1411.3.1 Auxiliary and secondary drain systems: Add the
following sentences to the end of paragraph #3:
Only one (1) water level detection device conforming to UL 508
that will shut off the equipment served prior to overflow of the pan
is required by this Section.
50. Amend Section M1501.1 Outdoor discharge delete exception and add:
Exception No. 1: Whole-house ventilation-type attic fans that
discharge into the attic space of dwelling units having private attics
shall be permitted.
Exception No. 2: Air may be discharged into a soffit vent if
composed of approved materials as determined by the Building Official.
51. Section M1506.2 Recirculation of air add exception:
Exception: Air may be exhausted into a soffit vent if composed
of approved materials as determined by the Building Official.
52. Section M2103.2.2 Suspended floor installations add exception:
Exception: For direct contact plate systems, no insulation is
required as long as space below is habitable.
53. Delete Section G2414.5.2 and add:
Copper tubing: Copper tubing shall comply with standard Type
K or L of ASTM B 88 or ASTM B 280.
Copper and brass tubing shall not be used if the gas contains
more than an average of three tenths (0.3) grains of hydrogen sulfide
per one hundred (100) standard cubic feet of gas (0.7 milligrams per
100 liters). Natural gas supplied by Ameren UE in Boone County exceeds
this level; therefore, copper or brass shall not be used with natural
gas.
54. Section G2415.12 add to end of paragraph:
Any underground gas piping allowed by this Section shall only
be approved for gas that is less dense than the atmospheric pressure
and shall be installed in accordance with G2415.12.1.
55. Delete Section G2415.12.2 in its entirety.
56. Delete first sentences of Section G2417.4.1 Test pressure and add:
G2417.4.1 Test pressure. The test pressure to be used shall
be not less than one and one-half (1.5) times the proposed maximum
working pressure, but not less than thirty (30) psig, irrespective
of design pressure. (Rest of Section remains as stated.)
57. Section G2417.1 Sediment trap. Change "any length" to "three and
one-half (3 1/2) inch minimum."
58. Add Section P2602.1.1:
P2602.1.1 Public water supply. A public water supply is considered
available if a lot is within three hundred (300) feet of a public
water main to which connection is practical and is permitted by the
governmental agency or utility responsible for the water main.
59. Add Section P2602.1.2:
P2602.1.2 Public sewer system. A public sewer system is considered
available if a lot is within two hundred twenty-five (225) feet of
a sanitary sewer system to which connection is practical and is permitted
by the governmental agency or utility responsible for the sanitary
sewer.
60. Delete Section P2603.6 Freezing in its entirety and add:
P2603.6 Freezing. A water, soil or waste pipe shall not be installed
outside of a building, or concealed in outside walls, or in any place
subjected to freezing temperature, unless adequate provision is made
to protect such pipe from freezing by insulation, heat or both. Water
pipes shall not be installed in an exterior wall cavity in one- and
two-family dwellings. For purposes of this Section exterior wall cavities
shall mean all walls that rain can fall upon. Water service piping
shall be installed below recorded frost penetration but not less than
thirty (30) inches below grade.
61. Delete Section P2603.6.1 and add:
P2603.6.1 Sewer depth. Building sewers that connect to private
sewage disposal systems shall be a minimum of thirty (30) inches below
finished grade at the point of septic tank connection. Building sewers
shall be a minimum of thirty (30) inches below grade.
62. Section P2604.3 Backfilling delete last sentence which reads: "Loose
earth shall be carefully placed in the trench in six (6) inch (152
mm) layers and tamped in place."
63. Amend first sentence of Section P2705.1 Water closets, lavatories
and bidets. #5 to read:
All water closets shall be spaced fifteen (15) inches from the
centerline of the fixture to any wall or plumbing fixture except the
centerline of the water closet may be spaced twelve (12) inches if
located next to the bathtub. (Rest of the paragraph remains as stated.)
64. Section P2903.5 Water hammer add exception:
Exception: A water-hammer arrester is not needed in water distribution
systems using PEX piping or systems using a combination of PEX and
copper.
65. Amend Section P2905.4 Water service pipe as follows:
Where this Section references one hundred sixty (160) pounds
per square inch replace with two hundred (200) pounds per square inch.
66. Section P2905.9.1.3 PVC plastic pipe. Delete in its entirety and
add:
Section P2905.9.1.3 PVC plastic pipe. A primer than conforms
to ASTM F 656 shall be applied to PVC solvent-cemented joints. Purple
primer shall be used below grade. Solvent cement for PVC plastic pipe
conforming to ASTM D 2564 shall be applied to all joint surfaces.
If purple primer is used, Section P2503 Inspections and Tests shall
not be required.
67. Amend first sentence of Section P3005.2.4 change of direction to
read:
Cleanouts shall be installed at each fitting with a change of
direction more than forty-five degrees (45°) (0.79 rad) horizontal
to horizontal in the building sewer, building drain and horizontal
waste or soil lines. (Rest of paragraph remains as stated.)
68. Section P3111.1 Type of fixtures, add exception:
Exception: Residential food waste grinders shall be allowed
to discharge into a combination waste and vent system provided an
air admittance valve is installed.
69. Section P3113.1 Size of vents. Add sentence at end of paragraph as
follows:
At least one (1) vent shall be three (3) inch unreduced in size
extending from the main building drain through the roof.
70. Delete Section P3201.2 Trap seals and trap seal protection.
71. Except as stated in Sections E3608.1.1 Exception, E3609.6.1 and E3609.7
of this ordinance, Chapters 34 through 43 of the International Residential
Code are superseded by the requirements as stated in the 2011 National
Electrical Code (NFP 70-2011).
72. Section E3608.1.1 Installation. Add exception:
E3608.1.1 Exception: When a concrete-encased electrode and/or
ground ring are not available for use in a grounding electrode system,
a rod or other electrode as specified in E3608.1.4 Rod and pipe electrodes
and E3608.1.5 Plate electrodes can be used as a substitute. The second
rod electrode shall not be connected in series with the first rod
electrode except where there exists a metal water pipe in contact
with earth for ten (10) feet or more, for one- and two-family dwellings
a single grounding electrode placed at the outside of the building
at the nearest point of the service disconnect shall be permitted
to fill the requirements of this Section.
73. Add Section E3609.6.1 Water heater bonding jumper to read:
E3609.6.1. Water heater bonding jumper. The interior metal water
piping bonding shall include a bonding jumper between the hot and
cold waterlines at the water heater fixture if the entire system is
copper, excluding the service.
74. Amend Section E3609.7 Bonding other metal piping by deleting "including
gas piping" from Section.
75. Delete Section E3902.12 Arc-fault circuit interrupter protection.
76. Delete Section E3902.13 Arc-fault circuit-interrupter protection
for branch circuit extensions or modifications.
77. Appendix G SWIMMING POOLS, SPAS AND HOT TUBS is adopted with the
following amendments:
(A)
|
Delete Section AG105.1 and add:
|
|
Application: The provisions of this Chapter shall control the
design of barriers for residential swimming pools, spas and hot tubs.
These design controls are intended to provide protection against potential
drowning and near-drowning by restricting access to swimming pools,
spas and hot tubs. Barriers are to be constructed of metal chain link
fence, wood, stone or masonry or other material approved by the Code
Official.
|
(B)
|
Add Section AG105.2.11 to read:
|
|
AG105.2.11 All swimming pool excavation sites are required to
be enclosed by a temporary construction barrier during installation.
Any temporary construction barrier shall comply with the design standards
of Section AG105.2. A permanent barrier shall be installed upon completion
of the pool structure.
|