[1]
Cross Reference: Fire prevention code, § 500.095 et seq.
[R.O. 1996 § 500.080; CC 1990 § 5-41; Ord. No. 885 § 5-41, 1-24-1994; Ord. No. 1151 § 1, 12-8-1997; Ord. No. 1466, 2-25-2002; Ord. No. 1698, 12-27-2004; Ord. No. 1880 §§ 1 — 3, 2-12-2007; Ord. No. 1931, 12-10-2007; Ord. No. 2271 § 1, 12-3-2012; Ord. No. 2550, 7-26-2021]
A. 
Adopt the 2018 International Building Code and supplements published by the International Code Council for all construction other than one- and two-family residential for use May 1, 2021.
B. 
Appendix Chapters to be adopted: B, C, E, F, G, I, J.
C. 
Amendments. Sections listed below are to be inserted in place of published Sections.
1. 
Section 109.2 Schedule of Fees. Fees for all building, sign, demolition or other permits required within shall be set forth in Section 140.050 of the Code of the City of Grain Valley. A separate plan review fee shall be assessed on all commercial construction as set forth in Section 140.050 of the Code.
2. 
Section 109.4 Work Commencing Before Permit Issuance. Any person who commences work on any project that requires a permit before the permit is issued will be assessed a double permit fee.
3. 
Section 114.4 Violation Penalties. Any person(s) found in violation of this code shall be guilty of an ordinance violation and subject to punishment in Section 100.110 of the Code of the City of Grain Valley.
4. 
Section 423.4 Storm Shelters is hereby amended to add the following language. Exception 4. Group E occupancies that undergo alterations or additions where the cost of compliance with ICC 500 Section 702 is greater than twenty percent (20%) of the total project cost may omit the requirements of ICC 500 Section 702 only.
5. 
Section 501.2 Premises Identification is hereby amended to add the following language. In multi-tenant commercial buildings where tenants have multiple entrances located on different sides of the building, each door shall be addressed. Address characters shall be capable of being illuminated by an internal or external lighting source.
6. 
Section 901.5 Acceptance Test is hereby amended to read as follows. Fire detection and alarm systems, fire extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurtenances thereto shall be subject to acceptances test(s) as contained in the installation standards and as approved by the Building Official or his/her agent. The Building Department shall be notified twenty-four (24) hours before any required acceptance testing.
7. 
Section 903.2.4 Group F is hereby amended to read as follows. An automatic sprinkler system shall be provided throughout all buildings containing a Group F-1 occupancy where one (1) of the following conditions exists:
1) 
A Group F-1 fire area exceeds twelve thousand (12,000) square feet (1,115 m2).
2) 
A Group F-1 fire area is located more than two (2) stories above grade plane.
3) 
The combined area of all Group F-1 fire areas on all floors, including any mezzanines, exceeds twenty-four thousand (24,000) square feet (2,230 m2).
4) 
A Group F-1 occupancy used for the manufacture of upholstered furniture or mattresses exceeds two thousand five hundred (2,500) square feet (232 m2).
8. 
Section 903.2.7 Group M is hereby amended to read as follows. An automatic sprinkler system shall be provided throughout buildings containing a Group M occupancy where one (1) of the following conditions exists:
1) 
A Group M fire area exceeds twelve thousand (12,000) square feet (1,115 m2).
2) 
A Group M fire area is located more than two (2) stories above grade plane.
3) 
The combined area of all Group M fire areas on all floors, including any mezzanines, exceeds twenty-four thousand (24,000) square feet (2,230 m2).
4) 
A Group M occupancy used for display and sale of upholstered furniture or mattresses exceeds five thousand (5,000) square feet (464 m2).
9. 
Section 903.2.9 Group S-1 is hereby amended to read as follows. An automatic sprinkler system shall be provided throughout all buildings containing a Group S-1 occupancy where one (1) of the following conditions exists:
1) 
Where a Group S-1 fire area exceeds twelve thousand (12,000) square feet (1,115 m2).
2) 
A Group S-1 fire area is located more than two (2) stories above grade.
3) 
The combined area of all Group S-1 fire areas on all floors, including any mezzanines, exceeds twenty-four thousand (24,000) square feet (2,230 m2).
4) 
A Group S-1 fire area is used for the storage of commercial trucks or buses where the fire area exceeds five thousand (5,000) square feet (464 m2).
5) 
A Group S-1 fire area used for the storage of upholstered furniture or mattresses exceeds two thousand five hundred (2,500) square feet (232 m2).
10. 
Section 903.2.9.1 Repair Garages is here by amended to read as follows. An automatic sprinkler system shall be provided throughout all buildings used as repair garages in accordance with Section 406, as shown.
