[1]
Cross References: Fire prevention code, § 500.095; electrical distribution system in mobile home parks, § 410.300 et seq.
[R.O. 1996 § 500.120; CC 1990 § 5-61; Ord. No. 885 § 5-61, 1-24-1994; Ord. No. 1151 § 1, 12-8-1997; Ord. No. 1468, 2-25-2002; Ord. No. 1697, 12-27-2004; Ord. No. 1699, 12-27-2004; Ord. No. 1942, 1-14-2008; Ord. No. 2271 § 1, 12-3-2012; Ord. No. 2550, 7-26-2021]
A. 
Adopt the 2017 National Electrical Code and supplements published by the National Fire Protection Association for all construction other than one- and two-family residential for use May 1, 2021.
B. 
Appendix Chapters to be adopted: Annex H.
1. 
Delete Annex H Section 80.2, Chief Electrical Inspector, and Electrical Inspector. Refer to Section 103.1 of the 2012 International Building Code.
2. 
Delete Annex H Section 80.13(13), delete question of ___ days and insert "24 hours."
3. 
Delete Annex H Section 80.15 in its entirety.
4. 
In Annex H Section 80.25(B) Special Considerations. Change last sentence to read, "the Building Official, or his/her authorized representative, shall determine what needs are permitted under this provision."
5. 
Delete Section Annex H 80.27 Inspector's Qualifications in its entirety.
C. 
Amendments. Sections listed below are to be deleted.
1. 
Article 210.2 Arc-Fault Circuit-Interrupted Protection.
2. 
Section 210.8(A)(5). Unfinished portions or areas of the basement not intended as habitable rooms is hereby amended to read as follows. All 125-volt, single phase 15- and 20-ampere receptacles installed in unfinished basements shall have ground fault circuit interrupter protection for personnel. For the purposes of this Section, unfinished basements are defined as portions or areas of the basement not intended as habitable rooms and limited to storage areas, work areas, and the like.
Exceptions:
I. 
Receptacles that are not readily accessible such as ceiling mounted receptacles for a garage door opener.
II. 
A single receptacle supplied by a dedicated branch circuit that is located and identified for a specific use by a cord-and-plug-connected appliance such as a refrigerator, freezer or sump pump.
III. 
A receptacle supplying only a permanently installed fire alarm or burglar alarm system.
3. 
Section 230.70(A)(1) is hereby amended to read as follows. The service disconnecting means shall be installed at a readily accessible location either outside of a building or inside nearest the point of entrance of the service conductors. When service entrance conductors are more than ten (10) feet in length from the point of entry to the service panel, a separate means of disconnect must be installed at the service cable entrance to the building or structure.
[R.O. 1996 § 500.130; Ord. No. 1474, 2-25-2002; Ord. No. 1942, 1-14-2008; Ord. No. 2271 § 1, 12-3-2012]
A. 
Adopt the 2012 International Electrical Code (administrative provisions) and supplements published by the International Code Council for all construction other than one- and two-family residential for use January 1, 2013.
B. 
Appendix Chapters to be adopted: None.
C. 
Amendments. Sections listed below are to be inserted in place of published Sections.
Section 302.10 Violation Penalties. Any person(s) found in violation of this code shall be guilty of an ordinance violation and subject to punishment in Section 100.110 of the Code of the City of Grain Valley.
[1]
Editor's Note: This Section 500.130, which previously contained exceptions to the 1999 electrical code adoption, was superseded by the material now set out in Section 500.120. At the editor's discretion, Ord. No. 1474 was included herein. Former Section 500.130 derived from CC 1990 § 5-62; Ord. No. 885 § 5-62, 1-24-90.