903.2.1.1. Group A-1. An automatic sprinkler system shall be
provided for Group A-1 occupancies where one of the following conditions
exist:
| |
1. The fire area exceeds 8,000 square feet;
| |
2. The fire area has an occupant load of 300 or
more;
| |
3. The fire area is located on a floor other than
the level of exit discharge; or
| |
4. The fire area contains a multi-theater complex.
| |
903.2.1.3. Group A-3. An automatic sprinkler system shall be
provided for Group A-3 occupancies where one of the following conditions
exist:
| |
1. The fire area exceeds 8,000 square feet;
| |
2. The fire area has an occupant load of 300 or
more; or
| |
3. The fire area is located on a floor other than
the level of exit discharge.
| |
903.2.3. Group F-1. An automatic sprinkler system shall be provided
throughout all buildings containing a Group F-1 occupancy where one
of the following conditions exist:
| |
1. Where a Group F-1 fire area exceeds 8,000 square
feet;
| |
2. Where a Group F-1 fire area is located more than
three stories above grade; or
| |
3. Where the combined area of all Group F-1 fire
areas on all floors, including any mezzanines, exceeds 24,000 square
feet.
| |
903.2.6. Group M. An automatic sprinkler system shall be provided
throughout buildings containing a Group M occupancy where one of the
following conditions exist:
| |
1. Where a Group M fire area exceeds 8,000 square
feet;
| |
2. Where a Group M fire area is located more than
three stories above grade; or
| |
3. Where the combined area of all Group M fire areas
on all floors, including any mezzanines, exceeds 24,000 square feet.
|