1) 
Buildings two (2) or more stories in height, including basements, with a fire area containing a repair garage exceeding five thousand (5,000) square feet (464 m2)
2) 
Buildings no more than one (1) story above grade plane with a fire area containing a repair garage exceeding five thousand (5,000) square feet (464 m2).
3) 
Buildings with a repair garage servicing vehicles parked in basements.
4) 
A Group S-1 fire area used for the repair of commercial trucks or buses where the fire area exceeds five thousand (5,000) square feet (464 m2).
11. 
Section 903.2.11.3 Buildings Fifty-Five (55) Feet Or More In Height is hereby amended to read as follow. Building more than two (2) stories in height. An automatic sprinkler system shall be installed throughout buildings with a floor level more than two (2) stories above the lowest level of Fire Department vehicle access.
Exceptions.
1) 
Open parking garages.
12. 
Section 903.3.7 Fire Department Connection is hereby added to read as follows. The location of Fire Department connections shall be approved by the Fire Code Official. Connections shall be five-inch Storz type fittings and located within one hundred (100) feet of a fire hydrant, or as approved by the Fire Code Official.
13. 
Section 903.4.2 Alarms is hereby amended to read as follows. One (1) all-weather horn/strobe shall be connected to every automatic sprinkler system on the exterior of the building in an approved location. Such sprinkler water-flow alarm devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. Where a fire alarm system is installed, actuation of the automatic sprinkler system shall actuate the building fire alarm system. Interior alarm notification appliances shall be installed as required.
14. 
Section 905.3 Required Installations is hereby amended to read as follows. Standpipe systems shall be provided in new buildings and structures in accordance with Sections 905.2 through 905.11, and as required by the Fire Code Official. In buildings used for high-piled combustible storage, fire protection shall be in accordance with Chapter 32 of the 2018 International Fire Code.
15. 
Section 907.2.7.1 Occupant Notification is hereby amended to read as follows. During times that the building is occupied, the initiation of a signal from a manual fire alarm box or from a water flow switch shall not be required to activate the alarm notification appliances when an alarm signal is activated at a constantly attended location from which evacuation instructions shall be initiated over an emergency voice/alarm communication system installed in accordance with Section 907.5.2.2 and only when approved by the Fire Code Official.
16. 
Section 912.2 Location is hereby amended to read as follows. With respect to hydrants, driveways, buildings and landscaping, Fire Department connections shall be so located that fire apparatus and hose connected to supply the system will not obstruct access to the buildings for other fire apparatus. The location of Fire Department connections shall be within one hundred (100) feet of an approved fire hydrant or as approved by the Fire Code Official.
17. 
Section 1010.1.9 Locks and Latches is hereby amended to read as follows. Egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
Exceptions:
I. 
Places of detention or restraint.
II. 
Where egress doors are used in pairs, approved automatic flush bolts shall be permitted to be used, provided that the door leaf having the automatic flush bolts has no doorknob or surface-mounted hardware. The unlatching of any leaf shall not require more than one (1) operation.
III. 
Doors for individual dwelling units and guest rooms of Group P occupancies having an occupant load of ten (10) or less are permitted to be equipped with a night latch, dead bolt or security chain, provided such devices are openable from the inside without the use of key or tool.
18. 
Section 1015.2 Where Required is hereby amended to add the following. Guards are required at retaining walls over thirty (30) inches above grade when walking surfaces are within thirty-six (36) inches of the high side of the retaining wall.
19. 
Chapter 13 Energy Efficiency is hereby deleted and replaced with the 2006 International Energy Conservation Code.
20. 
Table 1505.1 is hereby amended by deleting footnotes a, b and c.
21. 
Section 1505.5 Non-Classified Roofing is hereby deleted.
22. 
Section 1511.1 Reroofing is amended to add the following. Re-roofing includes any repairs of more than ten percent (10%) of the total roof covering in any three-year period. A repair of ten percent (10%) or less of the total roof covering in any three-year period may utilize approved roofing materials comparable to the existing roofing materials.
23. 
Section 1805.4 Subsoil Drainage System is amended to add the following. Where foundations retain earth and enclose habitable or usable space located below grade, drains shall be provided below the floor slab. Drainage tiles, perforated pipe or other approved systems or material shall be installed at or below the area(s) to be protected; shall be placed with positive or neutral slope to minimize the accumulation of deposits in the drainage system; and shall discharge by gravity or mechanical means to and approved stormwater drainage system. The under-slab drainage system shall be installed around the inner perimeter of the area(s) to be protected, or, in a manner that will provide adequate drainage for all area(s) to be protected and is approved by the Building Official. Interior under-slab drains installed on uncompacted fill material shall be supported by mechanical means which are adequately tied into the concrete slab to ensure proper drainage throughout the under-slab drain(s).
24. 
Section 3109 Swimming Pools/Spas/Hot Tubs shall be deleted.